SIMATIC DP, ELECT. SUBMODULE FOR ET200ISP, 4 AO HART, 4 - 20MA, FOR CONNECTION OF HART FIELD DEVICES |
Input current |
from load voltage1L+, max. | 330 mA |
Power losses |
Power loss, max. | 2.7 W |
Analog outputs |
Number of analog outputs | 4 |
Cycle time (all channels) max. | 3.6 ms |
Output ranges, current |
4 to 20 mA | Yes |
Connection of actuators |
for current output 2-conductor connection | Yes |
Load impedance (in rated range of output) |
with current outputs, max. | 750 Ω |
[nicht versorgt: TAK_ABT299_001_000] |
Cable length, shielded, max. | 500 m |
Analog value creation |
Integrations and conversion time/ resolution per channel |
Resolution with overrange (bit including sign), max. | 14 bit |
Settling time |
for resistive load | 4 ms |
for capacitive load | 40 ms |
for inductive load | 40 ms |
Errors/accuracies |
Linearity error (relative to output area) | +/- 0.015 % |
Temperature error (relative to output area) | +/- 0.005 %/K |
Crosstalk between the outputs, min. | -50 dB |
Repeat accuracy in settled status at 25 °C (relative to output area) | +/- 0.01 % |
Operational limit in overall temperature range |
Current, relative to output area | +/- 0.15 % |
Basic error limit (operational limit at 25 °C) |
Current, relative to output area | +/- 0.1 % |
Interrupts/diagnostics/status information |
Substitute values connectable | Yes |
Alarms |
Diagnostic alarm | Yes |
Diagnoses |
Diagnostic information readable | Yes |
Wire break | Yes |
Short circuit | Yes |
Diagnostics indication LED |
Group error SF (red) | Yes |
Galvanic isolation |
Galvanic isolation analog outputs |
between the channels | No |
between the channels and the backplane bus | Yes |
Standards, approvals, certificates |
CE mark | Yes |
Use in hazardous areas |
Type of protection acc. to EN 50020 (CENELEC) | II2 G (1) GD Ex ib[ia] IIC T4 and I M2 Ex ib[ia] I |
Type of protection acc. to KEMA | 04 ATEX 1250 |
Dimensions |
Width | 30 mm |
Height | 129 mm |
Depth | 136.5 mm |
Weight |
Weight, approx. | 265 g |