Your cart is empty

6AG1677-1DD00-4BB0 SIPLUS S7 MEC EC31-RTX

Manufacturer:
SIEMENS
Weight:
1.5kg
Product Range:
Converters

Product Information

SIPLUS S7 MEC EC31-RTX FOR MEDIAL STRESS WITH CONFORMAL COATING (LEVEL 1 BASED ON 6ES7677-1DD00-0BB0
General information
Hardware product version04
Firmware versionV1.3
PC configuration
Computer platformSIMATIC S7 modular embedded controller
Processor selectionIntel Core Duo 1.2 GHz
Main memory1 GB RAM
Flash Disk2 GB
Operating systemsWindows XP embedded SP2 FP2007
Installed software
ControlSIMATIC WinAC RTX 2009
CommunicationYes
Supply voltage
Rated value, 24 V DCYes
permissible range, lower limit (DC)20.4 V
permissible range, upper limit (DC)28.8 V
Mains buffering
Mains/voltage failure stored energy time5 ms
Input current
Rated value at 24 V DC800 mA; without backplane bus and USB power supply
Power losses
Power loss, typ.34 W
Memory
Memory type512 KB non-volatile memory for retentive data
CPU processing times
for bit operations, min.0.0040 µs; typ.
for fixed point arithmetic, min.0.0030 µs; typ.
for floating point arithmetic, min.0.0040 µs; typ.
CPU-blocks
DB
Number, max.Max. code size and max. data size: 4 MB each
Size, max.64 Kibyte
FB
Number, max.Max. code size and max. data size: 4 MB each
Size, max.64 Kibyte
FC
Number, max.Max. code size and max. data size: 4 MB each
Size, max.64 Kibyte
OB
Number, max.Max. code size and max. data size: 4 MB each
Size, max.64 Kibyte
Number of free cycle OBs1; OB 1
Number of time alarm OBs1; OB 10
Number of delay alarm OBs1; OB 20
Number of time interrupt OBs9; OB 30-38
Number of process alarm OBs1; OB 40
Number of startup OBs2; OB 100, 102
Number of asynchronous error OBs7; OB 80, 82-85, 86, 88
Number of synchronous error OBs2; OB 121, 122
Nesting depth
per priority class24
additional within an error OB24
Counters, timers and their retentivity
S7 counter
Number2,048
Retentivity
adjustableYes
lower limit0
upper limit2,047
preset8
Counting range
adjustableYes
lower limit0
upper limit999
IEC counter
presentYes
TypeSFB
S7 times
Number2,048
Retentivity
adjustableYes
lower limit0
upper limit2,047
Time range
lower limit10 ms
upper limit9,990 s
IEC timer
presentYes
TypeSFB
Data areas and their retentivity
retentive data area, total512 KB
Flag
Number, max.16 Kibyte
of which retentive without batteryMB 0 to MB 16383
Retentivity presetMB 0 to MB 15
Number of clock memories8
Data blocks
Number, max.Max. code size and max. data size: 4 MB each
Size, max.64 Kibyte
Address area
I/O address area
Inputs16 Kibyte
Outputs16 Kibyte
of which, distributed
Inputs8 Kibyte
Outputs8 Kibyte
Process image
Inputs, adjustable16 Kibyte
Outputs, adjustable16 Kibyte
Inputs, default512 byte
Outputs, default512 byte
Subprocess images
Number of subprocess images, max.15
Digital channels
Inputs128,000
Outputs128,000
Analog channels
Inputs8,000
Outputs8,000
Time of day
Clock
Hardware clock (real-time clock)Yes; Resolution: 1 s
Clock synchronization
supportedYes
to PC-CP, slaveYes
on Ethernet via NTPYes
1st interface
Type of interfacePROFINET
Physics2x RJ45
Automatic detection of transmission speedYes
AutonegotiationYes
AutocrossingYes
Number of connection resources32
Functionality
MPINo
DP masterNo
DP slaveNo
PROFINET IO DeviceNo
PROFINET IO ControllerYes
PROFINET CBAYes
Open IE communicationYes
Point-to-point connectionNo
PROFINET IO Controller
Services
PG/OP communicationYes
S7 routingYes
S7 communicationYes
Isochronous modeNo
Number of connectable IO devices, max.256
Number of IO devices with IRT and the option "high flexibility"64
IRT, supportedYes
Prioritized startup supportedYes
Number of IO Devices, max.32
