Your cart is empty

6ES7314-6CG03-0AB0 CPU314C-2DP, 24DI/16DO/4AI/2AO, 96 KB

Manufacturer:
SIEMENS
Weight:
0.68kg
Product Range:
Automation Systems

Product Information

SIMATIC S7-300, CPU 314C-2DP COMPACT CPU WITH MPI, 24 DI/16 DO, 4AI, 2AO, 1 PT100, 4 FAST COUNTERS (60 KHZ), INTEGRATED DP INTERFACE, INTEGRATED 24V DC POWER SUPPLY, 96 KBYTE WORKING MEMORY, FRONT CONNECTOR (2 X 40PIN) AND MICRO MEMORY CARD REQUIRED
General information
Hardware product version01
Firmware versionV2.6
[nicht versorgt: TAK_ABW067_001_000]
associated programming packageSTEP 7 V5.3 SP2 or higher with HW update
Supply voltage
24 V DCYes
permissible range, lower limit (DC)20.4 V
permissible range, upper limit (DC)28.8 V
External protection for supply cables (recommendation)Miniature circuit breaker, type C; min 2 A; miniature circuit breaker type B, min. 4 A
Load voltage L+
Rated value (DC)24 V
permissible range, lower limit (DC)20.4 V
permissible range, upper limit (DC)28.8 V
Digital inputs
Load voltage L+
Rated value (DC)24 V
Reverse polarity protectionYes
Digital outputs
Load voltage L+
Rated value (DC)24 V
Reverse polarity protectionNo
Analog outputs
Load voltage L+
Rated value (DC)24 V
Reverse polarity protectionYes
Input current
Current consumption (rated value)1000 mA
Current consumption (in no-load operation), typ.150 mA
Inrush current, typ.11 A
I²t0.7 A²·s
from supply voltage L+, max.1000 mA
Digital inputs
from load voltage L+ (without load), max.70 mA
Digital outputs
from load voltage L+, max.100 mA
Power losses
Power loss, typ.14 W
Memory
Work memory
integrated96 Kibyte
expandableNo
Load memory
pluggable (MMC)Yes
pluggable (MMC), max.8 Mbyte
Data management on MMC (after last programming), min.10 a
Backup
presentYes; Guaranteed by MMC (maintenance-free)
without batteryYes; Program and data
CPU processing times
for bit operations, min.0.1 µs
for bit operations, max.0.2 µs
for word operations, min.0.2 µs
for fixed point arithmetic, min.2 µs
for floating point arithmetic, min.3 µs
CPU-blocks
Number of blocks (total)1024; (DBs, FCs, FBs); the maximum number of loadable blocks can be reduced by the MMC used.
DB
Number, max.511; Number range: 1 to 511
Size, max.16 Kibyte
FB
Number, max.1024; Number range: 0 to 2047
Size, max.16 Kibyte
FC
Number, max.1024; Number range: 0 to 2047
Size, max.16 Kibyte
OB
Size, max.16 Kibyte
Number of free cycle OBs1; OB 1
Number of time alarm OBs1; OB 10
Number of delay alarm OBs1; OB 20
Number of time interrupt OBs1; OB 35
Number of process alarm OBs1; OB 40
Number of DPV1 alarm OBs3; OB 55, 56, 57
Number of startup OBs1; OB 100
Number of asynchronous error OBs5; OB 80, 82, 85, 86, 87
Number of synchronous error OBs2; OB 121, 122
Nesting depth
per priority class8
additional within an error OB4
Counters, timers and their retentivity
S7 counter
Number256
of which retentive without battery
adjustableYes
lower limit0
upper limit255
preset8
Retentivity
adjustableYes
lower limit0
upper limit255
preset8
Counting range
lower limit0
upper limit999
IEC counter
presentYes
TypeSFB
NumberUnlimited (limited only by RAM capacity)
S7 times
Number256
of which retentive without battery
adjustableYes
lower limit0
upper limit255
Retentivity
adjustableYes
lower limit0
upper limit255
presetNo retentivity
Time range
lower limit10 ms
upper limit9990 s
IEC timer
presentYes
TypeSFB
NumberUnlimited (limited only by RAM capacity)
Data areas and their retentivity
retentive data area, totalAll, max. 64 KB
Flag
Number, max.256 byte
Retentivity availableYes; MB 0 to MB 255
Retentivity presetMB 0 to MB 15
Number of clock memories8; 1 memory byte
Data blocks
Number, max.511; Number range: 1 to 511
Size, max.16 Kibyte
Retentivity adjustableYes; via non-retain property on DB
Retentivity presetYes
Local data
per priority class, max.510 byte
Address area
I/O address area
Inputs1 Kibyte
Outputs1 Kibyte
of which, distributed
Inputs979 byte
Outputs986 byte
Process image
Inputs128 byte
Outputs128 byte
Default addresses of the integrated channels
Digital inputs124,0 to 126,7
Digital outputs124.0 to 125.7
Analog inputs752 to 761
Analog outputs752 to 755
Digital channels
Inputs7856
Outputs7904
Inputs, of which central1016
Outputs, of which central1008
