SIMATIC DP, DISTRIBUTED I/O ET200X: EM148-FC, FREQUENCY CONVERTER, 1.5KW INTEGR. NETWORK FILTER, CONNECTION TO DESINA, IP65 |
Supply voltage |
Input voltage acc. to VDE |
permissible range, lower limit (AC) | 340 V |
permissible range, upper limit (AC) | 500 V |
Input voltage acc. to UL |
permissible range, upper limit (AC) | 340 V |
permissible range, lower limit (AC) | 480 V |
Line frequency |
permissible range, lower limit | 47 Hz |
permissible range, upper limit | 63 Hz |
Mains filter |
integrated | Yes; Type A (to EN 55011) |
Class A | Yes; to EN 55011 |
Operations for mains buffering time (20 ms) |
Max. current for Ue < 380 V | 1.85 A; at 3.8 A approx. 8 ms |
Max. current for Ue >= 380 V | 2.1 A; at 3.8 A approx. 8 ms |
Input current |
Continuous current on continued looping of the supply voltage, max. | 16 A |
from load voltage L+ (without load), max. | 125 mA |
from backplane bus 5 V DC, typ. | 50 mA |
Output current |
Continuous output current at 40 °C |
at 2 kHz and 4 kHz, max. | 3.8 A; Continuous currents > 1.9 A are only permissible if at least one of the following conditions is met: - Ambient temperature < 50 °C - Input continuous current when looping through the load supply voltage < 8 A |
at 8 kHz, max. | 3 A; Continuous currents > 1.9 A are only permissible if at least one of the following conditions is met: - Ambient temperature < 50 °C - Input continuous current when looping through the load supply voltage < 8 A |
at 16 kHz, max. | 1.45 A |
Continuous output current at 55 °C |
at 2 kHz and 4 kHz, max. | 2.1 A; Continuous currents > 1.9 A are only permissible if at least one of the following conditions is met: - Ambient temperature < 50 °C - Input continuous current when looping through the load supply voltage < 8 A |
at 8 kHz, max. | 1.7 A |
at 16 kHz, max. | 1.05 A |
Power |
Degree of efficiency of the converter, typ. | 97 % |
Power losses |
in intermittent operation, max. | 70 W |
in continuous operation, max. | 42 W |
Interrupts/diagnostics/status information |
Alarms |
Diagnostic alarm | Yes |
Diagnoses |
Diagnostics | Yes |
Diagnostics indication LED |
Group error SF (red) | Yes |
Status indicator STAT (yellow) | Yes |
Monitoring the power supply, power module PWR (green) | Yes |
Drive technology |
Control/mode |
V/f characteristic | Yes |
four quadrants | Yes |
Motor output, cable length max. | 10 m |
Overload capability | 150 %; for 60 s, relative to rated current |
Output frequency, min. | 0 Hz |
Output frequency, max. | 300 Hz |
Output frequency, resolution | 0.01 Hz |
Motor |
Rated motor power at 3 x 400 V AC |
acc. to VDE, max. | 1.5 kW |
acc. to UL, max. | 2 hp |
Power factor (cos phi), min. | 0.7 |
Number of poles | 2, 4 or 6 |
Motor brake | AC (rated voltage according to infeed supply voltage) / max. 1 A |
short-circuit proof | No; internal fuse 4 A provided |
Thermistor | Response range about 4 to 5 kohms; channel-related error message: overload |
Galvanic isolation |
between the load voltages | Yes |
between load voltage and all other switching components | Yes |
Permissible potential difference |
between different circuits | 1500 V AC |
Isolation |
Isolation checked with | 2830 V DC |
Degree and class of protection |
Protection against | Overtemperature in the converter; overtemperature in the motor; overvoltage and undervoltage; short-circuit and ground fault protection; motor stalling protection, no-load protection (interrupt) |
Dimensions |
Width | 120 mm |
Height | 265 mm |
Depth | 181 mm |
Weight |
Weight, approx. | 3 kg |