SIMATIC DP, ELECTRONIC MODULE ANALOG, FOR ET 200B, W=160MM, 8AI (THERMOCOUPLES) OR 4AI (PT100); 12 BIT |
Supply voltage |
Rated value (DC) | 24 V; Value at t < 0.5 s: 35 V |
permissible range, lower limit (DC) | 18.5 V |
permissible range, upper limit (DC) | 30.2 V |
Input current |
Digital outputs |
from load voltage L+, max. | 80 mA; Logic |
Power losses |
Power loss, typ. | 2 W |
Hardware configuration |
Rack |
Required terminal block | TB8 |
Analog inputs |
Number of analog inputs | 8; 8 voltage inputs/thermocouples or 4 Pt100, Ni100 |
permissible input voltage for voltage input (destruction limit), max. | 32 V |
Input ranges |
Voltage | Yes |
Thermocouple | Yes |
Resistance thermometer | Yes |
Resistance | Yes |
Input ranges (rated values), voltages |
-1 V to +1 V | Yes |
Input resistance (-1 V to +1 V) | 10 Ω |
-250 mV to +250 mV | Yes |
Input resistance (-250 mV to +250 mV) | 10 Ω |
-500 mV to +500 mV | Yes |
Input resistance (-500 mV to +500 mV) | 10 Ω |
-80 mV to +80 mV | Yes |
Input resistance (-80 mV to +80 mV) | 10 Ω |
Input ranges (rated values), thermoelements |
Type E | Yes |
Type J | Yes |
Type K | Yes |
Type L | Yes |
Type N | Yes |
Type R | Yes |
Type T | Yes |
Type U | Yes |
Input ranges (rated values), resistance thermometers |
Ni 100 | Yes |
Pt 100 | Yes |
Input ranges (rated values), resistors |
0 to 150 ohms | Yes |
0 to 300 ohms | Yes |
0 to 48 ohms | Yes |
0 to 600 ohms | Yes |
Thermocouple (TC) |
for thermocouples | Type E, J, K, L, N, T, U |
[nicht versorgt: TAK_ABT296_001_000] |
Cable length, shielded, max. | 100 m |
Analog value creation |
Measurement principle | Integrating voltage/time conversion |
Integrations and conversion time/ resolution per channel |
Resolution with overrange (bit including sign), max. | 12 bit; Two's complement |
Integration time, parameterizable | Yes; 2.5/ 16.67/ 20/ 100 ms |
Basic conversion time, including integration time, ms | 8 / 35 / 42 / 200 |
additional conversion time for wire break monitoring | 10/10/10/10 ms |
Interference voltage suppression for interference frequency f1 in Hz | 400/50/60/10 Hz |
Encoder |
Connection of signal encoders |
for resistance measurement with 2-conductor connection | Yes |
for resistance measurement with 4-conductor connection | Yes |
Errors/accuracies |
Linearity error (relative to input area) | +/- 0.05 % |
Temperature error (relative to input area) | +/- 0.005 %/K |
Crosstalk between the inputs, min. | 50 dB; At 50/60 Hz |
Repeat accuracy in settled status at 25 °C (relative to input area) | +/- 0.05 % |
Operational limit in overall temperature range |
Voltage, relative to input area | +/- 1 %; At 80 mV; +/-0.6 % from 250 to 1000 mV |
Impedance, relative to input area | +/- 1 % |
Basic error limit (operational limit at 25 °C) |
Voltage, relative to input area | +/- 0.6 %; at 80 mV; +/-0.4% from 250 to 1000 mV |
Impedance, relative to input area | +/- 0.6 % |
Interference voltage suppression for f = n x (fl +/- 1%), fl = interference frequency |
Series mode interference (peak value of interference < rated value of input range), min. | 40 dB |
Common mode interference, min. | 70 dB; Upp < 3 V |
Interfaces |
PROFIBUS DP |
Transmission rate, max. | 12 Mbit/s |
Communication functions |
Bus protocol/transmission protocol | PROFIBUS DP |
Interrupts/diagnostics/status information |
Alarms |
Diagnostic alarm | Yes; Parameterizable |
Limit value alarm | Yes; Parameterizable, channels 0 and 2 |
Diagnoses |
Overrange | Yes; Overrange |
Wire break in signal transmitter cable | Yes; For Pt 100, Ni 100, R, +/- -80 mV, thermocouples type E, J, K, L, N, T, U (parameterizable) |
Diagnostics indication LED |
Bus fault BF (red) | Yes |
Run mode RUN (green) | Yes |
Galvanic isolation |
between electronic block and PROFIBUS DP | Yes |
Galvanic isolation analog inputs |
Galvanic isolation analog inputs | No |
Permissible potential difference |
between the inputs (UCM) | max. +/- 1 V |
between inputs and MANA (UCM) | max. +/- 1 V |
Ambient conditions |
Operating temperature |
horizontal installation, min. | 0 °C |
horizontal installation, max. | 60 °C; 40°C for other mountings |
Air pressure |
permissible range, min. | 795 hPa |
permissible range, max. | 1080 hPa |
Relative humidity |
Operation, min. | 15 % |
Operation, max. | 95 %; RH class 2 in accordance with IEC 1131-2 |
Vibrations |
Operation, checked according to IEC 60068-2-6 | Yes; IEC 68, Part 2-6; 10 to 57 Hz; (constant amplitude 0.075 mm); 57 to 150 Hz; (constant acceleration 1 g) |
Shock test |
checked according to IEC 60068-2-27 | Yes; IEC 68, Part 2-27; half-sine, 15 g, 11 ms |
Degree and class of protection |
IP20 | Yes |
Connection method |
Inputs/outputs | Screw-type and spring-loaded terminals, permanent wiring; 3 and 4-wire connection |
Dimensions |
Width | 160 mm; EB and TB |
Height | 130 mm; EB and TB |
Depth | 60 mm; EB and TB |
Weight |
Weight, approx. | 550 g; EB and TB |