SIMATIC S7-1200, ANALOG INPUT, SM 1231, 8 AI, +/-10V, +/-5V, +/-2.5V, OR 0-20 MA 12 BIT + SIGN OR (13 BIT ADC) |
Supply voltage |
24 V DC | Yes |
Input current |
Current consumption, typ. | 45 mA |
from backplane bus 5 V DC, typ. | 90 mA |
Power losses |
Power loss, typ. | 1.5 W |
Analog inputs |
Number of analog inputs | 8; Current or voltage differential inputs |
permissible input frequency for current input (destruction limit), max. | ± 35 V |
permissible input voltage for voltage input (destruction limit), max. | 35 V |
permissible input current for voltage input (destruction limit), max. | 40 mA |
Cycle time (all channels) max. | 625 µs |
permissible input current for current input (destruction limit), max. | 40 mA |
Input ranges |
Voltage | Yes; ±10 V, ±5 V, ±2.5 V |
Current | Yes; 0 to 20 mA |
Thermocouple | No |
Resistance thermometer | No |
Resistance | No |
Input ranges (rated values), voltages |
-10 V to +10 V | Yes |
Input resistance (-10 V to +10 V) | ≥9 MOhm |
-2.5 V to +2.5 V | Yes |
Input resistance (-2.5 V to +2.5 V) | ≥9 MOhm |
-5 V to +5 V | Yes |
Input resistance (-5 V to +5 V) | ≥9 MOhm |
Input ranges (rated values), currents |
0 to 20 mA | Yes |
Input resistance (0 to 20 mA) | 280 Ω |
Temperature compensation |
Parameterizable | No |
Analog outputs |
Number of analog outputs | 0 |
Analog value creation |
Integrations and conversion time/ resolution per channel |
Resolution with overrange (bit including sign), max. | 12 bit; + sign |
Integration time, parameterizable | Yes |
Interference voltage suppression for interference frequency f1 in Hz | 40 dB, DC to 60 V for interference frequency 50 / 60 Hz |
Smoothing of measured values |
Parameterizable | Yes |
Step: None | Yes |
Step: low | Yes |
Step: Medium | Yes |
Step: High | Yes |
Errors/accuracies |
Temperature error (relative to input area) | 25 °C ±0.1 % to 55 °C ±0.2 % total measurement range |
Basic error limit (operational limit at 25 °C) |
Voltage, relative to input area | +/- 0,1 % |
Current, relative to input area | +/- 0,1 % |
Interference voltage suppression for f = n x (fl +/- 1%), fl = interference frequency |
common mode voltage, max. | 12 V |
Interrupts/diagnostics/status information |
Alarms |
Alarms | Yes |
Diagnostic alarm | Yes |
Diagnoses |
Diagnostic functions | Yes |
Monitoring the supply voltage to the electronics | Yes |
Wire break | No |
Diagnostics indication LED |
for status of the inputs | Yes |
for maintenance | Yes |
Galvanic isolation |
Galvanic isolation analog outputs |
between the channels and the power supply of the electronics | No |
Climatic and mechanical conditions for storage and transport |
Climatic conditions for storage and transport |
Free fall |
Drop height, max. (in packaging) | 0.3 m; five times, in dispatch package |
Temperature |
Permissible temperature range | -40 °C to +70 °C |
Air pressure acc. to IEC 60068-2-13 |
Permissible air pressure | 1080 to 660 hPa |
Mechanical and climatic conditions during operation |
Climatic conditions in operation |
Temperature |
Permissible temperature range | 0 °C to 55 °C horizontal installation 0 °C to 45 °C vertical installation |
Air pressure acc. to IEC 60068-2-13 |
Permissible air pressure | 1080 to 795 hPa |
Pollutant concentrations |
SO2 at RH < 60% without condensation | S02: < 0.5 ppm; H2S: < 0.1 ppm; RH < 60% condensation-free |
Degree and class of protection |
IP20 | Yes |
Standards, approvals, certificates |
CE mark | Yes |
C-TICK | Yes |
FM approval | Yes |
Connection method |
required front connector | Yes |
Mechanics/material |
Type of housing (front) | |
Plastic | Yes |
Dimensions |
Width | 45 mm |
Height | 100 mm |
Depth | 75 mm |
Weight |
Weight, approx. | 180 g |