Your cart is empty

6ES7134-0KH01-0XB0 SIMATIC S5/S7, ANALOG

Manufacturer:
SIEMENS
Weight:
0.55kg
Product Range:
Automation Systems

Product Information

SIMATIC DP, ELECTRONIC MODULE ANALOG, FOR ET 200B, W=160MM, 8AI (THERMOCOUPLES) OR 4AI (PT100); 12 BIT
Supply voltage
Rated value (DC)24 V; Value at t < 0.5 s: 35 V
permissible range, lower limit (DC)18.5 V
permissible range, upper limit (DC)30.2 V
Input current
Digital outputs
from load voltage L+, max.80 mA; Logic
Power losses
Power loss, typ.2 W
Hardware configuration
Rack
Required terminal blockTB8
Analog inputs
Number of analog inputs8; 8 voltage inputs/thermocouples or 4 Pt100, Ni100
permissible input voltage for voltage input (destruction limit), max.32 V
Input ranges
VoltageYes
ThermocoupleYes
Resistance thermometerYes
ResistanceYes
Input ranges (rated values), voltages
-1 V to +1 VYes
Input resistance (-1 V to +1 V)10 Ω
-250 mV to +250 mVYes
Input resistance (-250 mV to +250 mV)10 Ω
-500 mV to +500 mVYes
Input resistance (-500 mV to +500 mV)10 Ω
-80 mV to +80 mVYes
Input resistance (-80 mV to +80 mV)10 Ω
Input ranges (rated values), thermoelements
Type EYes
Type JYes
Type KYes
Type LYes
Type NYes
Type RYes
Type TYes
Type UYes
Input ranges (rated values), resistance thermometers
Ni 100Yes
Pt 100Yes
Input ranges (rated values), resistors
0 to 150 ohmsYes
0 to 300 ohmsYes
0 to 48 ohmsYes
0 to 600 ohmsYes
Thermocouple (TC)
for thermocouplesType E, J, K, L, N, T, U
[nicht versorgt: TAK_ABT296_001_000]
Cable length, shielded, max.100 m
Analog value creation
Measurement principleIntegrating voltage/time conversion
Integrations and conversion time/ resolution per channel
Resolution with overrange (bit including sign), max.12 bit; Two's complement
Integration time, parameterizableYes; 2.5/ 16.67/ 20/ 100 ms
Basic conversion time, including integration time, ms8 / 35 / 42 / 200
additional conversion time for wire break monitoring10/10/10/10 ms
Interference voltage suppression for interference frequency f1 in Hz400/50/60/10 Hz
Encoder
Connection of signal encoders
for resistance measurement with 2-conductor connectionYes
for resistance measurement with 4-conductor connectionYes
Errors/accuracies
Linearity error (relative to input area)+/- 0.05 %
Temperature error (relative to input area)+/- 0.005 %/K
Crosstalk between the inputs, min.50 dB; At 50/60 Hz
Repeat accuracy in settled status at 25 °C (relative to input area)+/- 0.05 %
Operational limit in overall temperature range
Voltage, relative to input area+/- 1 %; At 80 mV; +/-0.6 % from 250 to 1000 mV
Impedance, relative to input area+/- 1 %
Basic error limit (operational limit at 25 °C)
Voltage, relative to input area+/- 0.6 %; at 80 mV; +/-0.4% from 250 to 1000 mV
Impedance, relative to input area+/- 0.6 %
Interference voltage suppression for f = n x (fl +/- 1%), fl = interference frequency
Series mode interference (peak value of interference < rated value of input range), min.40 dB
Common mode interference, min.70 dB; Upp < 3 V
Interfaces
PROFIBUS DP
Transmission rate, max.12 Mbit/s
Communication functions
Bus protocol/transmission protocolPROFIBUS DP
Interrupts/diagnostics/status information
Alarms
Diagnostic alarmYes; Parameterizable
Limit value alarmYes; Parameterizable, channels 0 and 2
Diagnoses
OverrangeYes; Overrange
Wire break in signal transmitter cableYes; For Pt 100, Ni 100, R, +/- -80 mV, thermocouples type E, J, K, L, N, T, U (parameterizable)
Diagnostics indication LED
Bus fault BF (red)Yes
Run mode RUN (green)Yes
Galvanic isolation
between electronic block and PROFIBUS DPYes
Galvanic isolation analog inputs
Galvanic isolation analog inputsNo
Permissible potential difference
between the inputs (UCM)max. +/- 1 V
between inputs and MANA (UCM)max. +/- 1 V
Ambient conditions
Operating temperature
horizontal installation, min.0 °C
horizontal installation, max.60 °C; 40°C for other mountings
Air pressure
permissible range, min.795 hPa
permissible range, max.1080 hPa
Relative humidity
Operation, min.15 %
Operation, max.95 %; RH class 2 in accordance with IEC 1131-2
Vibrations
Operation, checked according to IEC 60068-2-6Yes; IEC 68, Part 2-6; 10 to 57 Hz; (constant amplitude 0.075 mm); 57 to 150 Hz; (constant acceleration 1 g)
Shock test
checked according to IEC 60068-2-27Yes; IEC 68, Part 2-27; half-sine, 15 g, 11 ms
Degree and class of protection
IP20Yes
Connection method
Inputs/outputsScrew-type and spring-loaded terminals, permanent wiring; 3 and 4-wire connection
Dimensions
Width160 mm; EB and TB
Height130 mm; EB and TB
Depth60 mm; EB and TB
Weight
Weight, approx.550 g; EB and TB

1 Units in Stock