Your cart is empty

6ES7123-1GB50-0AB0 SIMATIC SC,ELECTRONIC SUBMODULE

Manufacturer:
SIEMENS
Weight:
0.02kg
Product Range:
Automation Systems

Product Information

SIMATIC SC,ELECTRONIC SUBMODULE 2 AI, 4..20MA, 2 MS CONVERSION TIME P. CHANNEL 2-WIRE-TRANSDUCER
Supply voltage
Rated value (DC)24 V
Reverse polarity protectionYes
Input current
from supply voltage L+, max.30 mA
Output voltage
Power supply to the transmitters
presentYes
short-circuit proofYes
Supply current, max.100 mA
Power losses
Power loss, max.0.6 W
Hardware configuration
Rack
Required terminal blockTB 16IM-SC
Analog inputs
Number of analog inputs2
permissible input current for current input (destruction limit), max.35 mA; 35 mA continuous, 150 mA for max. 1 s (mark to space ratio 1:20)
Input ranges
CurrentYes
Input ranges (rated values), currents
4 to 20 mAYes
Input resistance (4 to 20 mA)50 Ω
Characteristic linearization
ParameterizableNo
Temperature compensation
ParameterizableNo
[nicht versorgt: TAK_ABT296_001_000]
Cable length, shielded, max.200 m
Analog value creation
Measurement principleActual value encryption
Integrations and conversion time/ resolution per channel
Resolution (incl. overrange)4 to 20 mA: 12 bit
Resolution with overrange (bit including sign), max.12 bit
Integration time, parameterizableNo
Basic conversion time, ms1 ms
Smoothing of measured values
ParameterizableYes; parameterizable in 4 stages by means of digital filtering
Step: NoneYes; 1 x cycle time
Step: lowYes; 8 x cycle time
Step: MediumYes; 64 x cycle time
Step: HighYes; 128 x cycle time
Encoder
Connection of signal encoders
for current measurement as 2-wire transducerYes
Burden of 2-wire transmitter, max.750 Ω
Errors/accuracies
Linearity error (relative to input area)+/- 0,05 %
Temperature error (relative to input area)+/- 0,01 %/K
Crosstalk between the inputs, min.50 dB; At 50/60 Hz
Repeat accuracy in settled status at 25 °C (relative to input area)+/- 0,1 %
Operational limit in overall temperature range
Current, relative to input area+/- 1 %
Basic error limit (operational limit at 25 °C)
Current, relative to input area+/- 0,7 %
Interference voltage suppression for f = n x (fl +/- 1%), fl = interference frequency
Series mode interference (peak value of interference < rated value of input range), min.70 dB; With smoothing factor k = 128
common mode voltage (USS < 2.5 V) , min.50 dB
Interrupts/diagnostics/status information
Alarms
AlarmsNo
Diagnoses
Diagnostic functionsNo
Galvanic isolation
Galvanic isolation analog inputs
between the channelsNo
between the channels and the backplane busNo
between the channels and the power supply of the electronicsNo
Permissible potential difference
between inputs and MANA (UCM)2 V DC / 2 Vpp AC
Dimensions
Width10 mm
Height64 mm
Depth51 mm
Required slots1; from 8
Weight
Weight, approx.20 g

1 Units in Stock


Call for Availability
Price for:  EachMinimum:  1

Target Price

Offer your acceptable price, and we may make you satisfied.Your Target Price

Technical Support

Technical Support

Customer Reviews

Write Review

Customer Q&A Exchange

Ask A Question

Additional Images