SIMATIC DP, ELECTRONIC MODULE FOR ET 200S, 2 AI TC STANDARD, 15 MM WIDE, 15 BIT + SIGN +/-80MV; CHARACTERISTICS LINEARIZATION FOR THERMOELEMENTS OF: B, E, J, K, L, N, R, S, T TYPES, CYCLE TIME 65 MS/CHANNEL WITH LED SF (GROUP FAULT) |
Supply voltage |
Load voltage L+ |
Rated value (DC) | 24 V; From power module |
Reverse polarity protection | Yes |
Input current |
from load voltage L+ (without load), max. | 30 mA |
from backplane bus 3.3 V DC, max. | 10 mA |
Power losses |
Power loss, typ. | 0.6 W |
Address area |
Address space per module |
Address space per module, max. | 4 byte |
Analog inputs |
Number of analog inputs | 2 |
permissible input voltage for voltage input (destruction limit), max. | 10 V; Permanent |
Cycle time (all channels) max. | Number of active channels per module x basic conversion time |
Technical unit for temperature measurement adjustable | No |
Input ranges |
Voltage | Yes |
Thermocouple | Yes |
Input ranges (rated values), voltages |
-80 mV to +80 mV | Yes |
Input resistance (-80 mV to +80 mV) | 1 MΩ |
Input ranges (rated values), thermoelements |
Type B | Yes |
Input resistance (Type B) | 1 MΩ |
Type E | Yes |
Input resistance (Type E) | 1 MΩ |
Type J | Yes |
Input resistance (type J) | 1 MΩ |
Type K | Yes |
Input resistance (Type K) | 1 MΩ |
Type L | Yes |
Input resistance (Type L) | 1 MΩ |
Type N | Yes |
Input resistance (Type N) | 1 MΩ |
Type R | Yes |
Input resistance (Type R) | 1 MΩ |
Type S | Yes |
Input resistance (Type S) | 1 MΩ |
Type T | Yes |
Input resistance (Type T) | 1 MΩ |
Characteristic linearization |
Parameterizable | Yes; Type B, E, J, K, L, N, R, S, T to IEC 584 |
Temperature compensation |
internal temperature compensation | Not possible |
external temperature compensation with compensations socket | Yes; possible, one external compensating box per channel |
Cable length |
Cable length, shielded, max. | 50 m |
Analog value creation |
Measurement principle | integrating |
Integrations and conversion time/ resolution per channel |
Resolution with overrange (bit including sign), max. | 16 bit; 15 bits + sign |
Integration time, parameterizable | Yes |
Integration time, ms | 16.7 / 20 ms |
Interference voltage suppression for interference frequency f1 in Hz | 60 / 50 Hz |
Conversion time (per channel) | 65 s; 55 / 65 ms (additional 20 ms on activated wire-break test) |
Smoothing of measured values |
Parameterizable | Yes; In four stages by means of digital filtering |
Step: None | Yes; 1 x cycle time |
Step: low | Yes; 4 x cycle time |
Step: Medium | Yes; 32 x cycle time |
Step: High | Yes; 64 x cycle time |
Encoder |
Connection of signal encoders |
for voltage measurement | Yes |
Errors/accuracies |
Linearity error (relative to input area) | +/- 0,01 % |
Temperature error (relative to input area) | +/- 0,005 %/K |
Crosstalk between the inputs, min. | -50 dB |
Repeat accuracy in settled status at 25 °C (relative to input area) | +/- 0,05 % |
Operational limit in overall temperature range |
Voltage, relative to input area | +/- 0,6 % |
Basic error limit (operational limit at 25 °C) |
Voltage, relative to input area | +/- 0,4 % |
Interference voltage suppression for f = n x (fl +/- 1%), fl = interference frequency |
Series mode interference (peak value of interference < rated value of input range), min. | 70 dB |
common mode voltage (USS < 2.5 V) , min. | 90 dB |
Isochronous mode |
Isochronous mode | No |
Interrupts/diagnostics/status information |
Diagnoses |
Diagnostic functions | Yes; Can be read out |
Diagnostic information readable | Yes |
Wire break | Yes; A break in the wire is only detected for thermocouples |
Group error | Yes |
Overflow/underflow | Yes |
Diagnostics indication LED |
Group error SF (red) | Yes |
Parameter |
Remark | 4 bytes |
Diagnosis: wire break | Disable / enable (wire break is detected only in thermocouples) |
Measurement type/range | Deactivated/ +/- 80 mV/ TC-EL Type T (Cu-CuNi)/ TC-EL Type K (NiCr-Ni)/ TC-EL Type B (PtRh-PtRh)/ TC-EL Type c (Wer-Wer) TC-EL Type N (NiCrSi-NiSi)/ TC-EL Type E (NiCr-CuNi)/ TC-EL Type R (PtRh-Pt)/ TC-EL Type S (PtRh-Pt)/ TC-EL Type J (Fe-Cu-Ni)/ TC |
Group diagnostics | Disable / enable |
Overflow/underflow | Disable / enable |
Comparison point | none / RTD |
Comparison point number | None / 1 / 2 / 3 / 4 / 5 / 6 / 7 / 8 |
Unit | Celsius |
Galvanic isolation |
Galvanic isolation analog inputs |
between the channels | No |
between the channels and the backplane bus | Yes |
between the channels and the load voltage L+ | Yes |
Permissible potential difference |
between inputs and MANA (UCM) | 2 V AC PP |
between MANA and M internally (UISO) | 75 VDC / 60 VAC |
Isolation |
Isolation checked with | 500 V DC |
Dimensions |
Width | 15 mm |
Height | 81 mm |
Depth | 52 mm |
Weight |
Weight, approx. | 40 g |
Status | Sep 14, 2011 |