SIMATIC DP, ET 200ECO PN, 16 DI 24V DC; 8 X M12, DOUBLE-ASSIGNEMENT; DEGREE OF PROTECTION IP67 |
General information |
Vendor identification (VendorID) | 002AH |
Device identifier (DeviceID) | 0306H |
Supply voltage |
24 V DC | Yes |
permissible range, lower limit (DC) | 20.4 V |
permissible range, upper limit (DC) | 28.8 V |
Reverse polarity protection | Yes |
Input current |
Current consumption, typ. | 100 mA |
Encoder supply |
Number of outputs | 8 |
Output current, rated value | 100 mA; per output |
24 V encoder supply |
Short-circuit protection | Yes |
Power losses |
Power loss, typ. | 6.5 W |
Digital inputs |
Number/binary inputs | 16 |
In groups of | 2 |
Input characteristic curve acc. to IEC 1131, Type 3 | Yes |
Number of simultaneously controllable inputs |
all mounting positions |
up to 60 °C, max. | 16 |
Input voltage |
Type of input voltage | DC |
Rated value, DC | 24 V |
for signal "0" | -3 to +5 V |
for signal "1" | 11 to 30 V |
Input current |
for signal "0", max. (permissible quiescent current) | 1.5 mA |
for signal "1", typ. | 7 mA |
Input delay (for rated value of input voltage) |
for standard inputs |
at "0" to "1", max. | typically 3 ms |
at "1" to "0", max. | typically 3 ms |
Cable length |
Cable length unshielded, max. | 30 m |
Interfaces |
Transmission procedure | 100BASE-TX |
Transmission rate, max. | 100 Mbit/s |
Supports protocol for PROFINET IO |
Number of PROFINET interfaces | 2 |
Autocrossing | Yes |
Automatic detection of transmission speed | Yes |
Integrated switch | Yes |
PROFINET IO Device |
IRT with the option "high flexibility" supported | Yes |
Prioritized startup supported | Yes |
Protocols |
Supports protocol for PROFINET IO | Yes |
Protocols (Ethernet) |
SNMP | Yes |
DCP | Yes |
LLDP | Yes |
ping | Yes |
arp | Yes |
Interrupts/diagnostics/status information |
Status indicator | Yes; Green LED |
Alarms |
Diagnostic alarm | Yes |
Diagnoses |
Diagnostic functions | Yes |
Diagnostic information readable | Yes |
Monitoring the supply voltage to the electronics | Yes; Green "ON" LED |
Wire break in signal transmitter cable | Yes |
Short circuit encoder supply | Yes; Per channel group |
Group error | Yes; Red/yellow "SF/MT" LED |
Galvanic isolation |
between the load voltages | Yes |
between load voltage and all other switching components | No |
between Ethernet and electronics | Yes |
Galvanic isolation digital inputs |
between the channels | No |
Permissible potential difference |
between different circuits | 75 VDC / 60 VAC |
Isolation |
tested with |
24 V DC circuits | 500 V |
Interface | 1500 V; According to IEEE 802.3 |
Degree and class of protection |
IP65 | Yes |
IP66 | Yes |
IP67 | Yes |
Connection method |
M12 | Yes |
Dimensions |
Width | 60 mm |
Height | 175 mm |
Depth | 49 mm |
Weight |
Weight | 910 g |