SIMATIC S7-1200, DIGITAL I/O SM 1223, 16DI / 16DO, 16DI DC 24 V, SINK/SOURCE, 16DO, TRANSISTOR 0.5A |
Supply voltage |
24 V DC | Yes |
permissible range, lower limit (DC) | 20.4 V |
permissible range, upper limit (DC) | 28.8 V |
Input current |
from backplane bus 5 V DC, max. | 185 mA |
Digital inputs |
from load voltage L+ (without load), max. | 4 mA; per channel |
Output voltage |
Power supply to the transmitters |
present | Yes |
Power losses |
Power loss, typ. | 4.5 W |
Digital inputs |
Number/binary inputs | 16 |
In groups of | 2 |
Input characteristic curve acc. to IEC 1131, Type 1 | Yes |
Number of simultaneously controllable inputs |
all mounting positions |
up to 40 °C, max. | 16 |
horizontal installation |
up to 40 °C, max. | 16 |
up to 50 °C, max. | 16 |
vertical installation |
up to 40 °C, max. | 16 |
Input voltage |
Type of input voltage | DC |
Rated value, DC | 24 V |
for signal "0" | 5 V DC at 1 mA |
for signal "1" | 15 V DC at 2.5 mA |
Input current |
for signal "0", max. (permissible quiescent current) | 1 mA |
for signal "1", min. | 2.5 mA |
for signal "1", typ. | 4 mA; Typical |
Input delay (for rated value of input voltage) |
for standard inputs |
Parameterizable | Yes; 0.2, 0.4, 0.8, 1.6, 3.2, 6.4, and 12.8 ms, selectable in groups of four |
for interrupt inputs |
Parameterizable | Yes |
Cable length |
Cable length, shielded, max. | 500 m |
Cable length unshielded, max. | 300 m |
Digital outputs |
Number/binary outputs | 16 |
In groups of | 1 |
Functionality/short-circuit strength | No; to be provided externally |
Limitation of inductive shutdown voltage to | L+ (-48 V) |
Switching capacity of the outputs |
with resistive load, max. | 0.5 A |
on lamp load, max. | 5 W |
Output voltage |
Rated value (DC) | 24 V |
for signal "0" (DC), max. | 0.1 V; with 10 kOhm load |
for signal "1", min. | 20 V DC |
Output current |
for signal "1" permissible range, max. | 0.5 A |
for signal "0" residual current, max. | 10 µA |
Output delay with resistive load |
0 to "1", max. | 50 µs |
1 to "0", max. | 200 µs |
Aggregate current of outputs (per group) |
horizontal installation |
up to 50 °C, max. | 8 A; Current per mass |
Relay outputs |
Switching capacity of contacts |
with inductive load, max. | 0.5 A |
on lamp load, max. | 5 W |
Switching frequency/contacts/at ohmic load/maximum | 0.5 A |
Cable length |
Cable length, shielded, max. | 500 m |
Cable length unshielded, max. | 150 m |
Interrupts/diagnostics/status information |
Alarms |
Alarms | Yes |
Diagnostic alarm | Yes |
Diagnoses |
Diagnostic functions | Yes |
Diagnostics indication LED |
for status of the inputs | Yes |
For status of the outputs | Yes |
for maintenance | Yes |
Status indicator digital output (green) | Yes |
Status indicator digital input (green) | Yes |
Galvanic isolation |
Galvanic isolation digital inputs |
between the channels, in groups of | 2 |
Galvanic isolation digital outputs |
between the channels, in groups of | 1 |
between the channels and the backplane bus | 500 V AC |
Climatic and mechanical conditions for storage and transport |
Climatic conditions for storage and transport |
Free fall |
Drop height, max. (in packaging) | 0.3 m; five times, in dispatch package |
Temperature |
Permissible temperature range | -40 °C to +70 °C |
Air pressure acc. to IEC 60068-2-13 |
Permissible air pressure | 1080 to 660 hPa |
Mechanical and climatic conditions during operation |
Climatic conditions in operation |
Temperature |
Permissible temperature range | 0 °C to 55 °C horizontal installation 0 °C to 45 °C vertical installation |
Permissible temperature change | 5°C to 55°C, 3°C / minute |
Degree and class of protection |
IP20 | Yes |
Standards, approvals, certificates |
CE mark | Yes |
C-TICK | Yes |
FM approval | Yes |
Connection method |
required front connector | Yes |
Mechanics/material |
Type of housing (front) | |
Plastic | Yes |
Dimensions |
Width | 70 mm |
Height | 100 mm |
Depth | 75 mm |
Weight |
Weight, approx. | 310 g |