SIMATIC DP, DISTRIBUTED I/O ET200X:BASIC MOD. BM141/ECOFAST 8 DE DC 24V, 5-PIN M12, WITH SINGLE-CHANNEL PORT, HYBRID FIELD BUS INTERFACE (RS485), IDENT CONNECTOR, IP67 IDENT CONNECTOR, IP67 |
Supply voltage |
Rated value (DC) | 24 V |
Reverse polarity protection | No |
Load voltage 2L+ |
Rated value (DC) | 24 V |
Reverse polarity protection | No |
Input current |
from load voltage 1L+ (unswitched voltage) | 180 mA |
from load circuit 1 (unswitched voltage/supply voltage) up to 40 °C | 10 A |
from load circuit 1 (unswitched voltage/supply voltage) up to 55 °C | 8 A |
from load circuit 2 (unswitched voltage/supply voltage) up to 40 °C | 10 A |
from load circuit 2 (unswitched voltage/supply voltage) up to 55 °C | 8 A |
Power losses |
Power loss, typ. | 3.5 W |
Hardware configuration |
Expansion modules |
Number of expansion modules, max. | 7 |
of which motor starters/frequency converters, max. | 6 |
of which, pneumatic interfaces, max. | 6 |
Digital inputs |
Number/binary inputs | 8; 8 process channels DI, single channel connector |
Input characteristic curve acc. to IEC 1131, Type 1 | Yes |
Input voltage |
Type of input voltage | |
Rated value, DC | 24 V |
for signal "0" | -3 to +5 V |
for signal "1" | 13 to 30 V |
Input current |
for signal "1", typ. | 7 mA |
Input delay (for rated value of input voltage) |
for standard inputs |
at "0" to "1", min. | 1.2 ms |
at "0" to "1", max. | 4.8 ms |
Cable length |
Cable length unshielded, max. | 30 m; for signal lines |
Encoder |
Connectable encoders |
2-wire BEROS | Yes |
permissible quiescent current (2-wire BEROS), max. | 1.5 mA |
1st interface |
Functionality |
DP slave | Yes |
DP slave |
Services |
Direct data exchange (slave-to-slave communication) | Yes; Sender |
Transmission rate, min. | 9.6 kbit/s |
Transmission rate, max. | 12 Mbit/s; 9.6 / 19.2 / 45.45 / 93.75 / 187.5 / 500 Kbit/s; 1.5 / 12 Mbit/s |
Interrupts/diagnostics/status information |
Alarms |
Diagnostic alarm | Yes |
Diagnostics indication LED |
Group error SF (red) | Yes |
Galvanic isolation |
Galvanic isolation | No electrical isolation between the load voltages and between the load voltages and all the other circuit components |
between PROFIBUS DP and all other circuit components | Yes |
Galvanic isolation digital inputs |
between the channels | No |
between the channels and the backplane bus | No |
Degree and class of protection |
IP67 | Yes |
Dimensions |
Width | 175 mm; 180 when screw mounted |
Height | 180 mm; 174 when screw mounted |
Depth | 110 mm; 90 when screw mounted |
Status | Sep 10, 2011 |