6ES7147-1AA11-0XB0 ET200X, BM147/CPU, WITH SPS-FUNCTION

Manufacturer:
SIEMENS
Weight:
0.5kg
Product Range:
Automation Systems

Product Information

SIMATIC DP, BASIC MODULE ET200X: BM147-1 CPU, 64KB WORK MEMORY FOR PREPROCESSING WITH INT. PLC FUNCTIONS, INT.PROFIBUS DP SLAVE IF, PROT. IP65/67
Supply voltage
Rated value (DC)24 V; Permissible range: 20.4 to 28.8 V
Reverse polarity protectionNo
Short-circuit protectionYes
Load voltage 2L+
Rated value (DC)24 V; Permissible range: 20.4 to 28.8 V
Reverse polarity protectionNo
Power losses
Power loss, typ.3 W
Memory
Work memory
integrated64 Kibyte; 21 K instructions
expandableNo
Load memory
expandable FEPROM, max.8 Mbyte; can be plugged in as MMC
Backup
presentYes; Guaranteed by MMC (maintenance-free)
CPU processing times
for bit operations, min.0.1 µs
for word operations, min.0.2 µs
for fixed point arithmetic, min.2 µs
for floating point arithmetic, min.3 µs
CPU-blocks
Number of blocks (total)1024; DBs, FCs, FBs
DB
Number, max.511
Size, max.16 Kibyte
FB
Number, max.512; In number range from FB 0 to FB 2047
Size, max.16 Kibyte
FC
Number, max.512; In number band of FC0 to FC2047
Size, max.16 Kibyte
OB
Descriptionsee instruction list
Size, max.16 Kibyte
Nesting depth
per priority class8
additional within an error OB4
Counters, timers and their retentivity
S7 counter
Number256
Retentivity
adjustableYes
presetZ 0 to Z 7
Counting range
lower limit0
upper limit999
IEC counter
presentYes; Number unlimited (limited only by work memory)
TypeSFB
S7 times
Number256
Retentivity
adjustableYes
presetNo retentivity
Time range
lower limit10 ms
upper limit9990 s
IEC timer
presentYes; Number unlimited (limited only by work memory)
TypeSFB
Data areas and their retentivity
retentive data area in total (incl. times, counters, flags), max.all
Flag
Number, max.256 byte
Retentivity availableYes
Retentivity presetMB 0 to MB 15
Number of clock memories8; 1 memory byte
Local data
per priority class, max.510 byte
Address area
I/O address area
Inputs1 Kibyte
Outputs1 Kibyte
Process image
Inputs128 byte
Outputs128 byte
Digital channels
Inputs8192 bits
Outputs8192 bits
Inputs, of which central56 bytes
Outputs, of which central56 bytes
Analog channels
Inputs512 words
Outputs512 words
Inputs, of which central14 words
Outputs, of which central14 words
Time of day
Clock
Hardware clock (real-time clock)Yes
battery-backed and synchronizableYes; Backup time typically 6 weeks (at 40 °C ambient temperature)
Deviation per day, max.10 s
Operating hours counter
Number1
Number/Number range0
Range of values0 to 2^31 hours (when using SFC 101)
Granularity1 hour
retentiveYes; Must be restarted at each restart
Clock synchronization
supportedYes
to MPI, slaveYes
in AS, masterYes
in AS, slaveYes
1st interface
Type of interfaceCoexistent, integrated RS 485 interface
PhysicsRS 485
IsolatedYes
Functionality
MPIYes
DP masterNo
DP slaveYes; active / passive
Point-to-point connectionNo
MPI
Services
PG/OP communicationYes
RoutingNo
Global data communicationYes
S7 basic communicationYes
S7 communicationYes
S7 communication, as serverYes
Transmission rate, max.12 Mbit/s
DP slave
Number of connections12
Services
RoutingNo
S7 communication, as clientNo
S7 communication, as serverNo
Transmission rate, max.12 Mbit/s
Transfer memory
Inputs244 byte
Outputs244 byte
Address area, max.32
User data per address area, max.32 byte
Communication functions
PG/OP communicationYes
Global data communication
supportedYes
Number of GD packets, max.4
Number of GD packets, transmitter, max.4
Number of GD packets, receiver, max.4
Size of GD packets, max.22 byte
Size of GD packet (of which consistent), max.22 byte
S7 basic communication
supportedYes
User data per job, max.76 byte
User data per job (of which consistent), max.76 byte; 76 bytes (with X_SEND or X_RCV); 64 bytes (with X_PUT or X_GET as server)
S7 communication
supportedYes
as serverYes
as clientNo
User data per job, max.180 byte; With PUT/GET
User data per job (of which consistent), max.64 byte
S5-compatible communication
supportedNo
Number of connections
overall12
usable for PG communication
reserved for PG communication1
Adjustable for PG communication, max.11
usable for OP communication
reserved for OP communication1
adjustable for OP communication, max.11
usable for S7 basic communication
Reserved for S7 basic communication10
adjustable for S7 basic communication, max.11
S7 message functions
Number of login stations for message functions, max.12; Depending on the configured connections for PG/OP and S7 basic communication
Process diagnostic messagesYes
simultaneously active Alarm-S blocks, max.40
Test commissioning functions
Status/control
Status/control variableYes
VariablesInputs, outputs, memory bits, DB, times, counters
Number of variables, max.30
of which status variables, max.30
of which control variables, max.14
Forcing
ForcingYes
Force, variablesInputs, outputs
Number of variables, max.10
Status blockYes
Single stepYes
Number of breakpoints2
Diagnostic buffer
presentYes
Number of entries, max.100
adjustableNo
Configuration
Configuration software
STEP 7Yes; V5.2 SP1
Dimensions
Width175 mm
Height110 mm
Depth90 mm
StatusSep 10, 2011

2 Units in Stock


Call for Availability
Price for:  EachMinimum:  1

Target Price

Offer your acceptable price, and we may make you satisfied.Your Target Price

Technical Support

Technical Support

Customer Reviews

Write Review

Customer Q&A Exchange

Ask A Question

Additional Images