SIMATIC DP, ELECTRON. MODULE F. ET200S, 4 F-DO PROFISAFE, DC 24V/2A, 30 MM WIDTH UP TO CATEGORY 4 (EN954-1) ALSO USEABLE IN PROFINET- NETWORKS WITH IM151-3 HF |
Supply voltage |
Load voltage L+ |
Rated value (DC) | 24 V |
Reverse polarity protection | No |
Input current |
from load voltage L+ (without load), max. | typ. 100 mA |
from backplane bus 3.3 V DC, max. | 28 mA |
Power losses |
Power loss, typ. | 3.5 W |
Digital outputs |
Number/binary outputs | 4 |
Functionality/short-circuit strength | Yes; Electronic |
Limitation of inductive shutdown voltage to | Typ. (2L+) -47 V |
Lamp load, max. | 10 W |
Controlling a digital input | No |
Output voltage |
for signal "1", min. | L+ (-2,0 V), current sourcing switch: L+ (-1,5 V), voltage drop on current sinking switch: max. 0.5 V |
Output current |
for signal "1" rated value | 2 A |
for signal "1" permissible range for 0 to 60 °C, min. | 20 mA |
for signal "1" permissible range for 0 to 60 °C, max. | 2.4 A |
for signal "0" residual current, max. | 0.5 mA; Current-sourcing: max. 0.5 mA; Current sinking: max. 4 mA |
Parallel switching of 2 outputs |
for increased power | No |
for redundant control of a load | No |
Switching frequency |
with resistive load, max. | 30 Hz |
with inductive load, max. | 0.1 Hz |
on lamp load, max. | 10 Hz |
Aggregate current of outputs (per group) |
horizontal installation |
up to 40 °C, max. | 6 A |
up to 55 °C, max. | 5 A |
up to 60 °C, max. | 4 A |
vertical installation |
up to 40 °C, max. | 4 A |
Load resistance range |
lower limit | 12 Ω |
upper limit | 1 kΩ |
Cable length |
Cable length, shielded, max. | 200 m |
Cable length unshielded, max. | 200 m |
Interrupts/diagnostics/status information |
Diagnoses |
Diagnostic functions | Yes |
Wire break | Yes |
Short circuit | Yes |
Diagnostics indication LED |
Group error SF (red) | Yes |
Status indicator digital output (green) | Yes |
Galvanic isolation |
Galvanic isolation digital outputs |
between the channels | No |
between the channels and the backplane bus | Yes |
between the channels and the load voltage L+ | No |
Isolation |
Isolation checked with | 500 V DC |
tested with |
Channels against backplane bus and load voltage L+ | 1500 V AC |
Standards, approvals, certificates |
Highest safety class achievable in safety mode |
acc. to EN 954 | Cat. 4 |
acc. to IEC 61508 | SIL 3 |
Dimensions |
Width | 30 mm |
Height | 81 mm |
Depth | 52 mm |
Weight |
Weight, approx. | 85 g |