6ES7135-4FB01-0AB0 ET200S, EL-MOD., 2AO U, +/-10V, 1-5V

Manufacturer:
SIEMENS
Weight:
0.04kg
Product Range:
Automation Systems

Product Information

SIMATIC DP, ELECTRONIC MODULE FOR ET 200S, 2 AO U, 15 MM WIDTH, +/-10 V; 13 BIT + SIGN, 1..5V; 12BIT, CYCLE TIME < 1 MS WITH LED SF (GROUP FAULT)
Supply voltage
Load voltage L+
Rated value (DC)24 V; From power module
Reverse polarity protectionYes
Input current
from load voltage L+ (without load), max.130 mA
from backplane bus 3.3 V DC, max.10 mA
Power losses
Power loss, max.2 W
Address area
Address space per module
Address space per module, max.4 byte
Analog outputs
Number of analog outputs2
Voltage output, short-circuit protectionYes
Voltage output, short-circuit current, max.25 mA
Cycle time (all channels) max.1.5 ms
Output ranges, voltage
1 to 5 VYes
-10 to +10 VYes
Connection of actuators
for voltage output 2-conductor connectionYes; Without compensation of the line resistances
for voltage output 4-conductor connectionYes
Load impedance (in rated range of output)
with voltage outputs, min.1 kΩ
with voltage outputs, capacitive load, max.1 µF
Destruction limits against externally applied voltages and currents
Voltages at the outputs towards MANA15 V; max. 15 V continuous; 75 V for max. 1 s (mark to space ratio 1:20)
Current, max.50 mA; DC
[nicht versorgt: TAK_ABT299_001_000]
Cable length, shielded, max.200 m
Analog value creation
Integrations and conversion time/ resolution per channel
Resolution with overrange (bit including sign), max.14 bit; 1 to 5 V: 12 bits, +/-10 V: 13 bits + sign
Settling time
for resistive load0.1 ms
for capacitive load0.5 ms
for inductive load0.5 ms
Errors/accuracies
Output ripple (based on output area, bandwidth 0 to 50 kHz)+/- 0,02 %
Linearity error (relative to output area)+/- 0,02 %
Temperature error (relative to output area)+/- 0,01 %/K
Repeat accuracy in settled status at 25 °C (relative to output area)+/- 0,05 %
Operational limit in overall temperature range
Voltage, relative to output area+/- 0,4 %
Basic error limit (operational limit at 25 °C)
Voltage, relative to output area+/- 0,2 %
Interrupts/diagnostics/status information
Substitute values connectableYes; 0 to 65535 (range of values must be within the rated range)
Diagnoses
Short circuitYes
Group errorYes
Diagnostics indication LED
Group error SF (red)Yes
Parameter
Remark7 bytes
Output type/rangedeactivated / 1 to 5 V / +/ -10 V
Diagnosis: short circuitDisable / enable
Group diagnosticsDisable / enable
Behavior on CPU/Master STOPOutput current and de-energized/substitute a value/keep last value
Galvanic isolation
Galvanic isolation analog outputs
between the channelsNo
between the channels and the backplane busYes
between the channels and the load voltage L+Yes
Permissible potential difference
between MANA and M internally (UISO)75 VDC / 60 VAC
Dimensions
Width15 mm
Height81 mm
Depth52 mm
Weight
Weight, approx.40 g

7 Units in Stock


Call for Availability
Price for:  EachMinimum:  1

Target Price

Offer your acceptable price, and we may make you satisfied.Your Target Price

Technical Support

Technical Support

Customer Reviews

Write Review

Customer Q&A Exchange

Ask A Question

Additional Images