SIPLUS LOGO! 230RC -25 ... +70 DEGREES C BASED ON 6ED1052-1FB00-0BA6 |
Supply voltage |
115 V DC | Yes |
230 V DC | Yes |
permissible range, lower limit (DC) | 100 V |
permissible range, upper limit (DC) | 253 V |
115 V AC | Yes |
230 V AC | Yes |
Time of day |
Time switching clocks |
Power reserve | 80 h |
Digital inputs |
Number/binary inputs | 8 |
Digital outputs |
Number/binary outputs | 4; Relay |
Functionality/short-circuit strength | No; external fusing necessary |
Relay outputs |
Switching capacity of contacts |
with inductive load, max. | 3 A; ; 1 A per relay @ > 55 °C; 3 A per relay @ > 55 °C & < 15 s |
Switching frequency/contacts/at ohmic load/maximum | 10 A; ; 3 A per relay @ > 55 °C; 10 A per relay @ > 55 °C & < 15 s |
EMC |
Emission of radio interference acc. to EN 55 011 |
Emission of radio interference acc. to EN 55 011 (limit class B) | Yes |
Ambient conditions |
Operating temperature |
Min. | -25 °C; = Tmin |
max. | 70 °C; = Tmax; 55 °C @ UL/cUL use |
Extended ambient conditions |
Relative to ambient temperature-atmospheric pressure-installation altitude | Tmin ... Tmax at 1080 hPa ... 795 hPa (-1000 m ... +2000 m) |
Relative humidity |
with condensation / maximum | 100 %; Relative humidity, incl. condensation / frost permitted (no commissioning under condensation conditions) |
Resistance |
to biologically active substances / conformity with EN 60721-3-3 | Yes; , Class 3B2 mold, fungus and dry rot spores (with the exception of fauna). The supplied connector covers must remain on the unused interfaces during operation! |
to chemically active substances / conformity with EN 60721-3-3 | Yes; , Class 3C4 incl. salt spray. The supplied connector covers must remain on the unused interfaces during operation! |
to mechanically active substances / conformity with EN 60721-3-3 | Yes; , Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation! |
Degree and class of protection |
IP20 | Yes |
Standards, approvals, certificates |
CSA approval | No |
UL approval | Yes; ; File: E120869 // Tmax = 55 °C |
FM approval | No |
Marine approval | No |
Developed according to IEC1131 | Yes |
according to VDE 0631 | Yes |
Mounting |
Mounting | on 35 mm DIN rail, 4 spacing units wide |
Dimensions |
Width | 72 mm |
Height | 90 mm |
Depth | 55 mm |
Status | Sep 10, 2011 |