COMMUNICATIONSPROCESSOR CP443-1 ADVANCED FOR CONNECTION OF SIMATIC S7-400 TILL FW V4.X TO IND. ETHERNET VIA PROFINET IO-CONTROLLER AND PROFINET CBA,ISO,TCP/IP SEND/RECEIVE AND FETCH/WRITE, UDP, TCP, S7 COMMUNICATION, WITH AND W/O RFC1006, MULTICAST HTML DIAGNOS.,FTP CLIENT/SERVER SNMP, DHCP, E-MAIL, WWW, 10/100 MBITS, SWITCH CONN. 4XRJ45 |
Transmission rate | |
Transfer rate / at the interface 1 | 10 Mbit/s…100 Mbit/s |
Interfaces | |
Number of electrical connections / at interface 1 / in accordance with Industrial Ethernet | 4 |
Supply voltage, current consumption, power loss | |
Type of voltage / of supply voltage | DC |
Power supply / 1 / from backplane bus | 5 V |
Relative symmetrical tolerance / [nicht versorgt - bei 5 V] / [nicht versorgt - bei DC] | 5 % |
Consumed current / from backplane bus / at 5 V / for DC / [nicht versorgt - typisch] | 1.8 A |
Resistive loss | 7.25 W |
Permitted ambient conditions | |
Ambient temperature | |
| 0 °C…60 °C |
| -40 °C…70 °C |
| -40 °C…70 °C |
Relative humidity / at 25 °C / without condensation / during operating / maximum | 95 % |
Protection class IP | IP20 |
Design, dimensions and weight | |
Width | 25 mm |
Height | 290 mm |
Depth | 210 mm |
Net weight | 0.7 kg |
Product properties, functions, components / general | |
Number of units | |
| 14 |
Performance data / open communication | |
Number of possible connections / for open communication / by means of SEND/RECEIVE blocks / maximum | 64 |
Data volume | |
- as user data per ISO connection / for open communication / by means of SEND/RECEIVE blocks / maximum
| 8 Kibyte |
- as user data per ISO on TCP connection / for open communication / by means of SEND/RECEIVE blocks / maximum
| 8 Kibyte |
- as user data per TCP connection / for open communication / by means of SEND/RECEIVE blocks / maximum
| 8 Kibyte |
- as user data per UDP connection / for open IE communication / by means of SEND/RECEIVE blocks / maximum
| 2 Kibyte |
Number of possible connections / for open communication / by means of T blocks / maximum | 64 |
Data volume / as user data per ISO on TCP connection / for open communication / by means of T blocks / maximum | 1452 byte |
Performance data / S7 communication | |
Number of possible connections / [nicht versorgt - für S7-Kommunikation] | |
- [nicht versorgt - maximal]
| 128 |
- with PG connections / maximum
| 2 |
Performance data / multi-protocol mode | |
Number of active connections / [nicht versorgt - bei Multiprotokollbetrieb] | 128 |
Performance data / PROFINET communication / as PN IO-Controller | |
Number of PN IO-Devices / on PROFINET IO-Controller / usable / total | 125 |
Number of PN IO IRT-Devices / on PROFINET IO-Controller / usable | 0 |
Number of external PN IO lines / with PROFINET / per rack | 4 |
Amount of data | |
- [nicht versorgt - als Nutzdaten für Eingangsvariablen] / [nicht versorgt - als PROFINET IO-Controller] / [nicht versorgt - maximal]
| 4 Kibyte |
- [nicht versorgt - als Nutzdaten für Eingangsvariablen] / [nicht versorgt - bei PROFINET IO-Controller] / [nicht versorgt - maximal]
| 4 Kibyte |
- [nicht versorgt - als Nutzdaten für Eingangsvariablen je PN IO-Device] / [nicht versorgt - bei PROFINET IO-Controller] / [nicht versorgt - maximal]
| 240 byte |
- [nicht versorgt - als Nutzdaten für Ausgangsvariablen je PN IO-Device] / [nicht versorgt - bei PROFINET IO-Controller] / [nicht versorgt - maximal]
| 240 byte |
Product functions / management, configuration | |
Product function / MIB support | Yes |
Protocol / is supported | |
| Yes |
| No |
Product functions / Diagnosis | |
Product function / Web-based diagnostics | Yes |
Product functions / switch | |
Product feature / switch | Yes |
Product function | |
| No |
- for IRT / PROFINET IO switch
| No |
- Configuration with STEP 7
| Yes |
Product functions / Redundancy | |
Product function | |
| No |
Product functions / Security | |
Product function | |
| Yes |
- switchoff of non-required services
| No |
- blocking of communication via physical ports
| Yes |
- log file for unauthorized access
| No |
Product functions / Time | |
Product function | |
| Yes |
- pass on time synchronization
| Yes |
Protocol / is supported / NTP | Yes |
Last change: | Oct 24, 2011 |