6ES7134-4JB01-0AB0 ET200S, EL-MOD., 2AI TC, +/-80MV, 15BIT

Manufacturer:
SIEMENS
Weight:
0.04kg
Product Range:
Automation Systems

Product Information

SIMATIC DP, ELECTRONIC MODULE FOR ET 200S, 2 AI TC STANDARD, 15 MM WIDE, 15 BIT + SIGN +/-80MV; CHARACTERISTICS LINEARIZATION FOR THERMOELEMENTS OF: B, E, J, K, L, N, R, S, T TYPES, CYCLE TIME 65 MS/CHANNEL WITH LED SF (GROUP FAULT)
Supply voltage
Load voltage L+
Rated value (DC)24 V; From power module
Reverse polarity protectionYes
Input current
from load voltage L+ (without load), max.30 mA
from backplane bus 3.3 V DC, max.10 mA
Power losses
Power loss, typ.0.6 W
Address area
Address space per module
Address space per module, max.4 byte
Analog inputs
Number of analog inputs2
permissible input voltage for voltage input (destruction limit), max.10 V; Permanent
Cycle time (all channels) max.Number of active channels per module x basic conversion time
Technical unit for temperature measurement adjustableNo
Input ranges
VoltageYes
ThermocoupleYes
Input ranges (rated values), voltages
-80 mV to +80 mVYes
Input resistance (-80 mV to +80 mV)1 MΩ
Input ranges (rated values), thermoelements
Type BYes
Input resistance (Type B)1 MΩ
Type EYes
Input resistance (Type E)1 MΩ
Type JYes
Input resistance (type J)1 MΩ
Type KYes
Input resistance (Type K)1 MΩ
Type LYes
Input resistance (Type L)1 MΩ
Type NYes
Input resistance (Type N)1 MΩ
Type RYes
Input resistance (Type R)1 MΩ
Type SYes
Input resistance (Type S)1 MΩ
Type TYes
Input resistance (Type T)1 MΩ
Characteristic linearization
ParameterizableYes; Type B, E, J, K, L, N, R, S, T to IEC 584
Temperature compensation
internal temperature compensationNot possible
external temperature compensation with compensations socketYes; possible, one external compensating box per channel
Cable length
Cable length, shielded, max.50 m
Analog value creation
Measurement principleintegrating
Integrations and conversion time/ resolution per channel
Resolution with overrange (bit including sign), max.16 bit; 15 bits + sign
Integration time, parameterizableYes
Integration time, ms16.7 / 20 ms
Interference voltage suppression for interference frequency f1 in Hz60 / 50 Hz
Conversion time (per channel)65 s; 55 / 65 ms (additional 20 ms on activated wire-break test)
Smoothing of measured values
ParameterizableYes; In four stages by means of digital filtering
Step: NoneYes; 1 x cycle time
Step: lowYes; 4 x cycle time
Step: MediumYes; 32 x cycle time
Step: HighYes; 64 x cycle time
Encoder
Connection of signal encoders
for voltage measurementYes
Errors/accuracies
Linearity error (relative to input area)+/- 0,01 %
Temperature error (relative to input area)+/- 0,005 %/K
Crosstalk between the inputs, min.-50 dB
Repeat accuracy in settled status at 25 °C (relative to input area)+/- 0,05 %
Operational limit in overall temperature range
Voltage, relative to input area+/- 0,6 %
Basic error limit (operational limit at 25 °C)
Voltage, relative to input area+/- 0,4 %
Interference voltage suppression for f = n x (fl +/- 1%), fl = interference frequency
Series mode interference (peak value of interference < rated value of input range), min.70 dB
common mode voltage (USS < 2.5 V) , min.90 dB
Isochronous mode
Isochronous modeNo
Interrupts/diagnostics/status information
Diagnoses
Diagnostic functionsYes; Can be read out
Diagnostic information readableYes
Wire breakYes; A break in the wire is only detected for thermocouples
Group errorYes
Overflow/underflowYes
Diagnostics indication LED
Group error SF (red)Yes
Parameter
Remark4 bytes
Diagnosis: wire breakDisable / enable (wire break is detected only in thermocouples)
Measurement type/rangeDeactivated/ +/- 80 mV/ TC-EL Type T (Cu-CuNi)/ TC-EL Type K (NiCr-Ni)/ TC-EL Type B (PtRh-PtRh)/ TC-EL Type c (Wer-Wer) TC-EL Type N (NiCrSi-NiSi)/ TC-EL Type E (NiCr-CuNi)/ TC-EL Type R (PtRh-Pt)/ TC-EL Type S (PtRh-Pt)/ TC-EL Type J (Fe-Cu-Ni)/ TC
Group diagnosticsDisable / enable
Overflow/underflowDisable / enable
Comparison pointnone / RTD
Comparison point numberNone / 1 / 2 / 3 / 4 / 5 / 6 / 7 / 8
UnitCelsius
Galvanic isolation
Galvanic isolation analog inputs
between the channelsNo
between the channels and the backplane busYes
between the channels and the load voltage L+Yes
Permissible potential difference
between inputs and MANA (UCM)2 V AC PP
between MANA and M internally (UISO)75 VDC / 60 VAC
Isolation
Isolation checked with500 V DC
Dimensions
Width15 mm
Height81 mm
Depth52 mm
Weight
Weight, approx.40 g
StatusSep 14, 2011

4 Units in Stock


Call for Availability
Price for:  EachMinimum:  1

Target Price

Offer your acceptable price, and we may make you satisfied.Your Target Price

Technical Support

Technical Support

Customer Reviews

Write Review

Customer Q&A Exchange

Ask A Question