SIMATIC DP, ELECTRONIC MODULE FOR ET200S, 2 AO U HIGH SPEED, 15 MM WIDTH, +/-10V, +/-5V, 1.. 5V; 16BIT, CYCLE TIME: 0.1 MS WITH LED SF (GROUP FAULT) |
Supply voltage |
Load voltage L+ |
Rated value (DC) | 24 V; From power module |
Reverse polarity protection | Yes |
Input current |
from load voltage L+ (without load), max. | 100 mA |
from backplane bus 3.3 V DC, max. | 10 mA |
Power losses |
Power loss, max. | 2 W |
Address area |
Address space per module |
Address space per module, max. | 4 byte |
Analog outputs |
Number of analog outputs | 2 |
Voltage output, short-circuit protection | Yes |
Voltage output, short-circuit current, max. | 25 mA |
Cycle time (all channels) max. | 0.25 ms |
Output ranges, voltage |
1 to 5 V | Yes |
-10 to +10 V | Yes; +/-5V as well |
Connection of actuators |
for voltage output 2-conductor connection | Yes; Without compensation of the line resistances |
for voltage output 4-conductor connection | Yes |
Load impedance (in rated range of output) |
with voltage outputs, min. | 1 kΩ |
with voltage outputs, capacitive load, max. | 1 µF; 0.1 µF for Twa=0.1 ms |
Destruction limits against externally applied voltages and currents |
Voltages at the outputs towards MANA | 15 V; Max. 15 V for max. 5 hours, 75 V for max. 1 s |
Current, max. | 30 mA; DC |
[nicht versorgt: TAK_ABT299_001_000] |
Cable length, shielded, max. | 200 m; Max. 20 m for TWA 100 µs |
Analog value creation |
Integrations and conversion time/ resolution per channel |
Resolution with overrange (bit including sign), max. | 16 bit; 1 to 5 V: 14 bits, +/-10 V: 15 bit + sign, +/-5 V: 14 bits + sign |
Settling time |
for resistive load | 0.05 ms |
for capacitive load | 0.05 ms |
for inductive load | 0.05 ms |
Errors/accuracies |
Output ripple (based on output area, bandwidth 0 to 50 kHz) | +/- 0,02 % |
Linearity error (relative to output area) | +/- 0,03 % |
Temperature error (relative to output area) | +/- 0,01 %/K |
Crosstalk between the outputs, min. | 60 dB |
Repeat accuracy in settled status at 25 °C (relative to output area) | +/- 0,03 % |
Operational limit in overall temperature range |
Voltage, relative to output area | +/- 0,2 % |
Basic error limit (operational limit at 25 °C) |
Voltage, relative to output area | +/- 0,01 % |
Isochronous mode |
Isochronous mode | Yes |
Interrupts/diagnostics/status information |
Substitute values connectable | Yes; 0 to 65535 (range of values must be within the rated range) |
Diagnoses |
Diagnostic functions | Yes |
Diagnostic information readable | Yes |
Wire break | No |
Short circuit | Yes |
Group error | Yes |
Diagnostics indication LED |
Group error SF (red) | Yes |
Parameter |
Remark | 7 |
Output type/range | deactivated / 1 to 5 V / +/ -10 V / +/- 5 V |
Diagnosis: short circuit | Disable / enable |
Group diagnostics | Disable / enable |
Behavior on CPU/Master STOP | Output current and de-energized/substitute a value/keep last value |
Galvanic isolation |
Galvanic isolation analog outputs |
between the channels | No |
between the channels and the backplane bus | Yes |
between the channels and the load voltage L+ | Yes |
Permissible potential difference |
between MANA and M internally (UISO) | 75 VDC / 60 VAC |
Dimensions |
Width | 15 mm |
Height | 81 mm |
Depth | 52 mm |
Weight |
Weight, approx. | 40 g |