SIMATIC S7-1200, CPU 1214C, COMPACT CPU, DC/DC/DC, ONBOARD I/O: 14 DI 24V DC; 10 DO 24 V DC; 2 AI 0 - 10V DC, POWER SUPPLY: DC 20.4 - 28.8 V DC, PROGRAM/DATA MEMORY: 50 KB |
General information |
Engineering with |
Programming package | STEP 7 V10.5 or higher |
Display |
integrated | No |
Supply voltage |
24 V DC | Yes |
permissible range, lower limit (DC) | 20.4 V |
permissible range, upper limit (DC) | 28.8 V |
Load voltage L+ |
Rated value (DC) | 24 V |
permissible range, lower limit (DC) | 20.4 V |
permissible range, upper limit (DC) | 28.8 V |
Input current |
Current consumption, max. | 1.5 A; 24 V DC |
Inrush current, max. | 12 A; at 28.8 V DC |
Encoder supply |
24 V encoder supply |
24 V | Permissible range: 20.4 to 28.8 V |
Output current |
Current output to backplane bus (DC 5 V), max. | 1600 mA; Max. 5 V DC for SM and CM |
Power losses |
Power loss, typ. | 12 W |
Memory |
Usable memory for user data | 50 kbyte |
Work memory |
integrated | 50 kbyte |
expandable | No |
Load memory |
integrated | 2 Mbyte |
expandable, max. | 24 Mbyte; with SIMATIC memory card |
Backup |
present | Yes; Entire project maintenance-free in the integral EEPROM |
without battery | Yes |
CPU processing times |
for bit operations, min. | 0.1 µs; / Operation |
for word operations, min. | 12 µs; / Operation |
for floating point arithmetic, min. | 18 µs; / Operation |
CPU-blocks |
Number of blocks (total) | DBs, FCs, FBs, counters and timers. The maximum number of addressable blocks ranges from 1 to 65535. There is no restriction, the entire working memory can be used |
OB |
Number, max. | Limited only by RAM for code |
Data areas and their retentivity |
retentive data area in total (incl. times, counters, flags), max. | 2048 byte |
Flag |
Number, max. | 8 kbyte; Size of bit memory address area |
Address area |
I/O address area |
I/O address area, overall | 1024 bytes for inputs / 1024 bytes for outputs |
Inputs | 1024 byte |
Outputs | 1024 byte |
Process image |
Inputs, adjustable | 1 kbyte |
Outputs, adjustable | 1 kbyte |
Hardware configuration |
Number of modules per system, max. | 3 comm. modules, 1 signal board, 8 signal modules |
Time of day |
Clock |
Hardware clock (real-time clock) | Yes |
Deviation per day, max. | +/- 60 s/month at 25 °C |
Backup time | 240 h; Typical |
Digital inputs |
Number/binary inputs | 14; integrated |
of which, inputs usable for technological functions | 6; HSC (High Speed Counting) |
integrated channels (DI) | 14 |
m/p-reading | Yes |
Input voltage |
Rated value, DC | 24 V |
for signal "0" | 5 V DC at 1 mA. |
for signal "1" | 15 VDC at 2.5 mA. |
Input current |
for signal "1", typ. | 1 mA |
Input delay (for rated value of input voltage) |
for standard inputs |
Parameterizable | 0.2, 0.4, 0.8, 1.6, 3.2, 6.4, and 12.8 ms, selectable in groups of four |
at "0" to "1", min. | 0.2 ms |
at "0" to "1", max. | 12.8 ms |
for interrupt inputs |
Parameterizable | Yes |
for counter/technological functions |
Parameterizable | Single phase : 3 at 100 kHz & 1 at 30 kHz, differential: 3 at 80 kHz & 1 at 30 kHz |
Cable length |
Cable length, shielded, max. | 500 m; 50 m for technological functions |
Cable length unshielded, max. | 300 m; For technological functions: No |
Digital outputs |
Number/binary outputs | 10 |
of which high-speed outputs | 2; 100 kHz Pulse Train Output |
integrated channels (DO) | 10 |
Functionality/short-circuit strength | No; to be provided externally |
Limitation of inductive shutdown voltage to | L+ (-48 V) |
Switching capacity of the outputs |
with resistive load, max. | 0.5 A |
on lamp load, max. | 5 W |
Output voltage |
for signal "1", min. | 20 V |
Output current |
for signal "1" rated value | 0.5 A |
for signal "0" residual current, max. | 0.1 mA |
Output delay with resistive load |
"0" to "1", max. | 1 µs |
"1" to "0", max. | 5 µs |
Switching frequency |
of the pulse outputs, with resistive load, max. | 100 kHz |
Cable length |
Cable length, shielded, max. | 500 m |
Cable length unshielded, max. | 150 m |
Analog inputs |
Integrated channels (AI) | 2; 0 to 10 V |
Number of analog inputs | 2 |
Input ranges |
Voltage | Yes |
Input ranges (rated values), voltages |
0 to +10 V | Yes |
Input resistance (0 to 10 V) | ≥100k ohms |
Cable length |
Cable length, shielded, max. | 100 m; twisted and shielded |
Analog outputs |
Cable length |
Cable length, shielded, max. | 100 m; Shielded, twisted wire pair |
Analog value creation |
Integrations and conversion time/ resolution per channel |
