6ES7131-0HF00-0XB0 SIMATIC S5/S7, DIGITAL

Manufacturer:
SIEMENS
Weight:
0.811kg
Product Range:
Automation Systems

Product Information

SIMATIC DP, DIGITAL ELECTRONIC SUBMODULE, FOR ET 200B, W=235MM, 16DI, 120/230V AC
Input current
Rated value at 120 V AC6.5 mA; at 60 Hz
Rated value at 230 V AC10.5 mA; at 50 Hz
from supply voltage L1, max.60 mA
Power losses
Power loss, typ.6 W; at 230 V; 4.5 W at 120 V
Hardware configuration
Rack
Required terminal blockTB6/AC
Digital inputs
Number/binary inputs16
Input characteristic curve acc. to IEC 1131, Type 1Yes
Input voltage
Type of voltage / of the input voltage
Rated value, AC120/230 V AC
for signal "0"0 to 40 V
for signal "1"79 to 264 V
Input current
for signal "1", typ.3 mA; 3 to 16 mA
Input delay (for rated value of input voltage)
for standard inputs
at "0" to "1", min.0 ms
at "0" to "1", max.25 ms
Cable length
Cable length unshielded, max.600 m
Encoder
Connectable encoders
2-wire BEROSNo
permissible quiescent current (2-wire BEROS), max.2 mA
Interfaces
PROFIBUS DP
Transmission rate, max.12 Mbit/s
Communication functions
Bus protocol/transmission protocolPROFIBUS DP
Interrupts/diagnostics/status information
Diagnostics indication LED
Bus fault BF (red)Yes
Run mode RUN (green)Yes
Status indicator digital input (green)Yes
Galvanic isolation
between electronic block and PROFIBUS DPYes; 500 V DC to the logic, 1500 V AC to connecting terminals
Galvanic isolation digital inputs
Galvanic isolation digital inputsYes; Optocoupler
between the channels, in groups of4
Ambient conditions
Operating temperature
horizontal installation, min.0 °C
horizontal installation, max.60 °C; 40°C for other mountings
Air pressure
permissible range, min.795 hPa
permissible range, max.1080 hPa
Relative humidity
Operation, min.15 %
Operation, max.95 %; RH class 2 in accordance with IEC 1131-2
Vibrations
Operation, checked according to IEC 60068-2-6Yes; IEC 68, Part 2-6; 10 to 57 Hz; (constant amplitude 0.075 mm); 57 to 150 Hz; (constant acceleration 1 g)
Shock test
checked according to IEC 60068-2-27Yes; IEC 68, Part 2-27; half-sine, 15 g, 11 ms
Degree and class of protection
IP20Yes
Connection method
Inputs/outputsScrew-type and spring-loaded terminals, permanent wiring; 3 and 4-wire connection
Dimensions
Width235 mm; EB and TB
Height130 mm; EB and TB
Depth60 mm; EB and TB
Weight
Weight, approx.811 g; EB and TB

1 Units in Stock