SIMATIC DP, ELECTRONIC MODULE DIGITAL, FOR ET 200B, W=160MM, 8 RO 24V - 60V DC, DEGR. OF PROTECT. IP20,STANDARD |
Supply voltage |
24 V DC | Yes; L3+; value at t < 0.5 s: 35 V |
permissible range, lower limit (DC) | 18.5 V |
permissible range, upper limit (DC) | 30.2 V |
Input current |
Current consumption, max. | 130 mA; from L3+; logic |
I²t | 0.05 A²·s; with starting current inrush |
Power losses |
Power loss, typ. | 2 W |
Hardware configuration |
Rack |
Required terminal block | TB1/DC, TB1-4/DC, TB3/DC, TB3-4/DC |
Digital outputs |
Number/binary outputs | 8; Relay |
Functionality/short-circuit strength | No |
Controlling a digital input | Yes |
Output voltage |
Rated value (DC) | 24 V; 24 to 60 V DC |
Switching frequency |
with resistive load, max. | 10 Hz |
with inductive load, max. | 2 Hz |
Relay outputs |
Switching capacity of contacts |
with inductive load, max. | 0.5 A; at 30 V DC |
Switching frequency/contacts/at ohmic load/maximum | 2 A; at 24 V DC; max. 1.5 A at 48 V DC; max. 1 A at 60 V DC |
Thermal continuous current, max. | 5 A |
Cable length |
Cable length unshielded, max. | 100 m |
Interfaces |
PROFIBUS DP |
Transmission rate, max. | 12 Mbit/s |
SYNC capability | Yes |
Communication functions |
Bus protocol/transmission protocol | PROFIBUS DP |
Interrupts/diagnostics/status information |
Diagnostics indication LED |
Bus fault BF (red) | Yes |
Run mode RUN (green) | Yes |
Status indicator digital output (green) | Yes |
Galvanic isolation |
between electronic block and PROFIBUS DP | Yes |
Galvanic isolation digital outputs |
Galvanic isolation digital outputs | Yes |
between the channels, in groups of | 1 |
Ambient conditions |
Operating temperature |
horizontal installation, min. | 0 °C |
horizontal installation, max. | 60 °C; 40°C for other mountings |
Air pressure |
permissible range, min. | 795 hPa |
permissible range, max. | 1080 hPa |
Relative humidity |
Operation, min. | 15 % |
Operation, max. | 95 %; RH class 2 in accordance with IEC 1131-2 |
Vibrations |
Operation, checked according to IEC 60068-2-6 | Yes; IEC 68, Part 2-6; 10 to 57 Hz; (constant amplitude 0.075 mm); 57 to 150 Hz; (constant acceleration 1 g) |
Shock test |
checked according to IEC 60068-2-27 | Yes; IEC 68, Part 2-27; half-sine, 15 g, 11 ms |
Degree and class of protection |
IP20 | Yes |
Connection method |
Inputs/outputs | Screw-type and spring-loaded terminals, permanent wiring; 3 and 4-wire connection |
Dimensions |
Width | 160 mm; EB and TB |
Height | 130 mm; EB and TB |
Depth | 60 mm; EB and TB |
Weight |
Weight, approx. | 650 g; EB and TB |