Your cart is empty

6ES7151-1CA00-3BL0 ET 200S COMPACT, 16DI/16DO STD

Manufacturer:
SIEMENS
Weight:
0.23kg
Product Range:
Automation Systems

Product Information

ET 200S COMPACT, 16DI/16DO STD DC24V, 3MS; DC24V, 0.5A EXPANDABLE WITH UP TO 12 ET 200S MODULES (NO F-MODULES) ELECTRONICBLOCK
General information
Vendor identification (VendorID)8200H
Supply voltage
Rated value (DC)24 V
Reverse polarity protectionYes
Input current
from supply voltage 1L+, max.100 mA
Address area
Addressing volume
Outputs100 byte
Inputs100 byte
Digital inputs
Number/binary inputs16
Input voltage
Type of input voltageDC
Rated value, DC24 V
for signal "0"-30 to +5 V
for signal "1"13 to 30 V
Input current
for signal "1", typ.3 mA
Input delay (for rated value of input voltage)
for standard inputs
at "0" to "1", min.3 ms
at "0" to "1", max.3 ms
Cable length
Cable length unshielded, max.1000 m
Digital outputs
Number/binary outputs16
Functionality/short-circuit strengthYes
Limitation of inductive shutdown voltage toL+ (-55 to -60 V)
Lamp load, max.5 W
Controlling a digital inputYes
Output current
for signal "1" permissible range for 0 to 60 °C, min.7 mA
for signal "0" residual current, max.0.5 mA
Output delay with resistive load
0 to "1", max.0.5 ms
1 to "0", max.1.3 ms
Switching frequency
with resistive load, max.100 Hz
with inductive load, max.2 Hz
on lamp load, max.10 Hz
Aggregate current of outputs (per group)
Digital inputs / Number of inputs that can be driven in parallel / all mounting positions
up to 60 °C, max.2 A
Cable length
Cable length unshielded, max.1000 m
Encoder
Connectable encoders
2-wire BEROSYes
permissible quiescent current (2-wire BEROS), max.1.5 mA
Interfaces
Interface physics, RS 485Yes
Interface physics, FOCNo
Supports protocol for PROFINET IO
Transmission rate, max.12 Mbit/s
PROFIBUS DP
Cable length, max.1200 m
PROFIBUS DP, output current, max.80 mA
Transmission procedureRS 485
Direct data exchange (slave-to-slave communication)Yes
Protocols
Supports protocol for PROFINET IONo
Protocols (Ethernet)
TCP/IP protocolNo
Further protocols
PROFIBUS DP protocolYes
Isochronous mode
Isochronous modeNo
Interrupts/diagnostics/status information
Alarms
AlarmsNo
Diagnoses
Diagnostic functionsYes
Diagnostics indication LED
Run mode RUN (green)Yes
Group error SF (red)Yes
Status indicator digital output (green)Yes
Status indicator digital input (green)Yes
Monitoring 24 V voltage supply ON (green)Yes
Connection to network LINK (green)No
Transmit/receive RX/TX (yellow)No
Galvanic isolation
between backplane bus and electronicsNo
between supply voltage and electronicsNo
Galvanic isolation digital inputs
Galvanic isolation digital inputsNo
Galvanic isolation digital outputs
Galvanic isolation digital outputsYes
Isolation
Isolation checked with500 V DC
Degree and class of protection
IP20Yes
Connection method
Inputs/outputsScrew-type and spring-loaded terminals, permanent wiring; 3 and 4-wire connection
Dimensions
Width120 mm
Height81 mm
Depth58 mm
Weight
Weight, approx.230 g; EB only

3 Units in Stock


Call for Availability
Price for:  EachMinimum:  1

Target Price

Offer your acceptable price, and we may make you satisfied.Your Target Price

Technical Support

Technical Support

Customer Reviews

Write Review

Customer Q&A Exchange

Ask A Question

Additional Images