SIMATIC DP, ELECTRONIC MODULE FOR ET 200S, 2 AO I HIGH SPEED 15 MM WIDE, +/-20 MA; 16 BIT, 4 . .20 MA; 16 BIT CYCLE TIME 0.1 MS WITH LED SF (GROUP FAULT) |
Supply voltage |
Load voltage L+ |
Rated value (DC) | 24 V |
Reverse polarity protection | Yes |
Input current |
from load voltage L+ (without load), max. | 150 mA; With load |
from backplane bus 3.3 V DC, max. | 10 mA |
Power losses |
Power loss, max. | 2.4 W; Typical |
Address area |
Address space per module |
Address space per module, max. | 4 byte |
Analog outputs |
Number of analog outputs | 2 |
Current output, no-load voltage, max. | 18 V |
Cycle time (all channels) max. | 250 µs |
Output ranges, current |
-20 to +20 mA | Yes |
4 to 20 mA | Yes |
Connection of actuators |
for current output 2-conductor connection | Yes |
Load impedance (in rated range of output) |
with current outputs, max. | 500 Ω |
with current outputs, inductive load, max. | 1 mH; for TWA 100µs |
Destruction limits against externally applied voltages and currents |
Current, max. | 15 mA; Max. 15 V / 5 hours (higher voltages not permissible even briefly) |
[nicht versorgt: TAK_ABT299_001_000] |
Cable length, shielded, max. | 200 m; Max. 20 m for TWA 100 µs |
Analog value creation |
Integrations and conversion time/ resolution per channel |
Resolution with overrange (bit including sign), max. | 16 bit |
Settling time |
for resistive load | 0.05 ms |
for capacitive load | 0.05 ms; at a load of up to 500 ohms/100 nF and a max. cable length of 20 m |
for inductive load | 0.05 ms |
Errors/accuracies |
Output ripple (based on output area, bandwidth 0 to 50 kHz) | +/- 0,02 % |
Linearity error (relative to output area) | +/- 0,03 %; with resistive load |
Temperature error (relative to output area) | +/- 0,01 %/K |
Crosstalk between the outputs, min. | -60 dB |
Repeat accuracy in settled status at 25 °C (relative to output area) | +/- 0,03 % |
Operational limit in overall temperature range |
Current, relative to output area | +/- 0,2 %; Specified value applies to loads from 200 to 350 Ohm, deviating operational limits for loads up to 200 Ohm and from 350 to 500 Ohm with up to 0.4% |
Basic error limit (operational limit at 25 °C) |
Current, relative to output area | +/- 0,1 %; Specified value applies for loads from 200 to 350 ohms, deviating basic error limits for loads up to 200 ohms and from 350 to 500 ohms with up to 0.3% |
Isochronous mode |
Isochronous mode | Yes |
Interrupts/diagnostics/status information |
Substitute values connectable | Yes |
Diagnoses |
Diagnostic functions | Yes |
Diagnostic information readable | Yes |
Wire break | Yes |
Group error | Yes |
Diagnostics indication LED |
Group error SF (red) | Yes |
Parameter |
Remark | 7 bytes |
Output type/range | deactivated / +/-20 mA / 4 to 20 mA |
Diagnosis: wire break | Disable / enable |
Group diagnostics | Disable / enable |
Behavior on CPU/Master STOP | Output current and de-energized/substitute a value/keep last value |
Galvanic isolation |
Galvanic isolation analog outputs |
Galvanic isolation analog outputs | Yes |
between the channels | No |
between the channels and the backplane bus | Yes |
between the channels and the load voltage L+ | Yes |
Permissible potential difference |
between MANA and M internally (UISO) | 75 VDC / 60 VAC |
Isolation |
Isolation checked with | 500 V DC |
Dimensions |
Width | 15 mm |
Height | 81 mm |
Depth | 52 mm |
Weight |
Weight, approx. | 45 g |