SIMATIC DP, ELECTRONIC MODULE ET 200S: 2AI HIGH SPEED I-4WIRE 4 - 20MA; 16BIT, 15 MM WIDTH, FOR 4-WIRE TRANSDUCER, CYCLE TIME OF MODULE: 0.1MS, WITH LED SF (GROUP FAULT)
Supply voltage
Load voltage L+
Rated value (DC)24 V
Short-circuit protectionYes
Reverse polarity protectionYes
Input current
from load voltage L+ (without load), max.80 mA; without load
from backplane bus 3.3 V DC, max.10 mA
Output voltage
Power supply to the transmitters
presentYes
short-circuit proofYes
Encoder supply
Number of outputs2
Output voltage24 V
Output current, rated value90 mA; Per channel
Output current, permissible range0 to 90 mA
Output current
Short-circuit protectionYes
Power losses
Power loss, typ.1.9 W
Address area
Address space per module
Address space per module, max.4 byte
Analog inputs
Number of analog inputs2
Cycle time (all channels) max.250 µs
permissible input current for current input (destruction limit), max.30 mA
Input ranges
VoltageNo
CurrentYes
ThermocoupleNo
Resistance thermometerNo
ResistanceNo
Input ranges (rated values), currents
0 to 20 mAYes
Input resistance (0 to 20 mA)106 Ω
-20 to +20 mAYes
4 to 20 mAYes
Cable length
Cable length, shielded, max.200 m
Analog value creation
Integrations and conversion time/ resolution per channel
Resolution with overrange (bit including sign), max.16 bit
Smoothing of measured values
ParameterizableYes
Step: NoneYes; 1 x cycle time
Step: lowYes; 4 x cycle time
Step: MediumYes; 16 x cycle time
Step: HighYes; 32 x cycle time
Encoder
Connection of signal encoders
for current measurement as 2-wire transducerNo
Errors/accuracies
Linearity error (relative to input area)+/- 0,03 %
Temperature error (relative to input area)+/- 0,01 %/K
Crosstalk between the inputs, min.-50 dB
Repeat accuracy in settled status at 25 °C (relative to input area)+/- 0,1 %
Operational limit in overall temperature range
Current, relative to input area+/- 0,3 %
Basic error limit (operational limit at 25 °C)
Current, relative to input area+/- 0,2 %
Isochronous mode
Isochronous modeYes
Interrupts/diagnostics/status information
Alarms
Hardware interruptYes
Diagnoses
Diagnostic functionsYes
Diagnostic information readableYes
Wire breakYes; Only with measuring range 4 to 20 mA
Group errorYes
Overflow/underflowYes
Diagnostics indication LED
Group error SF (red)Yes
Parameter
Diagnosis: wire breakAt 4 to 20 mA
Measurement type/range4 to 20 mA, 0 to 20 mA, +/-20 mA
Group diagnosticsYes
Overflow/underflowYes
Galvanic isolation
Galvanic isolation analog inputs
between the channelsNo
between the channels and the backplane busYes
between the channels and the load voltage L+Yes
Permissible potential difference
between MANA and M internally (UISO)75 V DC, 60 V AC
Dimensions
Width15 mm
Module width, max.15 mm
Height81 mm
Depth52 mm
Weight