SIMATIC DP, ELECTRONIC MODULES FOR ET200PRO 4 DO DC 24V, 2.0A HIGH FEATURE, CHANNEL DIAGNOSTICS; SHORT CIRCUIT AND WIRE BREAK; INCLUSIVE BUS MODULE CONNECTING MODULE IO 6ES7194-4..00-0AA0 MUST BE ORDERED SEPERATELY |
FH technology |
Module for failsafe applications | No |
Supply voltage |
Load voltage 2L+ |
Rated value (DC) | 24 V |
Short-circuit protection | Yes; per channel, electronic |
Reverse polarity protection | Yes; against destruction; load increasing |
Input current |
from load voltage 2L+ (without load), max. | 40 mA |
from backplane bus 3.3 V DC, max. | 40 mA |
Power losses |
Power loss, typ. | 2.5 W |
Address area |
Address space per module |
with packing | 4 bit |
without packing | 1 byte |
Digital outputs |
Number/binary outputs | 4 |
Functionality/short-circuit strength | Yes; per channel, electronic |
Response threshold, typ. | 3 |
Limitation of inductive shutdown voltage to | 2L+ (-47 V) |
Lamp load, max. | 10 W |
Controlling a digital input | Yes |
Output voltage |
for signal "1", min. | 2L+ (-0.8 V) |
Output current |
for signal "1" rated value | 2 A |
for signal "0" residual current, max. | 0.5 mA |
Parallel switching of 2 outputs |
for increased power | No |
for redundant control of a load | Yes |
Switching frequency |
with resistive load, max. | 100 Hz |
with inductive load, max. | 0.5 Hz |
on lamp load, max. | 1 Hz |
Aggregate current of outputs (per group) |
Digital inputs / Number of inputs that can be driven in parallel / all mounting positions |
up to 55 °C, max. | 4 A |
Load resistance range |
lower limit | 12 Ω |
upper limit | 4 kΩ |
Cable length |
Cable length, shielded, max. | 30 m |
Cable length unshielded, max. | 30 m |
Interrupts/diagnostics/status information |
Substitute values connectable | Yes |
Alarms |
Diagnostic alarm | Yes |
Diagnoses |
Diagnostic functions | Yes |
Diagnostic information readable | Yes |
Wire break | Yes |
Short circuit | Yes |
Diagnostics indication LED |
Group error SF (red) | Yes |
Status indicator digital output (green) | Yes |
Channel error indicator F (red) | Yes |
Parameter |
Diagnosis: wire break | channel by channel |
Diagnosis: short circuit | channel by channel |
Behavior on CPU/Master STOP | channel by channel |
Galvanic isolation |
between backplane bus and all other circuit components | Yes |
between the channels and backplane bus | Yes |
Galvanic isolation digital outputs |
between the channels | No |
between the channels and the backplane bus | Yes |
Permissible potential difference |
between different circuits | 75 VDC / 60 VAC |
Isolation |
Isolation checked with | 500 V DC |
Dimensions |
Width | 45 mm |
Height | 130 mm |
Depth | 35 mm; without terminal module |
Weight |
Weight, approx. | 140 g |