SIMATIC DP, ELECTRONIC MODULE FOR ET 200S, 1 POS-SSI D, CONTROLLED POSITIONING WITH DIGITAL OUTPUTS FOR SSI-ENCODER, 30MM WIDE |
Supply voltage |
24 V DC | Yes |
Load voltage L+ |
Rated value (DC) | 24 V |
permissible range, lower limit (DC) | 20.4 V |
permissible range, upper limit (DC) | 28.8 V |
Reverse polarity protection | Yes |
Input current |
from load voltage L+ (without load), max. | 50 mA |
from backplane bus 3.3 V DC, max. | 10 mA |
Power losses |
Power loss, typ. | 2 W |
Hardware configuration |
Module exchange |
Hot swapping the IM-DP | Yes |
Module exchange under process voltage | Yes |
Digital inputs |
Number/binary inputs | 3 |
Input characteristic curve acc. to IEC 1131, Type 2 | Yes |
Input voltage |
Type of voltage / of the input voltage | |
Rated value, DC | 24 V |
for signal "0" | -30 to +5 V |
for signal "1" | 11 to 30 V |
Input current |
for signal "0", max. (permissible quiescent current) | 2 mA |
for signal "1", typ. | 9 mA |
Input delay (for rated value of input voltage) |
for standard inputs |
at "0" to "1", min. | 500 µs |
Cable length |
Cable length unshielded, max. | 50 m |
Digital outputs |
Number/binary outputs | 3 |
Functionality/short-circuit strength | Yes |
Response threshold, typ. | 0.7 to 1.8 A |
Limitation of inductive shutdown voltage to | L+ (-55 to -60 V) |
Lamp load, max. | 5 W |
Controlling a digital input | Yes |
Output voltage |
Rated value (DC) | 24 V |
for signal "0" (DC), max. | 3 V |
for signal "1", min. | L+ (-1 V) |
Output current |
for signal "1" permissible range for 0 to 60 °C, min. | 7 mA |
for signal "1" permissible range for 0 to 60 °C, max. | 600 mA |
for signal "0" residual current, max. | 3 mA |
Output delay with resistive load |
0 to "1", max. | 1.3 ms; typically 150 µs |
1 to "0", max. | 200 µs; typically 150 µs |
Switching frequency |
with resistive load, max. | 100 Hz |
with inductive load, max. | 2 Hz |
on lamp load, max. | 10 Hz |
Cable length |
Cable length, shielded, max. | 1000 m |
Cable length unshielded, max. | 600 m |
Analog value creation |
Update time of the feedback messages | 2 ms |
Encoder |
Connectable encoders |
Absolute encoder (SSI) | Yes |
2-wire BEROS | Yes; Type 2 |
Encoder signals, absolute encoder (SSI) |
Input signal | to RS 422; 13, 21, 25 Bit |
Binary code | 1 |
Gray code | 1 |
Cable length, shielded, max. | 320 m; 320 m at 125 kHz, 160 m at 250 kHz, 60 m at 500 kHz, 20 m at 1 MHz, 8 m at 2 MHz, twisted in pairs and shielded |
Response times |
Latch | 400 µs; plus age of encoder value |
Response time at switchover/switchoff time | Output delay + message frame runtime + 30 µs |
Interrupts/diagnostics/status information |
Diagnostics indication LED |
Actual value falling DN (green) | Yes |
Actual value rising UP (green) | Yes |
Positioning mode POS (green) | Yes |
Group error SF (red) | Yes |
Status indicator digital input (green) | Yes |
Parameter |
Remark | 16 byte |
Galvanic isolation |
between the channels and backplane bus | Yes |
Dimensions |
Width | 30 mm |
Height | 81 mm |
Depth | 52 mm |
Weight |
Weight, approx. | 65 g |