SIMATIC DP, IM151-7 CPU FO FOR ET200S, WORKING MEMORY 48KB ( FROM FW V1.13 ON), INTEGR. PROFIBUS DP INTERFACE (FO SIMPLEX CONNECTOR) AS DP SLAVE, W/O BATTERY |
General information |
[nicht versorgt: TAK_ABW067_001_000] |
associated programming package | STEP 7 V5.1 or higher |
Supply voltage |
24 V DC | Yes |
permissible range, lower limit (DC) | 20.4 V |
permissible range, upper limit (DC) | 28.8 V |
Reverse polarity protection | Yes; against destruction |
Input current |
Inrush current, max. | 3.5 A |
from supply voltage 1L+, max. | 250 mA |
Output current |
Current output to backplane bus (DC 5 V), max. | 700 mA |
Power losses |
Power loss, typ. | 4.5 W |
Memory |
Work memory |
integrated | 48 Kibyte; as of FW V1.13 48 KB; previously 24 KB |
expandable | No |
Load memory |
pluggable (MMC) | Yes |
pluggable (MMC), max. | 2 Mbyte |
Data management on MMC (after last programming), min. | 10 a |
CPU processing times |
for bit operations, min. | 0.3 µs |
for word operations, min. | 1 µs |
for fixed point arithmetic, min. | 2 µs |
for floating point arithmetic, min. | 20 µs |
for timer/counter operations, min. | 12 µs |
CPU-blocks |
DB |
Number, max. | 127 |
Size, max. | 8 Kibyte |
FB |
Number, max. | 128 |
Size, max. | 8 Kibyte |
FC |
Number, max. | 128 |
Size, max. | 8 Kibyte |
OB |
Size, max. | 8 Kibyte |
Number of free cycle OBs | 1; OB 1 |
Number of time alarm OBs | 1; OB 10 |
Number of delay alarm OBs | 1; OB 20 |
Number of time interrupt OBs | 1; OB 35 |
Number of process alarm OBs | 1; OB 40 |
Number of startup OBs | 1; OB 100 |
Number of asynchronous error OBs | 4; OB 80, 82, 85, 86 |
Nesting depth |
per priority class | 8 |
additional within an error OB | 4 |
Counters, timers and their retentivity |
S7 counter |
Number | 64 |
Retentivity |
adjustable | Yes |
lower limit | 0 |
upper limit | 63 |
preset | Z 0 to Z 7 |
Counting range |
adjustable | Yes |
lower limit | 0 |
upper limit | 999 |
IEC counter |
present | Yes |
Type | SFB |
Number | Unlimited (limited only by RAM capacity) |
S7 times |
Number | 128 |
Retentivity |
adjustable | Yes |
lower limit | 0 |
upper limit | 127 |
preset | No retentivity |
Time range |
lower limit | 10 ms |
upper limit | 9990 s |
IEC timer |
present | Yes |
Type | SFB |
Number | Unlimited (limited only by RAM capacity) |
Data areas and their retentivity |
retentive data area in total (incl. times, counters, flags), max. | 4736 byte |
Flag |
Number, max. | 256 byte |
Retentivity available | Yes; MB 0 to MB 255 |
Retentivity preset | MB 0 to MB 15 |
Number of clock memories | 8; 1 memory byte |
Data blocks |
Number, max. | 127 |
Size, max. | 8 Kibyte |
Retentivity adjustable | Yes |
Local data |
per priority class, max. | 1536 byte |
Address area |
I/O address area |
Inputs | 1536 byte |
Outputs | 1536 byte |
of which, distributed |
Inputs | 64 byte |
Outputs | 64 byte |
Process image |
Inputs | 128 byte |
Outputs | 128 byte |
Digital channels |
Inputs | 248 |
Outputs | 248 |
Analog channels |
Inputs | 124 |
Outputs | 124 |
Addressing volume |
Outputs | 244 byte |
Inputs | 244 byte |
Hardware configuration |
Number of mounting rails that can be used | 1 |
Max. length of mounting rail | Station width: <= 1 m or < 2 m |
Number of modules per system, max. | 63 |
Connectable programming devices/PCs | PGs/OPs with STEP 7 connectable via PROFIBUS interface |
Time of day |
Clock |
Software clock | Yes |
Operating hours counter |
Number | 0 |
Interfaces |
Interfaces | 1 x MPI/PROFIBUS DP |
Number of USB interfaces | 0 |
Number of parallel interfaces | 0 |
Number of 20 mA interfaces (TTY) | 0 |
Number of RS 232 interfaces | 0 |
Number of RS 422 interfaces | 0 |
Number of other hardware interfaces | 1 |
PROFIBUS DP |
Node addresses | 1 to 125 |
Cable length, max. | 1000 m; 100 to 1000 m (depending on transmission speed), without repeaters |
1st interface |
Isolated | No |
Power supply to interface (15 to 30 V DC), max. | 80 mA |
Functionality |
DP slave | Yes |
DP slave |
Number of connections | 11 |
Services |
S7 communication, as client | Yes |
S7 communication, as server | Yes |
Direct data exchange (slave-to-slave communication) | Yes |
GSD file | http://www.siemens.de/profibus-gsd |
Transmission rate, max. | 12 Mbit/s |
Test commissioning functions |
Diagnostic buffer |
present | Yes |
Number of entries, max. | 100 |
Ambient conditions |
Operating temperature |
Min. | 0 °C |
max. | 60 °C |
Degree and class of protection |
Type of protection | IP20 |
Configuration |
Configuration software |
STEP 7 Lite | Yes; V2.0 or higher |
programming |
Programming language |
SCL | Yes |
Command set | Binary logic operations, bracketed operations, result allocation, saving, counting, loading, transferring, comparing, shifting, rotating, complementation, calling blocks, fixed point arithmetic, floating point arithmetic, jump functions |
Nesting levels | 8 |
Program organization | Linear, structured |
Software libraries |
Process diagnostics | Yes |
Software controller | Yes; depending on the required memory space and the resulting execution time |
System functions (SFC) | Interrupt and error processing, copy data, clock functions, diagnostic functions, module parameterization, operating mode transitions |
Know-how protection |
User program protection/password protection | Yes |
Cycle time monitoring |
lower limit | 1 ms |
upper limit | 6000 ms |
adjustable | Yes |
preset | 150 ms |
Dimensions |
Width | 60 mm |
Height | 119.5 mm |
Depth | 75 mm |
Weight |
Weight, approx. | 200 g |
internTechDB |
Characteristics will be deleted after 2012-12-31 |
Product version |
STEP 7 | Yes; as of V5.1 |