Your cart is empty

6ES7211-1BD30-0XB0 CPU 1211C, AC/DC/RELAY, 6DI/4DO/2AI

Manufacturer:
SIEMENS
Weight:
0.31kg
Product Range:
Automation Systems

Product Information

SIMATIC S7-1200, CPU 1211C, COMPACT CPU, AC/DC/RELAY, ONBOARD I/O: 6 DI 24V DC; 4 DO RELAY 2A; 2 AI 0 - 10V DC, POWER SUPPLY: AC 85 - 264 V AC AT 47 - 63 HZ, PROGRAM/DATA MEMORY: 25 KB
General information
[nicht versorgt: TAK_ABW067_001_000]
associated programming packageSTEP 7 V10.5 or higher
Display
integratedNo
Supply voltage
120 V ACYes
230 V ACYes
permissible range, lower limit (AC)85 V
permissible range, upper limit (AC)264 V
Line frequency
Frequency of the supply voltage47 Hz
Frequency of the supply voltage63 Hz
Input current
Current consumption (rated value)60 mA at 120 V AC; 30 mA at 240 V AC
Current consumption, max.180 mA at 120 V AC; 90 mA at 240 V AC
Inrush current, max.20 A; at 264 V
Encoder supply
24 V encoder supply
24 VPermissible range: 20.4 to 28.8 V
Output current
Current output to backplane bus (DC 5 V), max.750 mA; Max. 5 V DC for SM and CM
Power losses
Power loss, typ.10 W
Memory
Usable memory for user data25 kbyte
Work memory
integrated25 kbyte
expandableNo
Load memory
integrated1 Mbyte
expandable, max.24 Mbyte; with SIMATIC memory card
Backup
presentYes; Entire project maintenance-free in the integral EEPROM
without batteryYes
CPU processing times
for bit operations, min.0.1 µs; / Operation
for word operations, min.12 µs; / Operation
for floating point arithmetic, min.18 µs; / Operation
CPU-blocks
Number of blocks (total)DBs, FCs, FBs, counters and timers. The maximum number of addressable blocks ranges from 1 to 65535. There is no restriction, the entire working memory can be used
OB
Number, max.Limited only by RAM for code
Data areas and their retentivity
retentive data area in total (incl. times, counters, flags), max.2048 byte
Flag
Number, max.4 kbyte; Size of bit memory address area
Address area
I/O address area
I/O address area, overall1024 bytes for inputs / 1024 bytes for outputs
Inputs1024 byte
Outputs1024 byte
Process image
Inputs, adjustable1 kbyte
Outputs, adjustable1 kbyte
Hardware configuration
Number of modules per system, max.3 communication modules, 1 signal board
Time of day
Clock
Hardware clock (real-time clock)Yes
Deviation per day, max.+/- 60 s/month at 25 °C
Backup time240 h; Typical
Digital inputs
Number/binary inputs6; integrated
of which, inputs usable for technological functions3; HSC (High Speed Counting)
integrated channels (DI)6
m/p-readingYes
Input voltage
Type of input voltage
Rated value, DC24 V
for signal "0"5 V DC at 1 mA
for signal "1"15 V DC at 2.5 mA
Input current
for signal "1", typ.1 mA
Input delay (for rated value of input voltage)
for standard inputs
Parameterizable0.2, 0.4, 0.8, 1.6, 3.2, 6.4, and 12.8 ms, selectable in 4 groups
at "0" to "1", min.0.2 ms
at "0" to "1", max.12.8 ms
for interrupt inputs
ParameterizableYes
for counter/technological functions
ParameterizableSingle phase : 3 at 100 kHz, differential: 3 at 80 kHz
Cable length
Cable length, shielded, max.500 m; 50 m for technological functions
Cable length unshielded, max.300 m; For technological functions: No
Digital outputs
Number/binary outputs4; Relay
integrated channels (DO)4
Functionality/short-circuit strengthNo; to be provided externally
Switching capacity of the outputs
with resistive load, max.2 A
on lamp load, max.30 W DC; 200 W AC
Output delay with resistive load
0 to "1", max.10 ms; max.
1 to "0", max.10 ms; max.
Parallel switching of 2 outputs
for increased powerNo
Switching frequency
of the pulse outputs, with resistive load, max.1 Hz
Relay outputs
Number of relay outputs4
Number of operating cyclesmechanically 10 million, at rated load voltage 100,000
Cable length
Cable length, shielded, max.500 m
Cable length unshielded, max.150 m
Analog inputs
Number of analog inputs2
Integrated channels (AI)2
Number of analog inputs for voltage/current measurement2
Input ranges
VoltageYes
Input ranges (rated values), voltages
0 to +10 VYes
Input resistance (0 to 10 V)≥100k ohms
Cable length
Cable length, shielded, max.100 m; twisted and shielded
Analog outputs
Integrated channels (AO)0
Cable length
Cable length, shielded, max.100 m; Shielded, twisted wire pair
Analog value creation
