SIMATIC DP, ELECTRONIC MODULE ET 200S: 2AI RTD HIGH FEATURE, 15 MM WIDTH, 15BIT + SIGN ACCURACY +/- 0.1%, FOR 2-/3-/-4- WIRE SENSORS, WITH INTERNAL COMPENSATION OF THE WIRE RESISTOR, WITH LED SF (GROUP FAULT)
Supply voltage
Load voltage L+
Rated value (DC)24 V; From power module
Reverse polarity protectionYes
Input current
from load voltage L+ (without load), max.30 mA
from backplane bus 3.3 V DC, max.10 mA
Power losses
Power loss, typ.0.6 W
Address area
Address space per module
Address space per module, max.4 byte
Analog inputs
Number of analog inputs2
permissible input voltage for voltage input (destruction limit), max.9 V
Constant measurement current for resistance-type transmitter, typ.1.25 mA
Cycle time (all channels) max.Number of active channels per module x basic conversion time
Technical unit for temperature measurement adjustableYes
Input ranges
VoltageYes
CurrentNo
ThermocoupleYes
Resistance thermometerYes
ResistanceYes
Input ranges (rated values), resistance thermometers
Cu 10Yes
Input resistance (Cu 10)10 MΩ
Ni 100Yes
Input resistance (Ni 100)10 MΩ
Ni 1000Yes
Input resistance (Ni 1000)10 MΩ
Ni 120Yes
Input resistance (Ni 120)10 MΩ
Ni 200Yes
Input resistance (Ni 200)10 MΩ
Ni 500Yes
Input resistance (Ni 500)10 MΩ
Pt 100Yes
Input resistance (Pt 100)10 MΩ
Pt 1000Yes
Input resistance (Pt 1000)10 MΩ
Pt 200Yes
Input resistance (Pt 200)10 MΩ
Pt 500Yes
Input resistance (Pt 500)10 MΩ
Input ranges (rated values), resistors
0 to 150 ohmsYes
Input resistance (0 to 150 ohms)10 MΩ
0 to 300 ohmsYes
Input resistance (0 to 300 ohms)10 MΩ
0 to 600 ohmsYes
Input resistance (0 to 600 ohms)10 MΩ
0 to 3000 ohmsYes
Input resistance (0 to 3000 ohms)10 MΩ
Resistance thermometer (RTD)
Characteristic linearization
for resistance thermometerPtxxx, Nixxx
Characteristic linearization
ParameterizableYes; for Ptxxx, Nixxx
Temperature compensation
internal temperature compensationYes
Cable length
Cable length, shielded, max.200 m
Analog value creation
Measurement principleintegrating (Sigma-Delta)
Integrations and conversion time/ resolution per channel
Resolution with overrange (bit including sign), max.16 bit; for Pt100, Ni100, Ni120, Pt200, Ni200, Pt 500, Ni 500, Pt1000, Ni1000, Cu10: 15 bits + sign; for 150, 300, 600, 3000 ohms: 15 bits; for PTC: 1 bits
Integration time, ms16.7 / 20 ms
Interference voltage suppression for interference frequency f1 in Hz60 / 50 Hz
Conversion time (per channel)Basic conversion time incl. integration time: 50 / 60 ms; additional conversion time for diagnostics of wire break test: 5 / 5 ms; additional conversion time for line compensation with 3-wire connection: 50 / 60 ms
Smoothing of measured values
ParameterizableYes; In four stages by means of digital filtering
Step: NoneYes; 1 x cycle time
Step: lowYes; 4 x cycle time
Step: MediumYes; 32 x cycle time
Step: HighYes; 64 x cycle time
Encoder
Connection of signal encoders
for resistance measurement with 2-conductor connectionYes
for resistance measurement with 3-conductor connectionYes; internal compensation of the line resistances
for resistance measurement with 4-conductor connectionYes
Errors/accuracies
Linearity error (relative to input area)+/- 0,01 %
Temperature error (relative to input area)+/- 0,0009 %/K
Crosstalk between the inputs, min.-50 dB
Repeat accuracy in settled status at 25 °C (relative to input area)+/- 0,05 %
Operational limit in overall temperature range
Resistance-type thermometer, relative to input areaResistance-type transmitter: +/-0.1%; Pt100, Pt200, Pt500, Pt1000 standard: +/-1.0 K; Pt100, Pt200, Pt500, Pt1000 climate: +/-0.25 K; Ni100, Ni120, Ni200, Ni500, Ni1000 standard and climate: +/-0.4 K; Cu10 +/-1.5 K
Basic error limit (operational limit at 25 °C)
Resistance-type thermometer, relative to input areaResistance-type transmitter: +/-0.05%; Pt100, Pt200, Pt500, Pt1000 standard: +/-0.6 K; Pt100, Pt200, Pt500, Pt1000 climate: +/-0.13 K; Ni100, Ni120, Ni200, Ni500, Ni1000 standard and climate: +/-0.2 K; Cu10 +/-1 K
Interference voltage suppression for f = n x (fl +/- 1%), fl = interference frequency
Series mode interference (peak value of interference < rated value of input range), min.70 dB
common mode voltage (USS < 2.5 V) , min.90 dB
Isochronous mode
Isochronous modeNo
Interrupts/diagnostics/status information
Diagnoses
Wire breakYes
Group errorYes
Overflow/underflowYes
Diagnostics indication LED
Group error SF (red)Yes
Parameter
Remark7 bytes
Diagnosis: wire breakDisable / enable
Measurement type/rangeDeactivated/ 150 Ohm / 300 Ohm / 600 Ohm /Pt100/Pt200/Pt500/Pt1000 each standard or climate range / Ni100/Ni120/Ni200/Ni500/Ni1000 each standard or climate range / Cu10 each standard or climate range / PTC
Group diagnosticsDisable / enable
Overflow/underflowDisable / enable
Galvanic isolation
Galvanic isolation analog inputs
between the channelsNo
between the channels and the backplane busYes
between the channels and the load voltage L+Yes
Permissible potential difference
between MANA and M internally (UISO)75 VDC / 60 VAC
Isolation
Isolation checked with500 V DC
Dimensions
Width15 mm
Height81 mm
Depth52 mm
Weight