Your cart is empty

3RV1031-4FA10 CIRCUIT-BREAKER 28...40 A,

Part No.:
3RV1031-4FA10
Manufacturer:
SIEMENS
Weight:
0.45kg
Product Range:
Industrial Controls
3RV1031-4FA10

Product Information

CIRCUIT-BREAKER SIZE S2. FOR MOTOR PROTECTION, CLASS 10, A-REL. 28...40A, N-REL. 520A, SCREW TERMINAL, STANDARD SWITCHING CAPACITY
General technical data:
Product brand nameSIRIUS
product designationcircuit breaker
Size of the circuit-breakerS2
Trip classCLASS 10
Degree of pollution3
Installation altitude / at a height over sea level / maximumm2,000
Protection class IP / on the frontIP20
Ambient temperature
  • during storage
°C-50…60
  • during operating
°C-20…50
  • during transport
°C80…-50
Resistance against shock25g / 11 ms
Insulation voltage / rated valueV690
Impulse voltage resistance / rated valueV6,000
Active power loss / total / typicalW20
Item designation
  • according to DIN 40719 extendable after IEC 204-2 / according to IEC 750
Q
  • according to DIN EN 61346-2
Q
Mechanical operating cycles as operating time / of the main contacts / typical50,000
Type of the driving mechanism / motor driveNo
Design of the operating mechanismselector switch
Product function
  • overload protection
Yes
  • phase disturbance recognition
Yes
Product component
  • auxiliary switch
No
  • undervoltage release mechanism
No
  • trip indicator
No
Product extension / optional / motor driveYes
Main circuit:
Number of poles / for main current circuit3
type of voltageAC/DC
Operating voltage / at AC-3 / rated value / maximumV690
Operating current / at AC-3 / at 400 V / rated valueA40
Service power / at AC-3
  • at 400 V / rated value
kW18.5
Frequency of operation / at AC-3 / according to IEC 60947-6-2 / maximum1/h15
Arrangement of electrical connectors / for main current circuitfront side
Adjustable response current
  • of the non-delayed short-circuit release
A520...520
Adjustable response current
  • of the current-dependent overload release
A28...40
Continuous current / rated valueA40
Product extension / auxiliary switchYes
Auxiliary circuit:
Number of NC contacts / for auxiliary contacts / instantaneous switching0
Number of NO contacts / for auxiliary contacts / instantaneous switching0
Number of change-over switches / for auxiliary contacts0
Inputs/ Outputs:
Number of digital inputs0
Short-circuit:
Breaking capacity limit short-circuit current (lcu)
  • at 400 V / rated value
kA50
  • at 500 V / rated value
kA10
  • at 690 V / rated value
kA4
Design of the electrical connection / for auxiliary and control current circuitscrew-type terminals
Design of the overcurrent release and short-circuit releasethermomagnetic
Installation/mounting/dimensions:
Built in orientationany
Type of mountingscrew and snap-on mounting onto 35 mm standard mounting rail according to DIN EN 50022
Widthmm55
Heightmm140
Depthmm149
Distance, to be maintained, to the ranks assembly
  • backwards
mm0
  • sidewards
mm0
Product function / removable terminal for auxiliary and control circuitNo
Connections:
Design of the electrical connection
  • for main current circuit
screw-type terminals with box terminals
Type of the connectable conductor cross-section
  • for main contacts
  • solid
2x (0.75…16 mm²)
  • stranded
2x (0.75…25 mm²), 0.75…35 mm²
  • finely stranded
  • with conductor end processing
2x (0.75…16 mm²), 0.75…25 mm²
  • for AWG conductors / for main contacts
2x (18…2), 1x (18…2)
Conductor cross section that can be connected / for main contacts
  • solid
mm²0.75...16
  • stranded
mm²0.75...25
  • stranded wire
  • with conductor end processing
mm²0.75...25
AWG number / as coded connectable conductor cross-section
  • for main contacts
18...2

1 Units in Stock


Call for Availability
Price for:  EachMinimum:  1

Target Price

Offer your acceptable price, and we may make you satisfied.Your Target Price

Technical Support

Technical Support

Customer Reviews

Write Review

Customer Q&A Exchange

Ask A Question