SIMATIC S7-300, CPU 315T-2 DP, CENTRAL PROCESSING UNIT FOR PLC AND TECHNOLOGY 256 KBYTE WORKING MEMORY, 1. INTERFACE MPI/DP 12MBIT/S 2. INTERFACE DP(DRIVE), INTEGRATED I/O FOR TECHNOLOGY FRONT CONNECTOR (1 X 40PIN) AND MICRO MEMORY CARD MIN. 8 MB NECESSARY
General information
Hardware product version01
Firmware versionCPU:V2.7;integrated technology: V4.1.5
[nicht versorgt: TAK_ABW067_001_000]
associated programming packageSTEP 7 V5.4 + SP5 (and higher) and Optional package  S7-Technology V4.2
Supply voltage
24 V DCYes
permissible range, lower limit (DC)20.4 V
permissible range, upper limit (DC)28.8 V
External protection for supply cables (recommendation)2 A min.
Load voltage L+
Rated value (DC)24 V
Reverse polarity protectionYes
Digital outputs
Load voltage L+
Rated value (DC)24 V; (2L+)
Reverse polarity protectionNo; (2L+)
Input current
Current consumption (in no-load operation), typ.200 mA
Inrush current, typ.2.5 A
I²t1 A²·s
Power losses
Power loss, typ.6 W
Memory
Work memory
integrated256 Kibyte
expandableNo
Load memory
pluggable (MMC)Yes
pluggable (MMC), max.8 Mbyte
Data management on MMC (after last programming), min.10 a
Backup
presentYes; Guaranteed by MMC (maintenance-free)
without batteryYes; Program and data
CPU processing times
for bit operations, min.0.1 µs
for bit operations, max.0.1 µs
for word operations, min.0.2 µs
for fixed point arithmetic, min.2 µs
for floating point arithmetic, min.3 µs
CPU-blocks
Number of blocks (total)1024; (DBs, FCs, FBs); the maximum number of loadable blocks can be reduced by the MMC used.
DB
Number, max.1023; Number band: 1 to 1023
Size, max.64 Kibyte
FB
Number, max.1024; Number range: 0 to 2047
Size, max.64 Kibyte
FC
Number, max.1024; Number range: 0 to 2047
Size, max.64 Kibyte
OB
Descriptionsee instruction list
Size, max.64 Kibyte
Number of free cycle OBs1; OB 1
Number of time alarm OBs1; OB 10
Number of delay alarm OBs1; OB 20
Number of time interrupt OBs1; OB 35
Number of process alarm OBs1; OB 40
Number of DPV1 alarm OBs3; OB 55, 56, 57
Number isochronous mode OBs1; OB 61
Number of technology synchronous alarm OBs1; OB 65
Number of startup OBs1; OB 100
Number of asynchronous error OBs5; OB 80, 82, 85, 86, 87
Number of synchronous error OBs2; OB 121, 122
Nesting depth
per priority class8
additional within an error OB4
Counters, timers and their retentivity
S7 counter
Number256; Number range: 0 to 255
Retentivity
adjustableYes
preset8
Counting range
adjustableYes
lower limit0
upper limit999
IEC counter
presentYes
TypeSFB
NumberUnlimited (limited only by RAM capacity)
S7 times
Number256; Number range: 0 to 255
of which retentive without battery
adjustableYes; From Z 0 to Z 7
Retentivity
adjustableYes
presetNo retentivity
Time range
lower limit10 ms
upper limit9990 s
IEC timer
presentYes
TypeSFB
NumberUnlimited (limited only by RAM capacity)
Data areas and their retentivity
retentive data area, totalAll DBs, max. 128 KB
Flag
Number, max.2048 byte
Retentivity availableYes; MB 0 to MB 2047
Retentivity presetMB 0 to MB 15
Number of clock memories8; 1 memory byte
Data blocks
Number, max.1023; From DB 1 to DB 1023
Size, max.64 Kibyte
Retentivity adjustableYes; via non-retain property on DB
Retentivity presetYes
Local data
per priority class, max.1024 byte
Address area
I/O address area
Inputs2048 byte
Outputs2048 byte
of which, distributed
Inputs2048 byte
Outputs2048 byte
Process image
Inputs, adjustable2048 byte
Outputs, adjustable2048 byte
Inputs, default128 byte
Outputs, default128 byte
Default addresses of the integrated channels
Digital inputs66
Digital outputs66
Subprocess images
Number of subprocess images, max.1
Digital channels
Inputs16384
Outputs16384
Inputs, of which central512
Outputs, of which central512
Analog channels
Inputs1024
Outputs1024
Inputs, of which central64
Outputs, of which central64
Hardware configuration
Racks, max.1
Modules per rack, max.8
Expansion devices, max.0
Number of DP masters
integrated2; 1 DP and 1 DP (drive)
via CP2; for DP
Number of operable FMs and CPs (recommended)