Analog channels
Inputs494
Outputs495
Inputs, of which central253
Outputs, of which central250
Hardware configuration
Racks, max.4
Modules per rack, max.8; In rack 3 max. 7
Expansion devices, max.3
Number of DP masters
integrated1
via CP4
Number of operable FMs and CPs (recommended)
FM8
CP, point-to-point8
CP, LAN10
Time of day
Clock
Hardware clock (real-time clock)Yes
battery-backed and synchronizableYes
Deviation per day, max.10 s
Backup time6 wk; At 40 °C ambient temperature
Operating hours counter
Number1
Number/Number range0
Range of values0 to 2^31 hours (when using SFC 101)
Granularity1 hour
retentiveYes; Must be restarted at each restart
Clock synchronization
supportedYes
to MPI, masterYes
to MPI, slaveYes
to DP, masterYes; With DP slave only slave clock
to DP, slaveYes
in AS, masterYes
Digital inputs
Number/binary inputs24
of which, inputs usable for technological functions16
integrated channels (DI)24
Input characteristic curve acc. to IEC 1131, Type 1Yes
Number of simultaneously controllable inputs
horizontal installation
up to 40 °C, max.24
up to 60 °C, max.12
vertical installation
up to 40 °C, max.12
Technological functions
shielded, max.50 m
Unshielded, max.not allowed
Standard DI
shielded, max.1000 m
Unshielded, max.600 m
Input voltage
Type of voltage / of the input voltage
Rated value, DC24 V
for signal "0"-3 to +5 V
for signal "1"15 to 30 V
Input current
for signal "1", typ.9 mA
Input delay (for rated value of input voltage)
for standard inputs
ParameterizableYes; 0.1 / 0.3 / 3 / 15 ms
Rated value3 ms
for counter/technological functions
at "0" to "1", max.8 µs
Cable length
Cable length, shielded, max.1000 m; 50 m for technological functions
Cable length unshielded, max.600 m; For technological functions: No
Digital outputs
Number/binary outputs16
of which high-speed outputs4
integrated channels (DO)16
Functionality/short-circuit strengthYes; Clocked electronically
Response threshold, typ.1 A
Limitation of inductive shutdown voltage toL+ (-48 V)
Lamp load, max.5 W
Controlling a digital inputYes
Output voltage
for signal "1", min.L+ (-0.8 V)
Output current
for signal "1" rated value500 mA
for signal "1" permissible range, min.5 mA
for signal "1" permissible range, max.0.6 A
for signal "1" minimum load current5 mA
for signal "0" residual current, max.0.5 mA
Parallel switching of 2 outputs
for increased powerNo
for redundant control of a loadYes
Switching frequency
with resistive load, max.100 Hz
with inductive load, max.0.5 Hz
on lamp load, max.100 Hz
of the pulse outputs, with resistive load, max.2.5 kHz
Aggregate current of outputs (per group)
horizontal installation
up to 40 °C, max.3 A
up to 60 °C, max.2 A
vertical installation
up to 40 °C, max.2 A
Load resistance range
lower limit48 Ω
upper limit4 kΩ
Cable length
Cable length, shielded, max.1000 m
Cable length unshielded, max.600 m
Analog inputs
Integrated channels (AI)4+1
Number of analog inputs for voltage/current measurement4
Number of analog inputs for resistance/temperature measurement1
permissible input frequency for current input (destruction limit), max.5 V; Permanent
permissible input voltage for voltage input (destruction limit), max.30 V; Permanent
permissible input current for voltage input (destruction limit), max.0.5 mA; Permanent
permissible input current for current input (destruction limit), max.50 mA; Permanent
Technical unit for temperature measurement adjustableYes; Degrees Celsius / degrees Fahrenheit / Kelvin
Input ranges
CurrentYes
Resistance thermometerYes; Pt 100 / 10 MΩ
ResistanceYes
Input ranges (rated values), voltages
0 to +10 VYes
Input resistance (0 to 10 V)100 kΩ
Input ranges (rated values), currents
0 to 20 mAYes
Input resistance (0 to 20 mA)100 Ω
-20 to +20 mAYes
Input resistance (-20 to +20 mA)100 Ω
4 to 20 mAYes
Input resistance (4 to 20 mA)100 Ω
Input ranges (rated values), resistance thermometers
Pt 100Yes
Input resistance (Pt 100)10 MΩ
Input ranges (rated values), resistors
No-Load voltage, typ.2.5 V
Measured current, typ.1.8 to 3.3 mA
0 to 600 ohmsYes
Input resistance (0 to 600 ohms)10 MΩ
Resistance thermometer (RTD)
Characteristic linearization
for resistance thermometerPt 100
Characteristic linearization
