SIPLUS ET200S EM 8 DI -25 ... +70 DEGREES C BASED ON 6ES7131-4BF00-0AA0 |
Supply voltage |
24 V DC | Yes |
permissible range, lower limit (DC) | 20.4 V |
permissible range, upper limit (DC) | 28.8 V |
Reverse polarity protection | Yes |
Input current |
from backplane bus 3.3 V DC, max. | 10 mA |
from supply voltage L+, max. | Dependent on encoder |
Encoder supply |
Number of outputs | 0; no encoder supply |
Power losses |
Power loss, typ. | 1.2 W |
Address area |
Address space per module |
without packing | 1 byte |
Digital inputs |
Number/binary inputs | 8 |
Input characteristic curve acc. to IEC 1131, Type 1 | Yes; 2-wire sensors connectable |
Number of simultaneously controllable inputs | 8 |
Input voltage |
Type of input voltage | DC |
Rated value, DC | 24 V |
for signal "0" | -30 to +5 V |
for signal "1" | 15 to 30 V |
Input current |
for signal "1", typ. | 5 mA |
Input delay (for rated value of input voltage) |
for standard inputs |
Parameterizable | No |
at "0" to "1", min. | 2 ms |
at "0" to "1", max. | 4.5 ms |
at "1" to "0", min. | 2 ms |
at "1" to "0", max. | 4.5 ms |
Cable length |
Cable length, shielded, max. | 1,000 m |
Cable length unshielded, max. | 600 m |
Encoder |
Connectable encoders |
2-wire BEROS | Yes |
permissible quiescent current (2-wire BEROS), max. | 1.5 mA |
Isochronous mode |
Isochronous mode | Yes; TWE = 3000 us |
Interrupts/diagnostics/status information |
Diagnoses |
Diagnostic functions | No |
Diagnostics indication LED |
Status indicator digital input (green) | Yes |
Parameter |
Remark | 3-byte parameter (not accessible for the user) |
Galvanic isolation |
Galvanic isolation digital inputs |
between the channels | No |
between the channels and the backplane bus | Yes |
Permissible potential difference |
between different circuits | 75 VDC / 60 VAC |
Isolation |
Isolation checked with | 500 V DC |
Ambient conditions |
Extended ambient conditions |
Relative humidity |
with condensation / maximum | 100 % |
Resistance |
to biologically active substances / conformity with EN 60721-3-3 | Yes |
to chemically active substances / conformity with EN 60721-3-3 | Yes |
to mechanically active substances / conformity with EN 60721-3-3 | Yes |
Mechanical and climatic conditions during operation |
Climatic conditions in operation |
Temperature |
Min. | -25 °C |
max. | 70 °C |
Standards, approvals, certificates |
CE mark | Yes |
Dimensions |
Width | 15 mm |
Height | 81 mm |
Depth | 52 mm |
Weight |
Weight, approx. | 35 g |