Your cart is empty

6ES7134-7SD51-0AB0 ET200ISP, EL-MOD., 4 AI RTD, PT100/NI100

Manufacturer:
SIEMENS
Weight:
0.23kg
Product Range:
Automation Systems

Product Information

SIMATIC DP, ELECT. SUBMODULE FOR ET200ISP, 4 AI, RTD, FOR CONNECTION OF RESISTANCE THERMOMETER PT100/NI100
Input current
from supply voltage L+, max.22 mA
Power losses
Power loss, typ.0.4 W
Analog inputs
Number of analog inputs4
Cycle time (all channels) max.320 ms; 66 ms basic conversion time x 4 channels with 60 Hz interference frequency suppression; 80 ms basic conversion time x 4 channels with 50 Hz interference frequency suppression
Technical unit for temperature measurement adjustableYes
Input ranges
VoltageNo
CurrentNo
ThermocoupleNo
Resistance thermometerYes
ResistanceYes
Input ranges (rated values), resistance thermometers
Ni 100Yes
Input resistance (Ni 100)2000 kΩ
Pt 100Yes
Input resistance (Pt 100)2000 kΩ
Input ranges (rated values), resistors
0 to 600 ohmsYes; Also 1000 ohms
Input resistance (0 to 600 ohms)1000 kΩ
Resistance thermometer (RTD)
Characteristic linearization
for resistance thermometerYes
Characteristic linearization
ParameterizableYes
[nicht versorgt: TAK_ABT296_001_000]
Cable length, shielded, max.500 m
Analog value creation
Measurement principleintegrating (Sigma-Delta)
Integrations and conversion time/ resolution per channel
Resolution with overrange (bit including sign), max.16 bit
Integration time, parameterizableYes
Basic conversion time, including integration time, ms80 ms at 50 Hz; 66 ms at 60 Hz
additional conversion time for wire break monitoring5
Interference voltage suppression for interference frequency f1 in Hz50 / 60 Hz
Smoothing of measured values
ParameterizableYes; in 4 stages
Step: NoneYes; 1 x cycle time
Step: lowYes; 4 x cycle time
Step: MediumYes; 32 x cycle time
Step: HighYes; 64 x cycle time
Encoder
Connection of signal encoders
for resistance measurement with 2-conductor connectionYes
for resistance measurement with 3-conductor connectionYes
for resistance measurement with 4-conductor connectionYes
Errors/accuracies
Linearity error (relative to input area)+/- 0.015 %
Temperature error (relative to input area)+/- 0.02 %
Crosstalk between the inputs, min.-50 dB
Repeat accuracy in settled status at 25 °C (relative to input area)+/- 0.01 %
Operational limit in overall temperature range
Resistance-type thermometer, relative to input area+/- 0.15 %; Applies to resistances standard +/- 0.8K climatic +/- 0.3K
Basic error limit (operational limit at 25 °C)
Resistance-type thermometer, relative to input area+/- 0.1 %; Applies to resistances standard +/- 0.5 K climatic +/- 0.2 K
Interference voltage suppression for f = n x (fl +/- 1%), fl = interference frequency
Series mode interference (peak value of interference < rated value of input range), min.70 dB
Common mode interference, min.90 dB
Interrupts/diagnostics/status information
Alarms
Diagnostic alarmYes
Limit value alarmYes
Diagnoses
Diagnostic information readableYes
Wire breakYes
Short circuitYes
Group errorYes
Diagnostics indication LED
Group error SF (red)Yes
Galvanic isolation
Galvanic isolation analog inputs
between the channelsNo
between the channels and the backplane busYes
between the channels and the load voltage L+Yes; Channels and power bus
Standards, approvals, certificates
CE markYes
Use in hazardous areas
Type of protection acc. to EN 50020 (CENELEC)II2 G (1) GD Ex ib[ia] IIC T4 and I M2 Ex ib[ia] I
Type of protection acc. to KEMA04 ATEX 1247
Dimensions
Width30 mm
Height129 mm
Depth136.5 mm
Weight
Weight, approx.230 g

1 Units in Stock