SIMATIC DP, ELECTRONIC MODULE DIGITAL, FOR ET 200B, W=235MM, 16 DO 24V DC, 2A, DEGR. OF PROTECT. IP20,STANDARD |
Supply voltage |
24 V DC | Yes; L1+, L2+, L3+, L4+, L5+; value at t < 0.5 s: 35 V |
permissible range, lower limit (DC) | 18.5 V |
permissible range, upper limit (DC) | 30.2 V |
Input current |
Current consumption, max. | 100 mA; From L5+; logic |
I²t | 0.05 A²·s; with starting current inrush |
Power losses |
Power loss, typ. | 7 W |
Hardware configuration |
Rack |
Required terminal block | TB2/DC, TB2-4/DC, TB4/DC, TB4-4/DC |
Digital outputs |
Number/binary outputs | 16 |
Functionality/short-circuit strength | Yes; Electronic |
Limitation of inductive shutdown voltage to | typ. (L1+ to L4+) -50 V |
Lamp load, max. | 10 W |
Controlling a digital input | Yes |
Output voltage |
Rated value (DC) | 24 V |
for signal "0" (DC), max. | 2 V; Idling |
for signal "1", min. | UE -3 V |
Output current |
for signal "1" permissible range for 0 to 60 °C, min. | 2 A; in groups of 4 |
for signal "0" residual current, max. | 1 mA |
Switching frequency |
with resistive load, max. | 100 Hz |
with inductive load, max. | 0.5 Hz |
on lamp load, max. | 8 Hz |
Aggregate current of outputs (per group) |
Digital inputs / Number of inputs that can be driven in parallel / all mounting positions |
up to 60 °C, max. | 4 A |
Cable length |
Cable length unshielded, max. | 100 m |
Interfaces |
PROFIBUS DP |
Transmission rate, max. | 12 Mbit/s |
SYNC capability | Yes |
Communication functions |
Bus protocol/transmission protocol | PROFIBUS DP |
Interrupts/diagnostics/status information |
Diagnostics indication LED |
Bus fault BF (red) | Yes |
Run mode RUN (green) | Yes |
Status indicator digital output (green) | Yes |
Galvanic isolation |
between electronic block and PROFIBUS DP | Yes |
Galvanic isolation digital outputs |
Galvanic isolation digital outputs | Yes |
between the channels, in groups of | 4 |
Ambient conditions |
Operating temperature |
horizontal installation, min. | 0 °C |
horizontal installation, max. | 60 °C; 40°C for other mountings |
Air pressure |
permissible range, min. | 795 hPa |
permissible range, max. | 1080 hPa |
Relative humidity |
Operation, min. | 15 % |
Operation, max. | 95 %; RH class 2 in accordance with IEC 1131-2 |
Vibrations |
Operation, checked according to IEC 60068-2-6 | Yes; IEC 68, Part 2-6; 10 to 57 Hz; (constant amplitude 0.075 mm); 57 to 150 Hz; (constant acceleration 1 g) |
Shock test |
checked according to IEC 60068-2-27 | Yes; IEC 68, Part 2-27; half-sine, 15 g, 11 ms |
Degree and class of protection |
IP20 | Yes |
Connection method |
Inputs/outputs | Screw-type and spring-loaded terminals, permanent wiring; 3 and 4-wire connection |
Dimensions |
Width | 235 mm; EB and TB |
Height | 130 mm; EB and TB |
Depth | 60 mm; EB and TB |
Weight |
Weight, approx. | 900 g; EB and TB |