SIMATIC DP, POWER MODULE PM-E F PROFISAFE, FOR ET 200S; 24V DC USEABLE FOR INSTALLATIONS WITH GROUNDED REFERENCE POTENTIAL RELAIS FOR FAIL-SAFE SWITCHING OF VOLTAGE BUS P2 UP TO CATEGORY 3 (EN954-1)/ SIL 2 (IEC61508) ALSO USEABLE IN PROFINET- NETWORKS WITH IM151-3 HF |
Supply voltage |
Load voltage L+ |
Rated value (DC) | 24 V |
Reverse polarity protection | No |
Input current |
from load voltage L+ (without load), max. | typ. 100 mA |
from backplane bus 24 V DC, max. | 28 mA |
Current carrying capacity |
Current carrying capacity up to 30 °C, max. | 10 A |
Current carrying capacity up to 40 °C, max. | 8 A |
Current carrying capacity up to 60 °C, max. | 7 A |
Power losses |
Power loss, typ. | 4 W |
Address area |
Address space per module |
without packing | 5 byte; Input and output in each case |
Digital inputs |
Cable length |
Cable length, shielded, max. | 200 m |
Cable length unshielded, max. | 200 m |
Digital outputs |
Number/binary outputs | 1; Relay |
Functionality/short-circuit strength | No |
Lamp load, max. | 100 W |
Controlling a digital input | Yes |
Switching frequency |
with resistive load, max. | 2 Hz |
with inductive load, max. | 0.1 Hz; with inductive load to IEC 947-5-1, 13 DC /15 AC |
on lamp load, max. | 2 Hz |
Relay outputs |
Switching capacity of contacts |
at ohmic load, up to 50 °C, max. | 10 A |
Interrupts/diagnostics/status information |
Diagnoses |
Diagnostic functions | Yes |
Diagnostic information readable | Yes |
Wire break | No |
Short circuit | Yes |
Missing load voltage | Yes |
Diagnostics indication LED |
Rated load voltage PWR (green) | Yes |
Group error SF (red) | Yes |
Status indicator digital output (green) | Yes |
Galvanic isolation |
Galvanic isolation digital outputs |
between the channels | No |
between the channels and the backplane bus | Yes |
between the channels and the load voltage L+ | No |
Isolation |
Isolation checked with | 500 V DC |
tested with |
Channels against backplane bus and load voltage L+ | 500 V DC |
Standards, approvals, certificates |
Highest safety class achievable in safety mode |
acc. to EN 954 | With Std-DO: max. Cat.3, without Std-DO max. Cat.4 depending on configuration |
acc. to IEC 61508 | With Std-DO: Max. SIL 2, without Std-DO max. SIL 3 depending on configuration |
Dimensions |
Width | 30 mm |
Height | 81 mm |
Depth | 52 mm |
Weight |
Weight, approx. | 80 g |
Status | Sep 10, 2011 |