Activation/deactivation of IO DevicesYes
Number of IO Devices that can be simultaneously activated/deactivated, max.8
IO Devices changing during operation (partner ports), supportedYes
Max. number of IO devices per tool8
Send cyclesAdjustable: 250 µs, 500 µs and 1 ms
Updating times250 µs - 128 ms (with signal cycle 250 µs); 500 µs - 256 ms (with signal cycle 500 µs); 1 ms - 512 ms (with signal cycle 1 ms)
Address area
Inputs, max.16 Kibyte
Outputs, max.16 Kibyte
User data per address area, max.2 Kibyte
User data consistency, max.256 byte
PROFINET CBA
acyclic transmissionYes
Cyclic transmissionYes
Open IE communication
Open IE communication, supportedYes
Number of connections, max.32
Local port numbers used at the system end0, 20, 21, 23, 25, 80, 102, 135, 161, 8080, 34962, 34963, 34964, 65532, 65533, 65534, 65535
PROFINET functions
Detection of accessible nodes, supportedYes; DCP
Assignment of the IP address, supportedYes; DCP
Assignment of the device name, supportedYes; DCP
Topology recognition, supportedYes; LLDP, LLDP MIB, SNMP
Extended network diagnostics with Standard MIB II, supportedYes; Standard MIB II, SNMP
2nd interface
Type of interfaceIntegrated Ethernet interface
PhysicsEthernet RJ45
Automatic detection of transmission speedYes
AutonegotiationYes
AutocrossingNo
Number of connection resources32
Functionality
PROFINET IO ControllerNo
PROFINET IO DeviceNo
PROFINET CBANo
Communication functions
PG/OP communicationYes
Global data communication
supportedNo
S7 basic communication
supportedNo
S7 communication
supportedYes
as serverYes
as clientYes
Open IE communication
TCP/IPYes; Via integrated PROFINET interface (X1) and loadable FBs
Number of connections, max.32
Data length, max.8,192 byte
ISO-on-TCP (RFC1006)No
UDPYes; Via integrated PROFINET interface (X1) and loadable FBs
Number of connections, max.32
Data length, max.1,472 byte
Number of connections
overall64
usable for PG communication
reserved for PG communication1
usable for OP communication
reserved for OP communication1
S7 message functions
Number of login stations for message functions, max.62; The alarm functions cannot currently be used for central bus modules
Process diagnostic messagesYes; Alarm_S
Test commissioning functions
Status/control
Status/control variableYes
Forcing
ForcingNo
Diagnostic buffer
presentYes
EMC
Emission of radio interference acc. to EN 55 011
Limit class A, for use in industrial areasYes
Ambient conditions
Operating temperature
Min.0 °C
max.50 °C
Storage/transport temperature
Min.-40 °C
max.70 °C
Vibrations
Operation, checked according to IEC 60068-2-6Yes
Transport tested checked to IEC 60068-2-6Yes
Shock test
checked according to IEC 60068-2-27Yes
checked according to IEC 60068-2-29Yes
Shock testing
checked according to IEC 60068-2-29Yes
Operation, checked according to IEC 60068-2-29Operation, tested according to IEC 60068-2-27
Storage/transport, checked to IEC 60068-2-29Yes
Degree and class of protection
IP20Yes
Standards, approvals, certificates
CE markYes
CSA approvalNo
cULusNo
C-TICKNo
FM approvalNo
Configuration
Configuration software
STEP 7Yes
programming
Programming language
LADYes
FBDYes
STLYes
SCLYes
CFCYes
GRAPHYes
HiGraph®Yes
Dimensions
Width160 mm
Height125 mm
Depth115 mm
[nicht versorgt: TAK_ABV654_001_000]
[nicht versorgt: TAK_ABV463_001_000]
Product version
STEP 7Yes; V5.4 SP4 and higher + HW update/iMap V3.0 SP1

1 Units in Stock


Call for Availability
Price for:  EachMinimum:  1

Target Price

Offer your acceptable price, and we may make you satisfied.Your Target Price

Technical Support

Technical Support

Customer Reviews

Write Review

Customer Q&A Exchange

Ask A Question