DS1E-X FOR ET200S HIGH FEATURE DIRECT STARTER SETTING RANGE 0.3...3A MECHANICAL SWITCHING ELEKTRONIC CONTACTOR AC-3/TO 1.1KW/400V EXPANDABLE FOR BRAKE CONTROL MODULE 2DI MODULE MOTORSTARTER ES SIGNAL FROM CIRCUIT-BREAKER PARAMETERIZABLE |
General technical data: |
Product brand name | | Sirius |
product designation | | motor starter ET 200S |
Design of the product | | direct starter |
Product function | | |
| | Yes |
| | Yes |
| | No |
| | Yes |
| | Yes |
Design of the switching contact | | electromechanical |
Product component / outlet for enine brake | | Yes |
Trip class | | CLASS 10 and 20 adjustable |
Type of assignement | | 2 |
Product equipment | | |
- brake control with 230 V AC
| | No |
- brake control with 24 V DC
| | No |
- brake control with 180 V DC
| | No |
- brake control with 500 V DC
| | No |
Product extension / braking module for brake control | | Yes |
Impulse voltage resistance / rated value | kV | 6 |
Insulation voltage / rated value | V | 500 |
Active power loss / typical | W | 9 |
Maximum permissible voltage for safe disconnection / between main circuit and auxiliary circuit | V | 400 |
Item designation | | |
- according to DIN EN 61346-2
| | Q |
- according to DIN 40719 extendable after IEC 204-2 / according to IEC 750
| | A |
Type of mounting | | Can be plugged into terminal module |
Depth | mm | 150 |
Height | mm | 290 |
Width | mm | 65 |
Main circuit: |
Operating voltage | | |
| V | 400…500 |
Adjustable response current | | |
- of the current-dependent overload release
| A | 0.3…3 |
Service power | | |
- at AC-3 / at 400 V / rated value
| kW | 1.1 |
- for three-phase servomotors / at 400 V / at 50 Hz
| | |
| kW | 0.1…1.1 |
Breaking capacity limit short-circuit current (lcu) / at 400 V / rated value | kA | 50 |
Design of the short-circuit protection | | circuit-breakers |
Number of poles / for main current circuit | | 3 |
Type of the motor protection | | solid-state |
Mechanical operating cycles as operating time / of the main contacts / typical | | 100,000 |
Control circuit: |
Type of voltage / of the controlled supply voltage | | DC |
Control supply voltage / 1 | | |
| V | 24…24 |
Control supply voltage / 1 / for DC | | |
| V | 20.4…28.8 |
Supply voltage: | | |
Type of voltage / of supply voltage | | DC |
Supply voltage / 1 | | |
| V | 24…24 |
Supply voltage / 1 / for DC | | |
| V | 20.4…28.8 |
Ambient conditions: |
Protection class IP | | IP20 |
Ambient temperature | | |
| °C | 0…60 |
| °C | -40…70 |
| °C | -40…70 |
Relative humidity | | |
| % | 5…95 |
Resistance against vibration | | 2g |
Resistance against shock | | 5g / 11 ms |
Degree of pollution | | 3 at 400 V, 2 at 500 V according to IEC60664 (IEC61131) |
Installation altitude / at a height over sea level / maximum | m | 2,000 |
Built in orientation | | vertical, horizontal |
Communication: | | |
Protocol / will be supported | | |
| | Yes |
| | Yes |
| | No |
Design of the interface / PROFINET protocol | | Yes |
Design of the electrical connection | | |
- of the communication interface
| | via backplane bus |
- for communication transmission
| | via backplane bus |
Connections: | | |
Number of digital inputs | | 2 |
Number of sockets | | |
- for digital input signals
| | 0 |
- for digital output signals
| | 0 |
Product function | | |
- digital inputs parameterizable
| | Yes |
- digital outputs parameterizable
| | No |
Design of the electrical connection | | |
- 1 / for digital input signals
| | using control module |
- 2 / for digital input signals
| | using control module |
- at the manufacturer-specific device interface
| | plug |
| | screw-type terminals |
| | screw-type terminals |
- for main energy transmission
| | via energy bus |
- for supply voltage infeed
| | via backplane bus |
- for supply voltage transmission
| | via backplane bus |
| | screw-type terminals |
EMC: | | |
Conductor-bound parasitic coupling BURST / according to IEC 61000-4-4 | | 2 kV on voltage supply, inputs and outputs |
Conductor-bound parasitic coupling conductor-earth SURGE / according to IEC 61000-4-5 | | 2 kV (U > 24 V DC) |
Conductor-bound parasitic coupling conductor-conductor SURGE / according to IEC 61000-4-5 | | 1 kV (U > 24 V DC) |
Field-bound parasitic coupling / according to IEC 61000-4-3 | | 80 MHz ... 1 GHz 10 V/m, 1.4 GHz ...2 Hz 3 V/m, 2 GHz ... 2.7 GHz 1 V/m |
Verification of suitability | | CE / UL / CSA / CCC |
|