Resolution with overrange (bit including sign), max. | 10 bit |
Integration time, parameterizable | Yes |
Conversion time (per channel) | 625 µs |
Encoder |
Connectable encoders |
2-wire sensor | Yes |
1st interface |
Type of interface | PROFINET |
Physics | Ethernet |
Isolated | Yes |
Automatic detection of transmission speed | Yes |
Autonegotiation | Yes |
Autocrossing | Yes |
Functionality |
PROFINET IO Controller | Yes |
Communication functions |
S7 communication |
supported | Yes |
as server | Yes |
Open IE communication |
TCP/IP | Yes |
ISO-on-TCP (RFC1006) | Yes |
Web server |
supported | Yes |
User-defined websites | Yes |
Number of connections |
overall | 15; dynamically |
Test commissioning functions |
Status/control |
Status/control variable | Yes |
Variables | Inputs/outputs, memory bits, DBs, distributed I/Os, timers, counters |
Forcing |
Forcing | Yes |
Integrated Functions |
Number of counters | 6 |
Counter frequency (counter) max. | 100 kHz |
Frequency meter | Yes |
controlled positioning | Yes |
PID controller | Yes |
Number of alarm inputs | 4 |
Number of pulse outputs | 2 |
Limit frequency (pulse) | 100 kHz |
Galvanic isolation |
Galvanic isolation digital inputs |
Galvanic isolation digital inputs | No |
between the channels, in groups of | 1 |
Galvanic isolation digital outputs |
Galvanic isolation digital outputs | Yes |
between the channels | No |
between the channels, in groups of | 2 |
Permissible potential difference |
between different circuits | 500 V DC between 24 V DC and 5 V DC |
EMC |
Interference immunity against discharge of static electricity |
Interference immunity against discharge of static electricity acc. to IEC 61000-4-2 | Yes |
Test voltage at air discharge | 8 kV |
Test voltage at contact discharge | 6 kV |
Interference immunity to cable-borne interference |
on the supply lines acc. to IEC 61000-4-4 | Yes |
Interference immunity on signal lines acc. to IEC 61000-4-4 | Yes |
Surge immunity |
on the supply lines acc. to IEC 61000-4-5 | Yes |
Immunity against conducted interference induced by high-frequency fields |
Interference immunity against high-frequency radiation acc. to IEC 61000-4-6 | Yes |
Emission of radio interference acc. to EN 55 011 |
Emission of radio interferences acc. to EN 55 011 (limit class A) | Yes; Group 1 |
Emission of radio interference acc. to EN 55 011 (limit class B) | Yes; When appropriate measures are used to ensure compliance with the limits for Class B according to EN 55011 |
Degree and class of protection |
IP20 | Yes |
Standards, approvals, certificates |
CE mark | Yes |
cULus | Yes |
C-TICK | Yes |
FM approval | Yes |
Ambient conditions |
Operating temperature |
Min. | 0 °C |
max. | 55 °C |
vertical installation, min. | 0 °C |
vertical installation, max. | 45 °C |
horizontal installation, min. | 0 °C |
horizontal installation, max. | 55 °C |
Storage/transport temperature |
Min. | -40 °C |
max. | 70 °C |
Air pressure |
Operation, min. | 795 hPa |
Operation, max. | 1080 hPa |
Storage/transport, min. | 660 hPa |
Storage/transport, max. | 1080 hPa |
Relative humidity |
Operation, max. | 95 %; no condensation |
Vibrations |
Vibrations | 2G wall mounting, 1G DIN rail |
Operation, checked according to IEC 60068-2-6 | Yes |
Shock test |
checked according to IEC 60068-2-27 | Yes; IEC 68, Part 2-27 half-sine: strength of the shock 15 g (peak value), duration 11 ms |
Climatic and mechanical conditions for storage and transport |
Climatic conditions for storage and transport |
Free fall |
Drop height, max. (in packaging) | 0.3 m; five times, in dispatch package |
Temperature |
Permissible temperature range | -40 °C to +70 °C |
Mechanical and climatic conditions during operation |
Climatic conditions in operation |
Temperature |
Permissible temperature range | 0 °C to 55 °C horizontal installation 0 °C to 45 °C vertical installation |
Permissible temperature change | 5°C to 55°C, 3°C / minute |
Air pressure acc. to IEC 60068-2-13 |
Permissible air pressure | 1080 to 795 hPa |
Permissible operating height | -1000 to 2000 m |
Pollutant concentrations |
SO2 at RH < 60% without condensation | S02: < 0.5 ppm; H2S: < 0.1 ppm; RH < 60% condensation-free |
Configuration |
programming |
Programming language |
LAD | Yes |
FBD | Yes |
SCL | Yes |
Cycle time monitoring |
adjustable | Yes |
Dimensions |
Width | 110 mm |
Height | 100 mm |
Depth | 75 mm |
Weight |
Weight, approx. | 415 g |
Status | Jul 17, 2012 |