SIMATIC S7-200, DIGITAL OUTPUT EM 222, FOR S7-22X CPU ONLY, 8DQ, 24 V DC, |
Supply voltage |
Load voltage L+ |
Rated value (DC) | 24 V |
permissible range, lower limit (DC) | 20.4 V |
permissible range, upper limit (DC) | 28.8 V |
Input current |
from backplane bus 5 V DC, max. | 50 mA |
Power losses |
Power loss, typ. | 2 W |
Digital outputs |
Number/binary outputs | 8 |
Functionality/short-circuit strength | No; to be provided externally (see manual package "Setting up an S7-200") |
Limitation of inductive shutdown voltage to | L+ (-48 V) |
Output voltage |
for signal "1", min. | 20 V |
Output current |
for signal "1" permissible range for 0 to 40 °C, max. | 750 mA |
for signal "1" permissible range for 0 to 55 °C, max. | 750 mA |
for signal "0" residual current, max. | 10 µA |
Parallel switching of 2 outputs |
for increased power | Yes |
Aggregate current of outputs (per group) |
Digital inputs / Number of inputs that can be driven in parallel / all mounting positions |
up to 40 °C, max. | 3 A |
maximum current per conductor/group | 3 A |
horizontal installation |
up to 55 °C, max. | 3 A |
Relay outputs |
Switching capacity of contacts |
with inductive load, max. | 0.75 A |
on lamp load, max. | 5 W |
Switching frequency/contacts/at ohmic load/maximum | 0.75 A |
Cable length |
Cable length, shielded, max. | 500 m |
Cable length unshielded, max. | 150 m |
Galvanic isolation |
Galvanic isolation digital outputs |
Galvanic isolation digital outputs | Yes; Optocoupler |
between the channels, in groups of | 4 |
Connection method |
Plug-in I/O terminals | Yes |
Dimensions |
Width | 45 mm |
Height | 80 mm |
Depth | 62 mm |
Weight |
Weight, approx. | 150 g |