CIRCUIT-BREAKER, 7...10 A N-RELEASE 208 A, SIZE S0 TRANSFORMER PROTECTION, CL. 10, SCREW CONNECTION STANDARD BREAKING CAPACITY |
General technical data: |
Product brand name | | SIRIUS |
product designation | | circuit breaker |
Size of the circuit-breaker | | S0 |
Trip class | | CLASS 10 |
Degree of pollution | | 3 |
Installation altitude / at a height over sea level / maximum | m | 2,000 |
Protection class IP / on the front | | IP20 |
Ambient temperature | | |
| °C | -50…80 |
| °C | -20…70 |
| °C | 80…-50 |
Resistance against shock | | 25g / 11 ms |
Insulation voltage / rated value | V | 690 |
Impulse voltage resistance / rated value | V | 6,000 |
Active power loss / total / typical | W | 7 |
Item designation | | |
- according to DIN 40719 extendable after IEC 204-2 / according to IEC 750
| | Q |
- according to DIN EN 61346-2
| | Q |
Mechanical operating cycles as operating time / of the main contacts / typical | | 100,000 |
Type of the driving mechanism / motor drive | | No |
Design of the operating mechanism | | selector switch |
Product function | | |
| | Yes |
- phase disturbance recognition
| | Yes |
Product component | | |
| | No |
- undervoltage release mechanism
| | No |
| | No |
Product extension / optional / motor drive | | No |
Main circuit: |
Number of poles / for main current circuit | | 3 |
type of voltage | | AC/DC |
Operating voltage / at AC-3 / rated value / maximum | V | 690 |
Operating current / at AC-3 / at 400 V / rated value | A | 10 |
Frequency of operation / at AC-3 / according to IEC 60947-6-2 / maximum | 1/h | 15 |
Arrangement of electrical connectors / for main current circuit | | front side |
Adjustable response current | | |
- of the non-delayed short-circuit release
| A | 208…208 |
Adjustable response current | | |
- of the current-dependent overload release
| A | 7…10 |
Continuous current / rated value | A | 10 |
Product extension / auxiliary switch | | Yes |
Auxiliary circuit: |
Number of NC contacts / for auxiliary contacts / instantaneous switching | | 0 |
Number of NO contacts / for auxiliary contacts / instantaneous switching | | 0 |
Number of change-over switches / for auxiliary contacts | | 0 |
Inputs/ Outputs: | | |
Number of digital inputs | | 0 |
Short-circuit: |
Breaking capacity limit short-circuit current (lcu) | | |
| kA | 100 |
| kA | 42 |
| kA | 6 |
Design of the electrical connection / for auxiliary and control current circuit | | screw-type terminals |
Design of the overcurrent release and short-circuit release | | thermomagnetic |
Installation/mounting/dimensions: |
Built in orientation | | any |
Type of mounting | | screw and snap-on mounting onto 35 mm standard mounting rail according to DIN EN 50022 |
Width | mm | 45 |
Height | mm | 97 |
Depth | mm | 96 |
Distance, to be maintained, to the ranks assembly | | |
| mm | 0 |
| mm | 0 |
Product function / removable terminal for auxiliary and control circuit | | No |
Connections: |
Design of the electrical connection | | |
| | screw-type terminals |
Type of the connectable conductor cross-section | | |
| | |
| | 2x (1 ... 2.5 mm²), 2x (2.5 ... 6 mm²) |
| | 2x (1 ... 2.5 mm²), 2x (2.5 ... 6 mm²) |
| | |
- with conductor end processing
| | 2x (1 ... 2.5 mm²), 2x (2.5 ... 6 mm²) |
- for AWG conductors / for main contacts
| | 2x (14 ... 10) |
Conductor cross section that can be connected / for main contacts | | |
| mm² | 1…6 |
| mm² | 1…6 |
| | |
- with conductor end processing
| mm² | 1…6 |
AWG number / as coded connectable conductor cross-section | | |
| | 14…10 |