SIMATIC DP, ELECTRONIC BLOCK FOR ET 200L, 8 DI/8 DO, AC 120 V/1A WITH 1 POINT COMMON |
General information |
Vendor identification (VendorID) | 0029h |
Supply voltage |
120 V AC | Yes |
permissible range, lower limit (AC) | 74 V |
permissible range, upper limit (AC) | 132 V |
Reverse polarity protection | Yes |
Line frequency |
Frequency of the supply voltage | 47 Hz |
Frequency of the supply voltage | 63 Hz |
Mains buffering |
Mains buffering, min. | 20 ms |
Load voltage L+ |
Rated values | 120 VAC (permissible range: 74 VAC to 132 VAC, 47 to 63 Hz) |
Input current |
from supply voltage L+, max. | 130 mA |
Power losses |
Power loss, typ. | 12.2 W |
Hardware configuration |
Rack |
Required terminal block | TB 16L AC |
Digital inputs |
Number/binary inputs | 8 |
Input characteristic curve acc. to IEC 1131, Type 2 | Yes |
Input voltage |
Type of input voltage | |
Rated value, AC | 120 V |
for signal "0" | 0 to 20 V AC |
for signal "1" | 74 to 132 V AC |
Input current |
for signal "0", max. (permissible quiescent current) | 4 mA; 0 to 4 mA |
for signal "1", typ. | 9 mA; 9 to 27 mA |
Input delay (for rated value of input voltage) |
for standard inputs |
at "0" to "1", min. | 2 ms |
at "0" to "1", max. | 14 ms |
at "1" to "0", min. | 6 ms |
at "1" to "0", max. | 25 µs |
Cable length |
Cable length for NAMUR input, shielded, max. | 1000 m |
Digital outputs |
Number/binary outputs | 8 |
Size of motor starter, max. | Size 4 to NEMA (up to 40 °C); size 3 to NEMA (up to 60 °C) |
Functionality/short-circuit strength | No |
Lamp load, max. | 50 W |
Controlling a digital input | Yes |
Output voltage |
Rated value (AC) | 120 V |
for signal "1", min. | L+ (-1.5 V) |
Output current |
for signal "1" permissible range, min. | 100 mA |
for signal "1" permissible range, max. | 1 A |
for signal "1" permissible range for 0 to 60 °C, max. | 1 A; Pilot mode |
for signal "0" residual current, max. | 2.6 mA |
Output delay with resistive load |
0 to "1", max. | 20 ms |
Parallel switching of 2 outputs |
for increased power | No |
for redundant control of a load | Yes |
Switching frequency |
with resistive load, max. | 10 Hz |
with inductive load, max. | 0.5 Hz |
on lamp load, max. | 1 Hz |
Aggregate current of outputs (per group) |
Digital inputs / Number of inputs that can be driven in parallel / all mounting positions |
up to 60 °C, max. | 1 A |
horizontal installation |
up to 40 °C, max. | 1 A |
up to 60 °C, max. | 0.4 A |
Total current of the outputs (per module) |
all other mounting positions |
up to 40 °C, max. | 0.4 A |
Cable length |
Cable length, shielded, max. | 1000 m |
Cable length unshielded, max. | 600 m |
Encoder |
Connectable encoders |
2-wire BEROS | Yes |
Interfaces |
PROFIBUS DP |
Transmission rate, max. | 6000 Mbit/s; kbit/s |
SYNC capability | Yes |
FREECE capability | Yes |
Direct data exchange (slave-to-slave communication) | Yes; Transmitter (for digital outputs and hybrid modules ET 200L: not for L-SC or IM-SC) |
Communication functions |
Bus protocol/transmission protocol | PROFIBUS DP |
Interrupts/diagnostics/status information |
Alarms |
Alarms | No |
Diagnoses |
Diagnostic functions | Yes |
Diagnostics indication LED |
Bus fault BF (red) | Yes |
Status indicator digital output (green) | Yes |
Status indicator digital input (green) | Yes |
Monitoring 24 V voltage supply ON (green) | Yes |
Galvanic isolation |
between PROFIBUS DP and all other circuit components | Yes |
Galvanic isolation digital inputs |
between the channels | Yes |
between the channels and PROFIBUS DP | Yes |
Galvanic isolation digital outputs |
between the channels | Yes |
between the channels and PROFIBUS DP | Yes |
Isolation |
Isolation checked with | 1500 V AC |
Ambient conditions |
Operating temperature |
horizontal installation, min. | 0 °C |
horizontal installation, max. | 60 °C; 40°C for other mountings |
Air pressure |
permissible range, min. | 795 hPa |
permissible range, max. | 1080 hPa |
Relative humidity |
Operation, min. | 5 % |
Operation, max. | 95 %; RH class 2 in accordance with IEC 1131-2 |
Vibrations |
Operation, checked according to IEC 60068-2-6 | Yes; IEC 68, Part 2-6; 10 to 57 Hz; (constant amplitude 0.075 mm); 57 to 150 Hz; (constant acceleration 1 g) |
Shock test |
checked according to IEC 60068-2-27 | Yes; IEC 68, Part 2-27; half-sine, 15 g, 11 ms |
Degree and class of protection |
IP20 | Yes |
Connection method |
Inputs/outputs | Screw-type and spring-loaded terminals, permanent wiring; standard: 2-wire connection, optional: 3 and 4-wire connection |
Dimensions |
Width | 145 mm |
Height | 61 mm |
Depth | 85.5 mm |
Weight |
Weight, approx. | 318 g |