SIMATIC DP, ET 200ECO PN, 8 DO 24V DC/1,3A; 8 X M12, DEGREE OF PROTECTION IP67 |
General information |
Vendor identification (VendorID) | 002AH |
Device identifier (DeviceID) | 0306H |
Supply voltage |
Load voltage 1L+ |
Rated value (DC) | 24 V |
permissible range, lower limit (DC) | 20.4 V |
permissible range, upper limit (DC) | 28.8 V |
Reverse polarity protection | Yes |
Load voltage 2L+ |
Rated value (DC) | 24 V |
permissible range, lower limit (DC) | 20.4 V |
permissible range, upper limit (DC) | 28.8 V |
Reverse polarity protection | Yes |
Input current |
from load voltage 1L+ (unswitched voltage) | 4 A |
from load voltage 2L+, max. | 4 A |
Power losses |
Power loss, typ. | 5.5 W |
Digital outputs |
Number/binary outputs | 8 |
In groups of | 4 |
Functionality/short-circuit strength | Yes; Electronic |
Response threshold, typ. | 1.8 A |
Limitation of inductive shutdown voltage to | Typ. (L1+, L2+) -47 V |
Switching capacity of the outputs |
on lamp load, max. | 5 W |
Controlling a digital input | Yes |
Output current |
for signal "1" rated value | 1.3 A; Maximum |
for signal "0" residual current, max. | 1.5 mA |
Parallel switching of 2 outputs |
for increased power | No |
for redundant control of a load | Yes |
Switching frequency |
with resistive load, max. | 100 Hz |
with inductive load, max. | 0.5 Hz |
on lamp load, max. | 1 Hz |
Aggregate current of outputs (per group) |
Digital inputs / Number of inputs that can be driven in parallel / all mounting positions |
up to 60 °C, max. | 3.9 A |
Cable length |
Cable length unshielded, max. | 30 m |
Interfaces |
Transmission procedure | 100BASE-TX |
Transmission rate, max. | 100 Mbit/s |
Supports protocol for PROFINET IO |
Number of PROFINET interfaces | 2 |
Autocrossing | Yes |
Automatic detection of transmission speed | Yes |
Integrated switch | Yes |
PROFINET IO Device |
IRT with the option "high flexibility" supported | Yes |
Prioritized startup supported | Yes |
Protocols |
Supports protocol for PROFINET IO | Yes |
Protocols (Ethernet) |
SNMP | Yes |
DCP | Yes |
LLDP | Yes |
ping | Yes |
arp | Yes |
Interrupts/diagnostics/status information |
Status indicator | Yes; Green LED |
Alarms |
Diagnostic alarm | Yes |
Diagnoses |
Diagnostic functions | Yes |
Diagnostic information readable | Yes |
Monitoring the supply voltage to the electronics | Yes; Green "ON" LED |
Wire break in actuator cable | Yes |
Short circuit | Yes |
Group error | Yes; Red/yellow "SF/MT" LED |
Galvanic isolation |
between the load voltages | Yes |
between load voltage and all other switching components | No |
between Ethernet and electronics | Yes |
Galvanic isolation digital outputs |
between the channels | No |
Permissible potential difference |
between different circuits | 75 VDC / 60 VAC |
Isolation |
tested with |
24 V DC circuits | 500 V |
Interface | 1500 V; According to IEEE 802.3 |
Degree and class of protection |
IP65 | Yes |
IP66 | Yes |
IP67 | Yes |
Connection method |
M12 | Yes |
Dimensions |
Width | 60 mm |
Height | 175 mm |
Depth | 49 mm |
Weight |
Weight | 910 g |