SIPLUS S7-400 CPU414-4H FOR MEDIAL STRESS BASED ON 6ES7414-4HM14-0AB0 |
General information |
Hardware product version | 1 |
Firmware version | V4.5 |
[nicht versorgt: TAK_ABW067_001_000] |
associated programming package | STEP7 V 5.3 SP2 or higher with HW update |
CiR - Configuration in RUN |
CiR synchronization time, basic load | 100 ms |
CiR synchronization time, time per I/O slave | 25 µs |
Supply voltage |
24 V DC | No; Power supply via system power supply |
Input current |
from backplane bus 5 V DC, typ. | 1.4 A |
from backplane bus 5 V DC, max. | 1.7 A |
from backplane bus 24 V DC, max. | 150 mA; Per DP interface |
from interface 5 V DC, max. | 90 mA; At each DP interface |
Power losses |
Power loss, typ. | 6 W |
Backup battery |
Battery operation | |
Backup current, typ. | 190 µA; Valid up to 40°C |
Backup current, max. | 660 µA |
Backup time, max. | Dealt with in the module data manual with the secondary conditions and the factors of influence |
Feeding of external backup voltage to CPU | 5 to 15 VDC |
Feeding of external backup voltage to CPU | 5 to 15 VDC |
Memory |
Work memory |
integrated | 2.8 Mbyte |
integrated (for program) | 1.4 Mbyte |
integrated (for data) | 1.4 Mbyte |
expandable | No |
Load memory |
expandable FEPROM | Yes |
expandable FEPROM, max. | 64 Mbyte |
integrated RAM, max. | 256 Kibyte |
expandable RAM | Yes |
expandable RAM, max. | 64 Mbyte |
Backup |
present | Yes |
with battery | Yes; all data |
without battery | No |
CPU processing times |
for bit operations, min. | 0.045 µs |
for word operations, min. | 0.045 µs |
for fixed point arithmetic, min. | 0.045 µs |
for floating point arithmetic, min. | 0.135 µs |
CPU-blocks |
DB |
Number, max. | 4,095; Number range: 1 to 4095 |
Size, max. | 64 Kibyte |
FB |
Number, max. | 2,048; Number range: 0 to 2047 |
Size, max. | 64 Kibyte |
FC |
Number, max. | 2,048; Number range: 0 to 2047 |
Size, max. | 64 Kibyte |
OB |
Size, max. | 64 Kibyte |
Number of time alarm OBs | 4 |
Number of delay alarm OBs | 4 |
Number of time interrupt OBs | 4 |
Number of process alarm OBs | 4 |
Nesting depth |
per priority class | 24 |
additional within an error OB | 1 |
Counters, timers and their retentivity |
S7 counter |
Number | 2,048 |
Retentivity |
adjustable | Yes |
lower limit | 0 |
upper limit | 2,047 |
preset | Z 0 to Z 7 |
Counting range |
lower limit | 0 |
upper limit | 999 |
IEC counter |
present | Yes |
Type | SFB |
S7 times |
Number | 2,048 |
Retentivity |
adjustable | Yes |
lower limit | 0 |
upper limit | 2,047 |
preset | No times retentive |
Time range |
lower limit | 10 ms |
upper limit | 9,990 s |
IEC timer |
present | Yes |
Type | SFB |
Data areas and their retentivity |
retentive data area, total | Total working and load memory (with backup battery) |
Flag |
Number, max. | 8 Kibyte |
Retentivity available | Yes |
Retentivity preset | MB 0 to MB 15 |
Number of clock memories | 8; (in 1 memory byte) |
Data blocks |
Number, max. | 4,095; Number range: 1 to 4095 |
Size, max. | 64 Kibyte |
Local data |
adjustable, max. | 16 Kibyte |
preset | 8 Kibyte |
Address area |
I/O address area |
Inputs | 8 Kibyte |
Outputs | 8 Kibyte |
of which, distributed |
MPI/DP interface, inputs | 2 Kibyte |
MPI/DP interface, outputs | 2 Kibyte |
DP interface, inputs | 6 Kibyte |
DP interface, outputs | 6 Kibyte |
Process image |
Inputs, adjustable | 8 Kibyte |
Outputs, adjustable | 8 Kibyte |
Inputs, default | 256 byte |
Outputs, default | 256 byte |
consistent data, max. | 244 byte |
Access to consistent data in process image | Yes |
Subprocess images |
Number of subprocess images, max. | 15 |
Digital channels |
Inputs | 65,536 |
Outputs | 65,536 |
Inputs, of which central | 65,536 |
Outputs, of which central | 65,536 |
Analog channels |