FM8
CP, point-to-point8
CP, LAN10
Time of day
Clock
Hardware clock (real-time clock)Yes
battery-backed and synchronizableYes
Deviation per day, max.10 s
Backup time6 wk; At 40 °C ambient temperature
Operating hours counter
Number1
Number/Number range0
Range of values0 to 2^31 hours (when using SFC 101)
Granularity1 hour
retentiveYes; Must be restarted at each restart
Clock synchronization
supportedYes
to MPI, masterYes
to MPI, slaveYes
to DP, masterYes
to DP, slaveYes
in AS, masterYes
in AS, slaveYes
Digital inputs
Number/binary inputs4
of which, inputs usable for technological functions4
Input characteristic curve acc. to IEC 1131, Type 1Yes
Number of simultaneously controllable inputs
horizontal installation
up to 40 °C, max.4
up to 60 °C, max.4
vertical installation
up to 40 °C, max.4
Input voltage
Type of voltage / of the input voltage
Rated value, DC24 V
for signal "0"-3 to +5 V
for signal "1"15 to 30 V
Input current
for signal "1", typ.7 mA
Input delay (for rated value of input voltage)
for counter/technological functions
at "0" to "1", max.10 µs; typ.
at "1" to "0", max.10 µs; typ.
Cable length
Cable length, shielded, max.1000 m
Digital outputs
Number/binary outputs8
of which high-speed outputs8
FunctionsFor technology functions, e.g. high-speed cam switch signals
Functionality/short-circuit strengthYes
Response threshold, typ.1.0 A
Limitation of inductive shutdown voltage to48 V
Lamp load, max.5 W
Controlling a digital inputNo
Output voltage
for signal "0" (DC), max.3 V; (2L+)
for signal "1", min.Rated voltage -2.5 V
Output current
for signal "1" rated value0.5 A
for signal "1" permissible range for 0 to 60 °C, min.5 mA
for signal "1" permissible range for 0 to 60 °C, max.0.6 A
for signal "0" residual current, max.0.3 mA
Parallel switching of 2 outputs
for increased powerNo
for redundant control of a loadNo
Switching frequency
with resistive load, max.100 Hz
with inductive load, max.0.2 Hz; to IEC 947-5-1, DC13
on lamp load, max.100 Hz
Aggregate current of outputs (per group)
horizontal installation
up to 40 °C, max.4 A
up to 60 °C, max.3 A
all other mounting positions
up to 40 °C, max.3 A
Load resistance range
lower limit48 Ω
upper limit4 kΩ
Cable length
Cable length, shielded, max.1000 m
Encoder
Connectable encoders
2-wire BEROSNo
1st interface
Type of interfaceIntegrated RS 485 interface
PhysicsRS 485
IsolatedYes
Power supply to interface (15 to 30 V DC), max.200 mA
Functionality
MPIYes
DP masterYes
DP slaveYes
Point-to-point connectionNo
MPI
Number of connections32
Services
PG/OP communicationYes
RoutingYes
Global data communicationYes
S7 basic communicationYes
S7 communicationYes
S7 communication, as clientNo; but via CP and loadable FB
S7 communication, as serverYes; Connection configured on one side only
Transmission rate, max.12 Mbit/s
DP master
Services
PG/OP communicationYes
RoutingYes
Global data communicationNo
S7 basic communicationYes; I blocks only
S7 communicationYes
S7 communication, as clientNo; but via CP and loadable FB
S7 communication, as serverYes; Connection configured on one side only
Equidistance mode supportYes
Isochronous modeYes; OB 61
SYNC/FREEZEYes
Activation/deactivation of DP slavesYes
DPV1Yes
Transmission rate, max.12 Mbit/s
Number of DP slaves, max.124
Address area
Inputs, max.2048 byte
Outputs, max.2048 byte
User data per DP slave
Inputs, max.244 byte
Outputs, max.244 byte
DP slave
Services
PG/OP communicationYes
RoutingYes; Only with active interface
Global data communicationNo
S7 basic communicationNo
S7 communicationYes
S7 communication, as clientNo; but via CP and loadable FB
S7 communication, as serverYes; Connection configured on one side only
Direct data exchange (slave-to-slave communication)Yes
DPV1No
Transmission rate, max.12 Mbit/s
Automatic baud rate searchNo
Transfer memory
Inputs244 byte
Outputs244 byte
Address area, max.32
User data per address area, max.32 byte
2nd interface
Type of interfaceIntegrated RS 485 interface
PhysicsRS 485
IsolatedYes
