Your cart is empty

6ES7145-4FF00-0AB0 SIMATIC DP,

Manufacturer:
SIEMENS
Weight:
0.15kg
Product Range:
Automation Systems

Product Information

SIMATIC DP, ELECTRONIC MODULES FOR ET200PRO 4 AO U HIGH FEATURE, +-10V; 0...10V; 1...5V, CHANNEL DIAGNOSTICS; INCLUSIVE BUS MODULE CONNECTING MODULE IO 6ES7194-4..00-0AA0 MUST BE ORDERED SEPERATELY
Supply voltage
Load voltage L+
Rated value (DC)24 V
Reverse polarity protectionYes; against destruction
Input current
from backplane bus 3.3 V DC, max.10 mA
Address area
Address space per module
Address space per module, max.8 byte
Analog outputs
Number of analog outputs4
Voltage output, short-circuit protectionYes; per channel, electronic to chassis
Voltage output, short-circuit current, max.50 mA
Cycle time (all channels) max.3 ms
Output ranges, voltage
0 to 10 VYes
1 to 5 VYes
-10 to +10 VYes
Connection of actuators
for voltage output 2-conductor connectionYes
for voltage output 4-conductor connectionYes
Load impedance (in rated range of output)
with voltage outputs, min.1000 Ω
with voltage outputs, capacitive load, max.1 µF
Destruction limits against externally applied voltages and currents
Voltages at the outputs towards MANA16 V; Permanent
[nicht versorgt: TAK_ABT299_001_000]
Cable length, shielded, max.30 m
Analog value creation
Integrations and conversion time/ resolution per channel
Resolution with overrange (bit including sign), max.15 bit; at -10 to +10 V; 14 bits at 1 to 5 V; 15 bits at 0 to 10 V
Conversion time (per channel)0.7 ms
Settling time
for resistive load0.1 ms
for capacitive load6 ms
Errors/accuracies
Output ripple (based on output area, bandwidth 0 to 50 kHz)+/- 0.02 %
Linearity error (relative to output area)+/- 0.1 %
Temperature error (relative to output area)+/- 0.01 %
Repeat accuracy in settled status at 25 °C (relative to output area)+/- 0.05 %
Operational limit in overall temperature range
Voltage, relative to output area+/- 0.2 %
Basic error limit (operational limit at 25 °C)
Voltage, relative to output area+/- 0.15 %
Interrupts/diagnostics/status information
Substitute values connectableYes
Alarms
Diagnostic alarmYes; Parameterizable
Hardware interruptNo
Diagnoses
Wire breakNo
Short circuitYes; per channel, not in zero range
Diagnostics indication LED
Group error SF (red)Yes
Parameter
Output type/range1
Diagnosis: short circuitOutputs; sensor supply to M
Group diagnostics1
Behavior on CPU/Master STOP1
Galvanic isolation
Galvanic isolation analog outputs
between the channelsNo
between the channels and the backplane busYes
Dimensions
Width45 mm
Height130 mm
Depth35 mm
Weight
Weight, approx.150 g

1 Units in Stock


Call for Availability
Price for:  EachMinimum:  1

Target Price

Offer your acceptable price, and we may make you satisfied.Your Target Price

Technical Support

Technical Support

Customer Reviews

Write Review

Customer Q&A Exchange

Ask A Question