Your cart is empty

6ES7132-4BD00-0AB0 ET200S, EL-MOD., 4DO HF,DC24V, 0.5A,5PCS

Manufacturer:
SIEMENS
Weight:
0.04kg
Product Range:
Automation Systems

Product Information

SIMATIC DP, 5 ELECTRON. MODULES FOR ET 200S, 4 DO HIGH FEATURE DC 24V/0.5A, 15 MM WIDTH DIAGNOSIS SHORT CIRCUIT, SF-LED 5 PIECES PER PACKAGING UNIT
Supply voltage
Reverse voltage protectionYes; when using the same load voltage as on the power module
Load voltage L+
Rated value (DC)24 V; From power module
Reverse polarity protectionYes; polarity reversal can lead to the digital outputs being connected through
Input current
from load voltage L+ (without load), max.5 mA; Per channel
from backplane bus 3.3 V DC, max.10 mA
Address area
Address space per module
with packing4 bit
without packing1 byte
Digital inputs
Cable length
Cable length, shielded, max.1000 m
Cable length unshielded, max.600 m
Digital outputs
Number/binary outputs4
Functionality/short-circuit strengthYes; Per channel
Response threshold, typ.0.7 to 1.5 A
Limitation of inductive shutdown voltage to-55 to -60 V, L+( )
Lamp load, max.5 W
Controlling a digital inputYes
Output voltage
for signal "1", min.L+ (-1 V)
Output current
for signal "1" rated value0.5 A
for signal "1" permissible range for 0 to 60 °C, min.7 mA
for signal "1" permissible range for 0 to 60 °C, max.600 mA
for signal "0" residual current, max.0.3 mA
Output delay with resistive load
0 to "1", max.100 µs
1 to "0", max.300 µs
Parallel switching of 2 outputs
for increased powerNo
for redundant control of a loadYes; per module
Switching frequency
with resistive load, max.100 Hz
with inductive load, max.2 Hz
on lamp load, max.10 Hz
Aggregate current of outputs (per group)
all mounting positions
up to 60 °C, max.2 A
Load resistance range
lower limit48 Ω
upper limit3400 Ω
Cable length
Cable length, shielded, max.1000 m
Cable length unshielded, max.600 m
Isochronous mode
Isochronous modeYes
Interrupts/diagnostics/status information
Diagnoses
Diagnostic functionsYes
Short circuitYes; Module-wise
Diagnostics indication LED
Group error SF (red)Yes; SF-LED (red)
Status indicator digital output (green)Yes; Per channel
Galvanic isolation
Galvanic isolation digital outputs
between the channelsNo
between the channels and the backplane busYes
Isolation
Isolation checked with500 V DC
Dimensions
Width15 mm
Height81 mm
Depth52 mm
Weight
Weight, approx.40 g

2 Units in Stock


Call for Availability
Price for:  EachMinimum:  1

Target Price

Offer your acceptable price, and we may make you satisfied.Your Target Price

Technical Support

Technical Support

Customer Reviews

Write Review

Customer Q&A Exchange

Ask A Question