ParameterizableYes; by software
Temperature compensation
ParameterizableNo
Cable length
Cable length, shielded, max.100 m
Analog outputs
Number of analog outputs2
Integrated channels (AO)2
Voltage output, short-circuit protectionYes
Voltage output, short-circuit current, max.55 mA
Current output, no-load voltage, max.17 V
Output ranges, voltage
0 to 10 VYes
-10 to +10 VYes
Output ranges, current
0 to 20 mAYes
-20 to +20 mAYes
4 to 20 mAYes
Connection of actuators
for voltage output 2-conductor connectionYes; Without compensation of the line resistances
for voltage output 4-conductor connectionNo
for current output 2-conductor connectionYes
Load impedance (in rated range of output)
with voltage outputs, min.1 kΩ
with voltage outputs, capacitive load, max.0.1 µF
with current outputs, max.300 Ω
with current outputs, inductive load, max.0.1 mH
Destruction limits against externally applied voltages and currents
Voltages at the outputs towards MANA16 V; Permanent
Current, max.50 mA; Permanent
[nicht versorgt: TAK_ABT299_001_000]
Cable length, shielded, max.200 m
Analog value creation
Measurement principleActual value encryption (successive approximation)
Integrations and conversion time/ resolution per channel
Resolution with overrange (bit including sign), max.12 bit
Integration time, parameterizableYes; 2.5 / 16.6 / 20 ms
permissible input frequency, max.400 Hz
Interference voltage suppression for interference frequency f1 in Hz400 / 60 / 50 Hz
Conversion time (per channel)1 ms
Time constant of the input filter0.38 ms
Basic execution time of the module (all channels released)1 ms
Settling time
for resistive load0.6 ms
for capacitive load1 ms
for inductive load0.5 ms
Encoder
Connection of signal encoders
for voltage measurementYes
for current measurement as 2-wire transducerYes; with external supply
for current measurement as 4-wire transducerYes
for resistance measurement with 2-conductor connectionYes; Without compensation of the line resistances
for resistance measurement with 3-conductor connectionNo
for resistance measurement with 4-conductor connectionNo
Connectable encoders
2-wire BEROSYes
permissible quiescent current (2-wire BEROS), max.1.5 mA
Errors/accuracies
Temperature error (relative to input area)+/- 0,006 %/K
Crosstalk between the inputs, min.60 dB
Repeat accuracy in settled status at 25 °C (relative to input area)+/- 0,06 %
Output ripple (based on output area, bandwidth 0 to 50 kHz)+/- 0,1 %
Linearity error (relative to output area)+/- 0,15 %
Temperature error (relative to output area)+/- 0,01 %/K
Crosstalk between the outputs, min.60 dB
Repeat accuracy in settled status at 25 °C (relative to output area)+/- 0,06 %
Operational limit in overall temperature range
Voltage, relative to input area+/- 1 %
Current, relative to input area+/- 1 %
Impedance, relative to input area+/- 5 %
Voltage, relative to output area+/- 1 %
Current, relative to output area+/- 1 %
Basic error limit (operational limit at 25 °C)
Voltage, relative to input area+/- 0,7 %; Linearity error +/- 0.06 %
Current, relative to input area+/- 0,7 %; Linearity error +/- 0.06 %
Impedance, relative to input area+/- 3 %; Linearity error +/- 0.2%
Resistance-type thermometer, relative to input area+/- 3 %
Voltage, relative to output area+/- 0,7 %
Current, relative to output area+/- 0,7 %
Interference voltage suppression for f = n x (fl +/- 1%), fl = interference frequency
Series mode interference (peak value of interference < rated value of input range), min.30 dB
Common mode interference, min.40 dB
Interfaces
Number of USB interfaces0
Number of parallel interfaces0
Number of 20 mA interfaces (TTY)0
Number of RS 232 interfaces0
Number of RS 422 interfaces0
Number of other hardware interfaces0
MPI
Cable length, max.50 m; without repeater
1st interface
Type of interfaceIntegrated RS 485 interface
PhysicsRS 485
IsolatedNo
Power supply to interface (15 to 30 V DC), max.200 mA
Functionality
MPIYes
DP masterNo
DP slaveNo
Point-to-point connectionNo
MPI
Number of connections12
Services
PG/OP communicationYes
RoutingYes
Global data communicationYes
S7 basic communicationYes
S7 communicationYes
S7 communication, as clientNo
S7 communication, as serverYes