Integrations and conversion time/ resolution per channel
Resolution with overrange (bit including sign), max.10 bit
Integration time, parameterizableYes
Conversion time (per channel)625 µs
Encoder
Connectable encoders
2-wire BEROSYes
1st interface
Type of interfacePROFINET
PhysicsEthernet
IsolatedYes
Automatic detection of transmission speedYes
AutonegotiationYes
AutocrossingYes
Functionality
PROFINET IO ControllerYes
Communication functions
S7 communication
supportedYes
as serverYes
Open IE communication
TCP/IPYes
ISO-on-TCP (RFC1006)Yes
Web server
supportedYes
User-defined websitesYes
Number of connections
overall15; dynamically
Test commissioning functions
Status/control
Status/control variableYes
VariablesInputs/outputs, memory bits, DBs, distributed I/Os, timers, counters
Forcing
ForcingYes
Integrated Functions
Number of counters3
Counter frequency (counter) max.100 kHz
Frequency meterYes
controlled positioningYes
PID controllerYes
Number of alarm inputs4
Galvanic isolation
Galvanic isolation digital inputs
Galvanic isolation digital inputsNo
between the channels, in groups of1
Galvanic isolation digital outputs
Galvanic isolation digital outputsYes; Relay
between the channelsNo
between the channels, in groups of1
Permissible potential difference
between different circuits500 V DC between 24 V DC and 5 V DC
EMC
Interference immunity against discharge of static electricity
Interference immunity against discharge of static electricity acc. to IEC 61000-4-2Yes
Test voltage at air discharge8 kV
Test voltage at contact discharge6 kV
Interference immunity to cable-borne interference
on the supply lines acc. to IEC 61000-4-4Yes
Interference immunity on signal lines acc. to IEC 61000-4-4Yes
Surge immunity
on the supply lines acc. to IEC 61000-4-5Yes
Immunity against conducted interference induced by high-frequency fields
Interference immunity against high-frequency radiation acc. to IEC 61000-4-6Yes
Emission of radio interference acc. to EN 55 011
Emission of radio interferences acc. to EN 55 011 (limit class A)Yes; Group 1
Emission of radio interference acc. to EN 55 011 (limit class B)Yes; When appropriate measures are used to ensure compliance with the limits for Class B according to EN 55011
Ambient conditions
Operating temperature
Min.0 °C
max.55 °C
vertical installation, min.0 °C
vertical installation, max.45 °C
horizontal installation, min.0 °C
horizontal installation, max.55 °C
Storage/transport temperature
Min.-40 °C
max.70 °C
Air pressure
Operation, min.795 hPa
Operation, max.1080 hPa
Storage/transport, min.660 hPa
Storage/transport, max.1080 hPa
Relative humidity
Operation, max.95 %; no condensation
Vibrations
Vibrations2G wall mounting, 1G DIN rail
Operation, checked according to IEC 60068-2-6Yes
Shock test
checked according to IEC 60068-2-27Yes; IEC 68, Part 2-27 half-sine: strength of the shock 15 g (peak value), duration 11 ms
Climatic and mechanical conditions for storage and transport
Climatic conditions for storage and transport
Free fall
Drop height, max. (in packaging)0.3 m; five times, in dispatch package
Temperature
Permissible temperature range-40 °C to +70 °C
Mechanical and climatic conditions during operation
Climatic conditions in operation
Temperature
Permissible temperature range0 °C to 55 °C horizontal installation 0 °C to 45 °C vertical installation
Permissible temperature change5°C to 55°C, 3°C / minute
Air pressure acc. to IEC 60068-2-13
Permissible air pressure1080 to 795 hPa
Permissible operating height-1000 to 2000 m
Pollutant concentrations
SO2 at RH < 60% without condensationS02: < 0.5 ppm; H2S: < 0.1 ppm; RH < 60% condensation-free
Degree and class of protection
IP20Yes
Standards, approvals, certificates
CE markYes
cULusYes
C-TICKYes
FM approvalYes
Configuration
programming
Programming language
LADYes
FBDYes
SCLYes
Cycle time monitoring
adjustableYes
Dimensions
Width90 mm
Height100 mm
Depth75 mm
Weight
Weight, approx.420 g
internTechDB
Characteristics will be deleted after 2012-12-31
Product version
STEP 7STEP 7 V10.5 or higher

1 Units in Stock


Call for Availability
Price for:  EachMinimum:  1

Target Price

Offer your acceptable price, and we may make you satisfied.Your Target Price

Technical Support

Technical Support

Customer Reviews

Write Review