Your cart is empty

6ES7135-4GB52-0AB0 ET200S, EL-MOD., 2AO I, +/-20MA, 4-20MA

Manufacturer:
SIEMENS
Weight:
0.045kg
Product Range:
Automation Systems

Product Information

SIMATIC DP, ELECTRONIC MODULE FOR ET 200S, 2 AO I HIGH SPEED 15 MM WIDE, +/-20 MA; 16 BIT, 4 . .20 MA; 16 BIT CYCLE TIME 0.1 MS WITH LED SF (GROUP FAULT)
Supply voltage
Load voltage L+
Rated value (DC)24 V
Reverse polarity protectionYes
Input current
from load voltage L+ (without load), max.150 mA; With load
from backplane bus 3.3 V DC, max.10 mA
Power losses
Power loss, max.2.4 W; Typical
Address area
Address space per module
Address space per module, max.4 byte
Analog outputs
Number of analog outputs2
Current output, no-load voltage, max.18 V
Cycle time (all channels) max.250 µs
Output ranges, current
-20 to +20 mAYes
4 to 20 mAYes
Connection of actuators
for current output 2-conductor connectionYes
Load impedance (in rated range of output)
with current outputs, max.500 Ω
with current outputs, inductive load, max.1 mH; for TWA 100µs
Destruction limits against externally applied voltages and currents
Current, max.15 mA; Max. 15 V / 5 hours (higher voltages not permissible even briefly)
[nicht versorgt: TAK_ABT299_001_000]
Cable length, shielded, max.200 m; Max. 20 m for TWA 100 µs
Analog value creation
Integrations and conversion time/ resolution per channel
Resolution with overrange (bit including sign), max.16 bit
Settling time
for resistive load0.05 ms
for capacitive load0.05 ms; at a load of up to 500 ohms/100 nF and a max. cable length of 20 m
for inductive load0.05 ms
Errors/accuracies
Output ripple (based on output area, bandwidth 0 to 50 kHz)+/- 0,02 %
Linearity error (relative to output area)+/- 0,03 %; with resistive load
Temperature error (relative to output area)+/- 0,01 %/K
Crosstalk between the outputs, min.-60 dB
Repeat accuracy in settled status at 25 °C (relative to output area)+/- 0,03 %
Operational limit in overall temperature range
Current, relative to output area+/- 0,2 %; Specified value applies to loads from 200 to 350 Ohm, deviating operational limits for loads up to 200 Ohm and from 350 to 500 Ohm with up to 0.4%
Basic error limit (operational limit at 25 °C)
Current, relative to output area+/- 0,1 %; Specified value applies for loads from 200 to 350 ohms, deviating basic error limits for loads up to 200 ohms and from 350 to 500 ohms with up to 0.3%
Isochronous mode
Isochronous modeYes
Interrupts/diagnostics/status information
Substitute values connectableYes
Diagnoses
Diagnostic functionsYes
Diagnostic information readableYes
Wire breakYes
Group errorYes
Diagnostics indication LED
Group error SF (red)Yes
Parameter
Remark7 bytes
Output type/rangedeactivated / +/-20 mA / 4 to 20 mA
Diagnosis: wire breakDisable / enable
Group diagnosticsDisable / enable
Behavior on CPU/Master STOPOutput current and de-energized/substitute a value/keep last value
Galvanic isolation
Galvanic isolation analog outputs
Galvanic isolation analog outputsYes
between the channelsNo
between the channels and the backplane busYes
between the channels and the load voltage L+Yes
Permissible potential difference
between MANA and M internally (UISO)75 VDC / 60 VAC
Isolation
Isolation checked with500 V DC
Dimensions
Width15 mm
Height81 mm
Depth52 mm
Weight
Weight, approx.45 g

1 Units in Stock


Call for Availability
Price for:  EachMinimum:  1

Target Price

Offer your acceptable price, and we may make you satisfied.Your Target Price

Technical Support

Technical Support

Customer Reviews

Write Review

Customer Q&A Exchange

Ask A Question