SIMATIC DP, BASIC MOD. BM143 ET 200ECO: 8DI/8DO, 1.3A, 8 X M12, DOUBLE-ASSIGNEMENT, IP65/67, CONN. BLOCK 6ES7194-3AA00-0.A0 MUST BE ORDERED SEPARTELY |
General information |
Vendor identification (VendorID) | 80FCh |
Supply voltage |
Rated value (DC) | 24 V |
Reverse polarity protection | Yes |
Load voltage 2L+ |
Rated value (DC) | 24 V |
Reverse polarity protection | Yes |
Input current |
from load voltage 2L+ (without load), max. | 60 mA; typ. |
from supply voltage 1L+, max. | 70 mA; typ. |
Encoder supply |
Number of outputs | 8 |
Output current, rated value | 1 A; Up to 55°C max. 1 A (summation current) |
Output current |
Short-circuit protection | Yes; Electronic |
Power losses |
Power loss, typ. | 5 W |
Digital inputs |
Number/binary inputs | 8 |
Input characteristic curve acc. to IEC 1131, Type 1 | Yes |
Number of simultaneously controllable inputs | 8; All mounting positions up to 55 °C |
Input voltage |
Type of input voltage | DC |
Rated value, DC | 24 V |
for signal "0" | -3 to +5 V |
for signal "1" | 13 to 30 V |
Input current |
for signal "1", typ. | 7 mA |
Input delay (for rated value of input voltage) |
for standard inputs |
at "0" to "1", max. | 3 ms; typ. |
at "1" to "0", max. | 3 ms; typ. |
Digital outputs |
Number/binary outputs | 8 |
Functionality/short-circuit strength | Yes; Electronic |
Response threshold, typ. | 4 A per channel |
Limitation of inductive shutdown voltage to | 2L+ (-44 V) |
Lamp load, max. | 10 W |
Controlling a digital input | Yes |
Output voltage |
for signal "1", min. | 2L+ (-1.2 V) |
Output current |
for signal "1" rated value | 1.3 A |
for signal "1" permissible range for 0 to 55 °C, min. | 5 mA |
for signal "1" permissible range for 0 to 55 °C, max. | 1.8 A |
for signal "0" residual current, max. | 0.5 mA |
Parallel switching of 2 outputs |
for increased power | No |
for redundant control of a load | Yes |
Switching frequency |
with resistive load, max. | 100 Hz |
with inductive load, max. | 0.5 Hz; to IEC 947-5-1, DC13 |
on lamp load, max. | 1 Hz |
Aggregate current of outputs (per group) |
Digital inputs / Number of inputs that can be driven in parallel / all mounting positions |
up to 55 °C, max. | 5.2 A; Please note the current carrying capacity of the cable! |
Load resistance range |
lower limit | 12 Ω |
upper limit | 4 kΩ |
Cable length |
Cable length unshielded, max. | 30 m |
Encoder |
Connectable encoders |
2-wire BEROS | Yes |
permissible quiescent current (2-wire BEROS), max. | 1.5 mA |
Interfaces |
PROFIBUS DP |
Transmission rate, max. | 12 Mbit/s; 9.6 / 19.2 / 45.45 / 93.75 / 187.5 / 500 Kbit/s; 1.5 / 3 / 6 / 12 Mbit/s |
Protocols |
Further protocols |
PROFIBUS DP protocol | Yes |
Interrupts/diagnostics/status information |
Status indicator | Yes |
Alarms |
Alarms | No |
Diagnoses |
Diagnostics | Yes; Diagnostic information readable |
Diagnostics indication LED |
Group error SF (red) | Yes |
Status indicator digital output (green) | Yes |
Status indicator digital input (green) | Yes |
Channel error indicator F (red) | No |
Galvanic isolation |
between PROFIBUS DP and all other circuit components | Yes |
Galvanic isolation digital inputs |
between the channels | No |
Galvanic isolation digital outputs |
between the channels | No |
Permissible potential difference |
between different circuits | 75 VDC / 60 VAC |
Isolation |
Isolation checked with | 500 V DC |
Dimensions |
Width | 60 mm |
Height | 210 mm |
Depth | 28 mm |
Weight |
Weight, approx. | 210 g |