SIMATIC DP, ELECTRONIC MODULE FOR ET200PRO 8 DI DC 24V, MODULE DIAGNOSTICS; INCLUSIVE BUS MODULE CONNECTING MODULE IO 6ES7194-4..00-0AA0 MUST BE ORDERED SEPERATELY |
FH technology |
Module for failsafe applications | No |
Supply voltage |
24 V DC | Yes |
permissible range, lower limit (DC) | 20.4 V |
permissible range, upper limit (DC) | 28.8 V |
Reverse polarity protection | Yes; Against destruction; encoder power supply outputs applied with reversed polarity |
Input current |
from backplane bus 3.3 V DC, max. | 20 mA |
from supply voltage 1L+, max. | 20 mA |
Encoder supply |
Number of outputs | 8 |
Output current |
up to 55 °C, max. | 1 A |
Short-circuit protection | Yes; per module, electronic |
Power losses |
Power loss, typ. | 2.5 W |
Address area |
Occupied address area |
Inputs | 1 byte |
Digital inputs |
Number/binary inputs | 8 |
Input characteristic curve acc. to IEC 1131, Type 1 | Yes |
Input characteristic curve acc. to IEC 1131, Type 2 | No |
Number of simultaneously controllable inputs |
[nicht versorgt: TAK_ABP289_001_000] |
up to 55 °C, max. | 8 |
Input voltage |
Type of input voltage | DC |
Rated value, DC | 24 V |
for signal "0" | -3 to +5 V |
for signal "1" | 13 to 30 V |
Input current |
for signal "1", typ. | 7 mA |
Input delay (for rated value of input voltage) |
for standard inputs |
Parameterizable | No |
at "0" to "1", min. | 1.2 ms |
at "0" to "1", max. | 4.8 ms |
at "1" to "0", min. | 1.2 ms |
at "1" to "0", max. | 4.8 ms |
Cable length |
Cable length, shielded, max. | 30 m |
Cable length unshielded, max. | 30 m |
Encoder |
Connectable encoders |
2-wire BEROS | Yes |
permissible quiescent current (2-wire BEROS), max. | 1.5 mA |
Isochronous mode |
Isochronous mode | No |
Interrupts/diagnostics/status information |
Diagnoses |
Diagnostic functions | Yes |
Diagnostic information readable | Yes |
Short circuit | Yes; Sensor supply to M; module by module |
Diagnostics indication LED |
Group error SF (red) | Yes |
Status indicator digital input (green) | Yes; Per channel |
Parameter |
Diagnosis: short circuit | Sensor supply to M; module by module |
Galvanic isolation |
between backplane bus and all other circuit components | Yes |
Galvanic isolation digital inputs |
between the channels | No |
between the channels and the backplane bus | Yes |
Permissible potential difference |
between different circuits | 75 VDC / 60 VAC |
Isolation |
Isolation checked with | 500 V DC |
Degree and class of protection |
IP65 | Yes |
IP66 | Yes |
IP67 | Yes |
Dimensions |
Width | 45 mm |
Height | 130 mm |
Depth | 35 mm |
Weight |
Weight, approx. | 140 g |