Your cart is empty

6ES7134-4LB02-0AB0 SIMATIC DP, ELECTRONIC MODULE

Manufacturer:
SIEMENS
Weight:
0.045kg
Product Range:
Automation Systems

Product Information

SIMATIC DP, ELECTRONIC MODULE 2 AI U HIGH FEATURE FOR ET 200S, 15 MM WIDE, CYCLE TIME PER MODULE: 0.5MS, +/-10V; 15 BI + SIGN, +/-5V;15BIT+SIGN, 1..5V; 15BIT, OPERATIONAL LIMITS +/-0.1% WITH LED SF (GROUP FAULT)
Supply voltage
Load voltage L+
Rated value (DC)24 V
Reverse polarity protectionYes
Input current
from load voltage L+ (without load), max.55 mA
from backplane bus 3.3 V DC, max.10 mA
Output voltage
Power supply to the transmitters
presentNo
Power losses
Power loss, typ.0.85 W
Address area
Address space per module
Address space per module, max.4 byte
Analog inputs
Number of analog inputs2
permissible input voltage for voltage input (destruction limit), max.35 V; 35 V continuous; 75 V for max. 1 ms
Cycle time (all channels) max.0.5 ms; 0.5 ms for 2 channels without noise suppression, 18 / 21 ms per channel with noise suppression
Input ranges
VoltageYes
CurrentNo
ThermocoupleNo
Resistance thermometerNo
ResistanceNo
Input ranges (rated values), voltages
1 to 5 VYes
Input resistance (1 to 5 V)800 kΩ
-10 V to +10 VYes
Input resistance (-10 V to +10 V)800 kΩ
-5 V to +5 VYes
Input resistance (-5 V to +5 V)800 kΩ
Cable length
Cable length, shielded, max.200 m
Analog value creation
Integrations and conversion time/ resolution per channel
Resolution with overrange (bit including sign), max.16 bit; 0 to 5 V: 15 bits, +/-10 V: 16 bits, +/-5 V: 16 bits
Integration time, parameterizableYes
Interference voltage suppression for interference frequency f1 in Hz60 / 50 Hz / no
Conversion time (per channel)0.04 ms; Without noise suppression 17/20 ms per channel with error
Smoothing of measured values
ParameterizableYes; In 4 stages: 1 x, 4 x, 16 x, 32 x cycle time
Step: NoneYes; 1 x
Step: lowYes; 4 x
Step: MediumYes; 16 x
Step: HighYes; 32 x
Encoder
Connection of signal encoders
for voltage measurementYes
Errors/accuracies
Linearity error (relative to input area)+/- 0,01 %
Temperature error (relative to input area)+/- 0,003 %/K
Crosstalk between the inputs, min.-100 dB
Repeat accuracy in settled status at 25 °C (relative to input area)+/- 0,01 %
Operational limit in overall temperature range
Voltage, relative to input area+/- 0,1 %; 0.2% without interference frequency suppression
Basic error limit (operational limit at 25 °C)
Voltage, relative to input area+/- 0,05 %; 0.1% without interference frequency suppression
Interference voltage suppression for f = n x (fl +/- 1%), fl = interference frequency
Series mode interference (peak value of interference < rated value of input range), min.90 dB
common mode voltage (USS < 2.5 V) , min.100 dB
Isochronous mode
Isochronous modeYes
Interrupts/diagnostics/status information
Alarms
Hardware interruptYes
Diagnoses
Diagnostic functionsYes
Wire breakYes; Measuring range 1 to 5 V only
Group errorYes
Overflow/underflowYes
Diagnostics indication LED
Group error SF (red)Yes
Parameter
Remark12 bytes, 4 bytes in compatibility mode
Measurement type/rangedeactivated / +/-5 V / 1 to 5 V / +/-10 V
Group diagnosticsDisable / enable
Overflow/underflowDisable / enable
Galvanic isolation
Galvanic isolation analog inputs
between the channelsNo; however, increased permissible potential difference between the inputs.
between the channels and the backplane busYes
between the channels and the load voltage L+Yes
Permissible potential difference
between the inputs (UCM)140 V DC/100 V AC
Isolation
Isolation checked with500 V DC
Dimensions
Width15 mm
Module width, max.15 mm
Height81 mm
Depth52 mm
Weight
Weight, approx.45 g
StatusSep 14, 2011

2 Units in Stock


Call for Availability
Price for:  EachMinimum:  1

Target Price

Offer your acceptable price, and we may make you satisfied.Your Target Price

Technical Support

Technical Support

Customer Reviews

Write Review

Customer Q&A Exchange

Ask A Question

Additional Images