Transmission rate, max.187.5 kbit/s
2nd interface
Type of interfaceIntegrated RS 485 interface
PhysicsRS 485
IsolatedYes
Power supply to interface (15 to 30 V DC), max.200 mA
Media redundancy
Number of connection resources12
Functionality
MPINo
DP masterYes
DP slaveYes
PROFINET IO ControllerNo
PROFINET CBANo
Local Operating NetworkNo
DP master
Number of connections, max.12; For PG/OP communication
Services
PG/OP communicationYes
RoutingYes
Global data communicationNo
S7 basic communicationYes; I blocks only
S7 communicationYes
S7 communication, as clientNo
S7 communication, as serverYes
Equidistance mode supportYes
Isochronous modeNo
SYNC/FREEZEYes
Activation/deactivation of DP slavesYes
Direct data exchange (slave-to-slave communication)Yes
DPV1Yes
Transmission rate, max.12 Mbit/s
Number of DP slaves, max.32
Address area
Inputs, max.1 Kibyte
Outputs, max.1 Kibyte
User data per DP slave
Inputs, max.244 byte
Outputs, max.244 byte
DP slave
Number of connections12
Services
PG/OP communicationYes
RoutingYes; Only with active interface
Global data communicationNo
S7 basic communicationNo
S7 communicationYes
S7 communication, as clientNo
S7 communication, as serverYes
Direct data exchange (slave-to-slave communication)Yes
DPV1No
GSD fileThe latest GSD file is available at: http://www.siemens.de/profibus-gsd
Transmission rate, max.12 Mbit/s
Automatic baud rate searchYes; only with passive interface
Transfer memory
Inputs244 byte
Outputs244 byte
Address area, max.32
User data per address area, max.32 byte
Communication functions
PG/OP communicationYes
Global data communication
supportedYes
Number of GD loops, max.4
Number of GD packets, max.4
Number of GD packets, transmitter, max.4
Number of GD packets, receiver, max.4
Size of GD packets, max.22 byte
Size of GD packet (of which consistent), max.22 byte
S7 basic communication
supportedYes
User data per job, max.76 byte
User data per job (of which consistent), max.76 byte; 76 bytes (with X_SEND or X_RCV); 64 bytes (with X_PUT or X_GET as server)
S7 communication
supportedYes
as serverYes
as clientYes; Via CP and loadable FB
User data per job, max.180 Kibyte; With PUT/GET
User data per job (of which consistent), max.64 byte
S5-compatible communication
supportedYes; via CP and loadable FC
Number of connections
overall12
usable for PG communication11
reserved for PG communication1
Adjustable for PG communication, min.1
Adjustable for PG communication, max.11
usable for OP communication11
reserved for OP communication1
adjustable for OP communication, min.1
adjustable for OP communication, max.11
usable for S7 basic communication8
Reserved for S7 basic communication0
adjustable for S7 basic communication, min.0
adjustable for S7 basic communication, max.8
usable for routing4; max.
S7 message functions
Number of login stations for message functions, max.12; Depending on the configured connections for PG/OP and S7 basic communication
Process diagnostic messagesYes
simultaneously active Alarm-S blocks, max.40
Test commissioning functions
Status/control
Status/control variableYes
VariablesInputs, outputs, memory bits, DB, times, counters
Number of variables, max.30
of which status variables, max.30
of which control variables, max.14
Forcing
ForcingYes
Force, variablesInputs, outputs
Number of variables, max.10
Status blockYes
Single stepYes
Number of breakpoints2
Diagnostic buffer
presentYes
Number of entries, max.100
Interrupts/diagnostics/status information
Diagnostics indication LED
Status indicator digital output (green)Yes
Status indicator digital input (green)Yes
Integrated Functions
Number of counters4; See "Technological Functions" manual
Counter frequency (counter) max.60 kHz
Frequency measurementYes
Number of frequency meters4; up to 60 kHz (see "Technological Functions" manual)
controlled positioningYes
Integrated function blocks (closed-loop control)PID controller (see "Technological Functions" manual)
PID controllerYes
20 Units in Stock


Call for Availability
Price for:  EachMinimum:  1

Target Price

Offer your acceptable price, and we may make you satisfied.Your Target Price

Technical Support

Technical Support

Customer Reviews

Write Review

Customer Q&A Exchange

Ask A Question