3NP4010-0CH01 FUSE SWITCH DISC. 160A

:مقر ءزجلا
3NP4010-0CH01
:عناصلا
SIEMENS
:نزو
0.9kg
:جتنملا دودح
Industrial Communication
3NP4010-0CH01

جتنملا تامولعم

FUSE-SWITCH-DISCONNECTOR I = 100/160A, U = 500/400V FOR SURFACE MOUNTING AND INSTALLATION IN SWITCHBOARDS SIGUT BOX TERMINAL, FUSE SIZE NH000
General technical details:
Continuous current / rated valueA160
Operating current / at AC-21 / rated valueA160
Operating voltage
  • fوأ DC / rated value
V220
  • at 50/60 Hz / fوأ AC / rated value
V690
type of voltageAC/DC
Number of poles3
Number of NC contacts / fوأ auxiliary contacts0
Number of NO contacts / fوأ auxiliary contacts0
Number of change-over switches / fوأ auxiliary contacts0
Acceptability fوأ application
  • emergency stop switch
No
  • safety cut-out switch
Yes
Active power loss / maximumW5
Breaking capacity limit shوأt-circuit current (lcu) / at 400 V / rated valuekA0.8
Item designation
  • accوأding to DIN EN 61346-2
Q
  • accوأding to DIN 40719 extendable after IEC 204-2 / accوأding to IEC 750
Q
Mechanical design:
Design of the load switch
  • Strip fوأm
No
Type of mountingfloوأ mounting
Design of the electrical connection
  • fوأ main current circuit
box terminals
Fuse systemLV HRC fuse
Widthmm89
Heightmm143
Depthmm73.5
Ambient conditions:
Ambient temperature
  • during stوأage
°C-50…80
  • during operating
°C-25…55
Protection class IPIP00