Inputs | 4,096 |
Outputs | 4,096 |
Inputs, of which central | 4,096 |
Outputs, of which central | 4,096 |
Hardware configuration |
Expansion devices, max. | 21 |
connectable OPs | 31 without message processing, 8 with message processing |
Multicomputing | No |
Interface modules |
Number of connectable IMs (total), max. | 6 |
Number of connectable IM 460s, max. | 6 |
Number of connectable IM 463s, max. | 4; Single mode only |
Number of DP masters |
integrated | 2 |
via CP | 10 |
Mixed mode IM + CP permitted | No |
Number of operable FMs and CPs (recommended) |
FM | See manual Automation System S7-400H fault-tolerant systems. Limited by number of slots and number of connections |
CP, point-to-point | See manual Automation System S7-400H fault-tolerant systems. Limited by number of slots and number of connections |
PROFIBUS and Ethernet CPs | 14; Of which max. 10 CP as DP master |
Time of day |
Clock |
Hardware clock (real-time clock) | Yes |
battery-backed and synchronizable | Yes |
Resolution | 1 ms |
Deviation per day (buffered), max. | 1.7 ms; Power off |
Deviation per day (unbuffered) max. | 8.6 ms; Power on |
Operating hours counter |
Number | 8 |
Number/Number range | 0 to 7 |
Range of values | 0 to 32767 hours |
Granularity | 1 hour |
retentive | Yes |
Clock synchronization |
supported | Yes |
to MPI, master | Yes |
to MPI, slave | Yes |
to DP, master | Yes |
to DP, slave | Yes |
in AS, master | Yes |
in AS, slave | Yes |
Time difference in system when synchronizing via |
MPI, max. | 200 ms |
Digital outputs |
integrated channels (DO) | 0 |
Analog inputs |
Integrated channels (AI) | 0 |
Interfaces |
Number of parallel interfaces | 0 |
Number of 20 mA interfaces (TTY) | 0 |
Number of RS 232 interfaces | 0 |
Number of RS 422 interfaces | 0 |
Number of other hardware interfaces | 0 |
1st interface |
Type of interface | integrated |
Physics | RS 485 / PROFIBUS + MPI |
Isolated | Yes |
Power supply to interface (15 to 30 V DC), max. | 150 mA |
Number of connection resources | MPI: 32, DP: 32 |
Functionality |
MPI | Yes |
DP master | Yes |
DP slave | No |
MPI |
Number of connections | 32 |
Services |
PG/OP communication | Yes |
Routing | Yes |
Global data communication | No |
S7 basic communication | No |
S7 communication | Yes |
Transmission rate, max. | 12 Mbit/s |
DP master |
Number of connections, max. | 16 |
Services |
PG/OP communication | Yes |
Routing | Yes |
Global data communication | No |
S7 basic communication | No |
S7 communication | Yes |
Equidistance mode support | No |
SYNC/FREEZE | No |
Activation/deactivation of DP slaves | No |
Direct data exchange (slave-to-slave communication) | No |
Transmission rate, max. | 12 Mbit/s |
Number of DP slaves, max. | 32 |
Address area |
Inputs, max. | 2 Kibyte |
Outputs, max. | 2 Kibyte |
User data per DP slave |
User data per DP slave, max. | 244 byte |
Inputs, max. | 244 byte |
Outputs, max. | 244 byte |
Slots, max. | 244 |
per slot, max. | 128 byte |
2nd interface |
Type of interface | integrated |
Physics | RS 485 / PROFIBUS + MPI |
Isolated | Yes |
Power supply to interface (15 to 30 V DC), max. | 150 mA |
Media redundancy |
Number of connection resources | 16 |
Functionality |
DP master | Yes |
DP slave | No |
DP master |
Number of connections, max. | 16 |
Services |
PG/OP communication | Yes |
Routing | Yes |
Global data communication | No |
S7 basic communication | No |
S7 communication | Yes |
Equidistance mode support | No |
SYNC/FREEZE | No |
Activation/deactivation of DP slaves | No |
Direct data exchange (slave-to-slave communication) | No |
Transmission rate, max. | 12 Mbit/s |
Number of DP slaves, max. | 96 |
Address area |
Inputs, max. | 6 Kibyte |
Outputs, max. | 6 Kibyte |
User data per DP slave |