Power supply to interface (15 to 30 V DC), max.200 mA
Functionality
MPINo
DP masterYes; DP(DRIVE)-Master
DP slaveNo
Local Operating NetworkNo
DP master
Services
PG/OP communicationNo
RoutingNo
Global data communicationNo
S7 basic communicationNo
S7 communicationNo
Equidistance mode supportYes
Isochronous modeYes
SYNC/FREEZENo
Activation/deactivation of DP slavesYes
DPV1No
Transmission rate, max.12 Mbit/s
Number of DP slaves, max.64
Address area
Inputs, max.1024 byte
Outputs, max.1024 byte
User data per DP slave
Inputs, max.244 byte
Outputs, max.244 byte
DP slave
Services
GSD filehttp://www.ad.siemens.de/support in Product Support area
Transmission rate, max.12 Mbit/s
Communication functions
PG/OP communicationYes
Global data communication
supportedYes
Number of GD loops, max.8
Number of GD packets, max.8
Number of GD packets, transmitter, max.8
Number of GD packets, receiver, max.8
Size of GD packets, max.22 byte
Size of GD packet (of which consistent), max.22 byte
S7 basic communication
supportedYes
User data per job, max.76 byte
User data per job (of which consistent), max.76 byte; 76 bytes (with X_SEND or X_RCV), 76 bytes (with X_PUT or X_GET as server)
S7 communication
supportedYes
as serverYes
as clientYes; Via CP and loadable FB
User data per job, max.See online help of STEP 7 (shared parameters of the SFBs/FBs and of the SFCs/FCs of S7 Communication)
S5-compatible communication
supportedYes; via CP and loadable FC
Number of connections
overall16
usable for PG communication15
reserved for PG communication1
Adjustable for PG communication, min.1
Adjustable for PG communication, max.15
usable for OP communication15
reserved for OP communication1
adjustable for OP communication, min.1
adjustable for OP communication, max.15
usable for S7 basic communication12
Reserved for S7 basic communication0
adjustable for S7 basic communication, min.0
adjustable for S7 basic communication, max.12
usable for routing8; additional
S7 message functions
Number of login stations for message functions, max.16; Depending on the configured connections for PG/OP and S7 basic communication
Process diagnostic messagesYes
simultaneously active Alarm-S blocks, max.40
Test commissioning functions
Status/control
Status/control variableYes
VariablesInputs, outputs, memory bits, DB, times, counters
Number of variables, max.30
of which status variables, max.30
of which control variables, max.14
Forcing
ForcingYes
Force, variablesInputs, outputs
Number of variables, max.10
Status blockYes
Single stepYes
Number of breakpoints2
Diagnostic buffer
presentYes
Number of entries, max.100
adjustableNo
Interrupts/diagnostics/status information
Alarms
AlarmsNo
Diagnoses
Diagnostic functionsNo
Diagnostics indication LED
Status indicator digital output (green)Yes
Status indicator digital input (green)Yes
Galvanic isolation
Galvanic isolation digital inputs
between the channels and the backplane busYes
Galvanic isolation digital outputs
between the channels and the backplane busYes
Permissible potential difference
between different circuits75 VDC / 60 VAC
Isolation
Isolation checked with500 V DC
Ambient conditions
Operating temperature
Min.0 °C
max.60 °C
Configuration
Configuration software
STEP 7Yes; V5.2 SP1 or higher and S7 Technology option package
programming
Programming language
LADYes
FBDYes
STLYes
SCLYes
CFCYes
GRAPHYes
HiGraph®Yes
Command setsee instruction list
Nesting levels8
Software libraries
System functions (SFC)see instruction list
System function blocks (SFB)see instruction list
Know-how protection
User program protection/password protectionYes
Cycle time monitoring
lower limit1 ms
upper limit6000 ms
adjustableYes
preset150 ms
Dimensions
Width160 mm
Height125 mm
Depth130 mm
Weight
Weight, approx.750 g

1 Units in Stock


Call for Availability
Price for:  EachMinimum:  1

Target Price

Offer your acceptable price, and we may make you satisfied.Your Target Price

Technical Support

Technical Support

Customer Reviews

Write Review

Customer Q&A Exchange

Ask A Question