SIMATIC DP, DIGITAL ELECTRONIC SUBMODULE FOR ET200B W=235MM, 16DO, 120/230V AC,0.5A |
Input current |
from supply voltage L1, max. | 150 mA |
Power losses |
Power loss, max. | 11 W |
Hardware configuration |
Rack |
Required terminal block | TB6/AC |
Digital outputs |
Number/binary outputs | 16 |
Size of motor starter, max. | Size 3 to NEMA |
Functionality/short-circuit strength | No |
Lamp load, max. | 25 W |
Controlling a digital input | Yes |
Output voltage |
Rated value (AC) | 120/230 V AC |
Output current |
for signal "1" permissible range for 0 to 60 °C, min. | 0.5 A; in groups of 4 |
for signal "0" residual current, max. | 1.3 mA |
Parallel switching of 2 outputs |
for logic links | Yes |
for increased power | No |
for redundant control of a load | Yes |
Switching frequency |
with resistive load, max. | 10 Hz |
with inductive load, max. | 0.5 Hz |
on lamp load, max. | 1 Hz |
Cable length |
Cable length unshielded, max. | 600 m |
Interfaces |
PROFIBUS DP |
Transmission rate, max. | 12 Mbit/s |
Communication functions |
Bus protocol/transmission protocol | PROFIBUS DP |
Interrupts/diagnostics/status information |
Diagnostics indication LED |
Bus fault BF (red) | Yes |
Run mode RUN (green) | Yes |
Status indicator digital output (green) | Yes |
Galvanic isolation |
between electronic block and PROFIBUS DP | Yes; 500 V DC to the logic, 1500 V AC to connecting terminals |
Galvanic isolation digital outputs |
Galvanic isolation digital outputs | Yes; Optocoupler |
between the channels, in groups of | 4 |
Ambient conditions |
Operating temperature |
horizontal installation, min. | 0 °C |
horizontal installation, max. | 60 °C; 40°C for other mountings |
Air pressure |
permissible range, min. | 795 hPa |
permissible range, max. | 1080 hPa |
Relative humidity |
Operation, min. | 15 % |
Operation, max. | 95 %; RH class 2 in accordance with IEC 1131-2 |
Vibrations |
Operation, checked according to IEC 60068-2-6 | Yes; IEC 68, Part 2-6; 10 to 57 Hz; (constant amplitude 0.075 mm); 57 to 150 Hz; (constant acceleration 1 g) |
Shock test |
checked according to IEC 60068-2-27 | Yes; IEC 68, Part 2-27; half-sine, 15 g, 11 ms |
Degree and class of protection |
IP20 | Yes |
Connection method |
Inputs/outputs | Screw-type and spring-loaded terminals, permanent wiring; 3 and 4-wire connection |
Dimensions |
Width | 235 mm; EB and TB |
Height | 130 mm; EB and TB |
Depth | 60 mm; EB and TB |
Weight |
Weight, approx. | 805 g; EB and TB |