Your cart is empty

6ES7231-7PF22-0XA0 EM 231, 8AI, +/-80 MV, 15 BITS

Manufacturer:
SIEMENS
Weight:
0.21kg
Product Range:
Automation Systems

Product Information

SIMATIC S7-200, T/C INPUT MOD. EM 231, FOR S7-22X CPU ONLY, 8 AI, +/-80 MV AND THERMOCOUPLE TYPE J,K,S,T,R,E,N; 15BIT+VORZ.
Input current
from load voltage L+ (without load), max.60 mA
from backplane bus 5 V DC, max.87 mA
Power losses
Power loss, typ.1.8 W
Analog inputs
Number of analog inputs8
permissible input voltage for voltage input (destruction limit), max.30 V
Loop resistance cable100 Ω
Updating time (all channels)810 ms
Input ranges
VoltageYes
CurrentNo
ThermocoupleYes
Resistance thermometerNo
ResistanceNo
Input ranges (rated values), voltages
-80 mV to +80 mVYes
Input resistance (-80 mV to +80 mV)1 MΩ
Input ranges (rated values), thermoelements
Type EYes
Type JYes
Input resistance (type J)1 MΩ
Type KYes
Input resistance (Type K)1 MΩ
Type NYes
Input resistance (Type N)1 MΩ
Type RYes
Input resistance (Type R)1 MΩ
Type SYes
Input resistance (Type S)1 MΩ
Type TYes
Input resistance (Type T)1 MΩ
[nicht versorgt: TAK_ABT296_001_000]
Cable length, shielded, max.100 m; to the sensor
Analog value creation
Measurement principleSigma Delta
Integrations and conversion time/ resolution per channel
Resolution with overrange (bit including sign), max.16 bit; Temperature 0.1 °C / 0.1 °F
Interference voltage suppression for interference frequency f1 in Hz85 dB at 50 / 60 / 400 Hz
Displayable conversion value range
bipolar signals-27.648 to +27.648
Errors/accuracies
cold connection point+/-1.5 °C
Repeat accuracy in settled status at 25 °C (relative to input area)+/- 0,05 %
Operational limit in overall temperature range
Voltage, relative to output area+/- 0,1 %
Interference voltage suppression for f = n x (fl +/- 1%), fl = interference frequency
common mode voltage, max.120 V; AC
Common mode interference, min.120 dB; At 120 V DC
Interrupts/diagnostics/status information
Diagnostics indication LED
External fault EXTF (red)Yes
Group error SF (red)Yes
Galvanic isolation
Galvanic isolation analog inputs
Galvanic isolation analog inputsYes
Permissible potential difference
between inputs and MANA (UCM)500 V AC
between M internally and the inputs500 V AC
Connection method
Plug-in I/O terminalsNo
Dimensions
Width71.2 mm
Height80 mm
Depth62 mm
Weight
Weight, approx.210 g

2 Units in Stock


Call for Availability
Price for:  EachMinimum:  1

Target Price

Offer your acceptable price, and we may make you satisfied.Your Target Price

Technical Support

Technical Support

Customer Reviews

Write Review

Customer Q&A Exchange

Ask A Question