User data per DP slave, max. | 244 byte |
Inputs, max. | 244 byte |
Outputs, max. | 244 byte |
Slots, max. | 244 |
per slot, max. | 128 byte |
3rd interface |
Type of interface | Pluggable synchronization submodule (FO) |
Plug-in interface modules | Synchronization submodule IF 960 6ES7 960-1AA04-0XA0 or 6ES7 960-1AB04-0XA0 |
4th interface |
Type of interface | Pluggable synchronization submodule (FO) |
Plug-in interface modules | Synchronization submodule IF 960 6ES7 960-1AA04-0XA0 or 6ES7 960-1AB04-0XA0 |
Communication functions |
PG/OP communication | Yes |
Number of connectable OPs without message processing | 31 |
Number of connectable OPs with message processing | 8 |
Global data communication |
supported | No |
S7 basic communication |
supported | No |
S7 communication |
supported | Yes |
as server | Yes |
as client | Yes |
User data per job, max. | 64 Kibyte |
User data per job (of which consistent), max. | 462 byte; 1 variable |
S5-compatible communication |
supported | Yes; (via CP max. 10 and FC AG_SEND and FC AG_RECV) |
User data per job, max. | 8 Kibyte |
User data per job (of which consistent), max. | 240 byte |
Number of simultaneous AG-SEND/AG-RECV orders per CPU, max. | 24/24 |
Standard communication (FMS) |
supported | Yes; Via CP and loadable FB |
Number of connections |
overall | 32 |
usable for PG communication | |
reserved for PG communication | 1 |
Adjustable for PG communication, max. | 0 |
usable for OP communication | |
reserved for OP communication | 1 |
adjustable for OP communication, max. | 0 |
usable for S7 basic communication | |
Reserved for S7 basic communication | 0 |
adjustable for S7 basic communication, max. | 0 |
usable for S7 communication | |
reserved for S7 communication | 0 |
Adjustable for S7 communication, max. | 0 |
usable for routing | |
Reserved for routing | 0 |
adjustable for routing, max. | 0 |
S7 message functions |
Number of login stations for message functions, max. | 8 |
Symbol-related messages | No |
Number of additional values |
Block related messages | Yes |
simultaneously active Alarm-S blocks, max. | 100 |
Alarm 8-blocks | Yes |
Number of instances for alarm 8 and S7 communication blocks, max. | 1,200 |
preset, max. | 900 |
Process control messages | Yes |
Number of archives that can log on simultaneously (SFB 37 AR_SEND) | 16 |
Test commissioning functions |
Status/control |
Status/control variable | Yes |
Variables | Inputs/outputs, memory bits, DBs, distributed I/Os, timers, counters |
Number of variables, max. | 70 |
Forcing |
Forcing | Yes |
Force, variables | Inputs/outputs, bit memories, distributed I/Os |
Number of variables, max. | 256 |
Status block | Yes |
Single step | Yes |
Number of breakpoints | 4 |
Diagnostic buffer |
present | Yes |
Number of entries, max. | 3,200 |
adjustable | Yes |
preset | 120 |
Configuration |
Configuration software |
STEP 7 | Yes |
programming |
Programming language |
LAD | Yes |
FBD | Yes |
STL | Yes |
SCL | Yes |
CFC | Yes |
GRAPH | Yes |
HiGraph® | Yes |
Command set | see instruction list |
Nesting levels | 8 |
Access to consistent data in process image | Yes |
System functions (SFC) | see instruction list |
Number of simultaneously active SFCs |
RD_REC | 8 |
WR_REC | 8 |
WR_PARM | 8 |
PARM_MOD | 1 |
WR_DPARM | 2 |
DPNRM_DG | 8 |
RDSYSST | 8 |
DP_TOPOL | 1 |
System function blocks (SFB) | see instruction list |
Number of simultaneously active SFBs |
RD_REC | 8 |
WR_REC | 8 |
Know-how protection |
User program protection/password protection | Yes |
Dimensions |
Width | 50 mm |
Height | 290 mm |
Depth | 219 mm |
Required slots | 2 |
Weight |
Weight, approx. | 995 g |
internTechDB |
Characteristics will be deleted after 2012-12-31 |
Product version |
STEP 7 | Yes; With hardware update as of STEP7 V5.3 SP2 |