6ES7132-0GF00-0XB0 SIMATIC S5/S7 ET200B

Manufacturer:
SIEMENS
Weight:
0.65kg
Product Range:
Automation Systems

Product Information

SIMATIC DP, ELECTRONIC MODULE DIGITAL, FOR ET 200B, W=160MM, 8 RO 24V - 60V DC, DEGR. OF PROTECT. IP20,STANDARD
Supply voltage
24 V DCYes; L3+; value at t < 0.5 s: 35 V
permissible range, lower limit (DC)18.5 V
permissible range, upper limit (DC)30.2 V
Input current
Current consumption, max.130 mA; from L3+; logic
I²t0.05 A²·s; with starting current inrush
Power losses
Power loss, typ.2 W
Hardware configuration
Rack
Required terminal blockTB1/DC, TB1-4/DC, TB3/DC, TB3-4/DC
Digital outputs
Number/binary outputs8; Relay
Functionality/short-circuit strengthNo
Controlling a digital inputYes
Output voltage
Rated value (DC)24 V; 24 to 60 V DC
Switching frequency
with resistive load, max.10 Hz
with inductive load, max.2 Hz
Relay outputs
Switching capacity of contacts
with inductive load, max.0.5 A; at 30 V DC
Switching frequency/contacts/at ohmic load/maximum2 A; at 24 V DC; max. 1.5 A at 48 V DC; max. 1 A at 60 V DC
Thermal continuous current, max.5 A
Cable length
Cable length unshielded, max.100 m
Interfaces
PROFIBUS DP
Transmission rate, max.12 Mbit/s
SYNC capabilityYes
Communication functions
Bus protocol/transmission protocolPROFIBUS DP
Interrupts/diagnostics/status information
Diagnostics indication LED
Bus fault BF (red)Yes
Run mode RUN (green)Yes
Status indicator digital output (green)Yes
Galvanic isolation
between electronic block and PROFIBUS DPYes
Galvanic isolation digital outputs
Galvanic isolation digital outputsYes
between the channels, in groups of1
Ambient conditions
Operating temperature
horizontal installation, min.0 °C
horizontal installation, max.60 °C; 40°C for other mountings
Air pressure
permissible range, min.795 hPa
permissible range, max.1080 hPa
Relative humidity
Operation, min.15 %
Operation, max.95 %; RH class 2 in accordance with IEC 1131-2
Vibrations
Operation, checked according to IEC 60068-2-6Yes; IEC 68, Part 2-6; 10 to 57 Hz; (constant amplitude 0.075 mm); 57 to 150 Hz; (constant acceleration 1 g)
Shock test
checked according to IEC 60068-2-27Yes; IEC 68, Part 2-27; half-sine, 15 g, 11 ms
Degree and class of protection
IP20Yes
Connection method
Inputs/outputsScrew-type and spring-loaded terminals, permanent wiring; 3 and 4-wire connection
Dimensions
Width160 mm; EB and TB
Height130 mm; EB and TB
Depth60 mm; EB and TB
Weight
Weight, approx.650 g; EB and TB

1 Units in Stock


Call for Availability
Price for:  EachMinimum:  1

Target Price

Offer your acceptable price, and we may make you satisfied.Your Target Price

Technical Support

Technical Support

Customer Reviews

Write Review

Customer Q&A Exchange

Ask A Question